1
Simply easy! TM XUSL2E/4E light curtains Pilot light ? How to provide a signal to a pilot light or to a PLC input
2
Telemecanique Sensors 2 - Technical support – April 17 th, 2015 XUSL2E/4E light curtains ●Alternative to supply a pilot light or a PLC signaling input ●No additional output integrated into the light curtain to provide such electrical signal ●External light or PLC input, how to energize it : ●Either by using directly the NC contact available in the FSD (final switch device) connected to the OSSD. ●Either by an external component, when a safety interface is used If it is associated to a safety relay, if possible use an optional output of this relay (or of the monitoring unit). Please check current compatibility of this output with the light or PLC input.
3
Telemecanique Sensors 3 - Technical support – April 17 th, 2015 XUSL2E/4E light curtains ●Pilot light ●Recommended colour According to the table 4 of the IEC 60204-1 standard (electrical equipment of machines), the yellow (or orange) colour is recommended. In this european standard, the red colour is dedicated for an action required in case of hazardous situation. ●Possible product selection in dia22mm ●Plastic pilot light in XB5A range (version integrated into XY2CE switch) ●Metal pilot light in XB4B range ●Monolithic plastic pilot light in XB7 range
4
Telemecanique Sensors 4 - Technical support – April 17 th, 2015 XUSL2E/4E light curtains ●Pilot light ●Examples of light units ●XB5AV ●XB7EV
5
Telemecanique Sensors 5 - Technical support – April 17 th, 2015 XUSL2E/4E light curtains ●How to supply the light in the stand-alone solution ●From the 2 nd NC contact of the CAD32* auxiliary contactor, with linked contacts ●Possible option : NC contact available on the instantaneous auxiliary contact block of the contactor
6
Telemecanique Sensors 6 - Technical support – April 17 th, 2015 XUSL2E/4E light curtains ●How to supply the light in the stand-alone solution ●K1 contactor detail, CAD32* used ●The light indicates the machine stop 0V +24Vdc K1 OSSD1 K1 K2 restart XUSL receiver
7
Telemecanique Sensors 7 - Technical support – April 17 th, 2015 XUSL2E/4E light curtains ●How to supply the light, in case of safety interface association ●From the XPS safety relay, using an auxiliary NC contact. Attached XPSAK example using the auxiliary NC output.