Introducing GAC’s New Line of Intelligent Generator Set Controllers
2
The InteliSys Stand-By, Prime Mover (single and multiple set), and Parralel to Utility (single and multiple set) Applications Features: 320 x 240 LCD 16 / 14 Discrete Inputs and Outputs (Configurable) Expandable to 128 / 70 4 Analog Inputs (Fuel Level, Coolant Temp., Oil Press.) Expandable to 68 and 1 Analog Output Speed Measurement (Mag Pick-Up) 3 Phase Generator / Utility Voltage 3 Phase Generator / 1 Phase Utility Current Measurement RS232 for Direct Communication Remote Communication (Analog, Internet, and GSM)
3
InteliSys Connections 1 Phase Utility Current 3 Phase Generator Current 3 Phase Generator / Utility Voltage 16 Configurable Discrete Inputs RS232 for direct and modem connection CAN Connection For Extension Modules CAN Connection for Multiple Set Applications
4
InteliSys Connections Cont. Load Sharing Line Governor Output Output for AVRi Interface Analog Output 4 Analog Inputs Mag. Pick-up 2 Relay Outputs (Starter, Fuel Solenoid) 14 Configurable Discrete Outputs 12 or 24 V DC
5
InteliSys’s Versions InteliSys has three versions depending on the application it is intended for: iS-PCM, Power Control For single sets that will parallel with the Utility. iS-PCLSM, Power Control with Load Sharing For multiple sets that may or may not parallel with the Utility. iS-PCLSM-PMS, Load Sharing and Power Management The same as PCLSM with the added features of Volt and PF control.
6
AVR control (needs 18 V AC power supply) Expandable I / O Communications Modem Support (multiple set applications, iG-MU) Internet Support (iG-IB) InteliSys’s Modules
7
iS-BIN16/8 CAN Communication with InteliSys 16 Discrete Inputs and 8 Discrete Outputs Must Assign Controllers Address in InteliSys and on Module Up to 7 of these modules can be Connected to InteliSys
8
AVRi Module Input from PCLSM 18 V AC Power Supply Output for AVR Control DIN Rail Mounting Output Level Adjustment (turn pot)
9
iS-AIN8 CAN Communication with InteliSys 8 Analog Inputs Must Assign Controllers Address in InteliSys and on Module Up to 8 of these modules can be Connected to InteliSys
10
InteliMains: InteliGen With Special Software Mains (= Utility) Circuit Breaker Control –Reverse Synchronization –Vector surge protection (locally required) Power Management - Engine Usage Optimization –Number of running engines: Dependent on required load –Engine starting order: Dependent on running hours Import/Export Control
11
Parallel To Utility & Other Gen Set’s GG iS-PCLSM InteliMains iS-PCLSM
12
InteliSys’s User Friendly Operating Software Free User Friendly PC Format Controller Setpoints Values History
13
Value Screen All Metered Values in Real Time. Screen Selection Metering
14
History Every Action Logged All Values Associated w/ that Action Up to 177 events (FIFO)
15
Controller Same as Keypad Essential Metering Alarm List
16
Setpoints Change any Setpoint Current Value Range Screen Selection Value Acceptable Range for Parameter
17
Customizable Software Parameters Nominal RPM 80 300 Multilingual Texts Overspeed Überdrehzahl Sobrevelocidad Units °C °F; kPa bar psi Controller Operating Mode SPM SSB SPtM MINT MEXT Text Water temp Coolant temp
18
Local connection to the Control System Modem connection to remote monitoring* SMS (Mobile phones) connection* Internet connection* Communications
19
Controller Screens Water Temp 91°C Oil Pressure 5.1bar Fuel level 75% Battery voltage 25.2V Analog Meters Bar Graphs Numeric Values Controller Screens Allow for Similar Interface as WinEdit Software MAINS: 230 228 233V 50.0Hz GENERATOR: 1517RPM 221 223 220V 50.6Hz 872 896 932A 0.98L 183 194 208kW 118kVAr Running in Island
20
Setpoint Adjustment PARAMETERS MF-Start Delay 3s Start Attempts 5 Mains OK-Delay 10s Cooling time 30s Adjustable via iS Keypad Three Level Password Protection
21
History Screens 121 125 124A 62kVAr 27 29 29kW 72 73 71A 48kVAr 17 18 16kW 0 0 0A 0 0 0kW 0 0 0A 0 0 0kW -15 FINISHED HOUR 07:00:00 16.10. -16 GCB CLOSED-ISLAND 06:23:53 16.10. -17 ENGINE START 06:23:49 16.10. -18 MF-MCB OPENED 06:23:44 16.10. 85kW 1503RPM 0.81L 88C 6.1bar 24.9V 84% 50kW 1495RPM 0.72L 25C 5.3bar 24.7V 87% 0kW 0RPM - 22C 0.0bar 25.8V 87% 0kW ORPM - 22C 0.0bar 25.8V 87% M 0 0 0V 0.0Hz G233 227 229V 50.1Hz M 0 0 0V 0.0Hz G230 228 223V 49.8Hz M 0 0 0V 0.0Hz G 0 0 0V 0.0Hz M190 195 201V 48.7Hz G 0 0 0V 0.0Hz History Events Can be Viewed From iS Screens as well as WinEdit Viewed on Multiple Screens
22
Adjustable Delay Settings Five Protective Actions –Warning –Slow stop –Shut-down –Unloading –History Record Reset Function (Horn + Flashing Light) Protection Handling
23
Protections Generator / Utility Over / Under Voltage and Frequency Voltage and Current Asymmetry OverCurrent OverLoad Oil Pressure (two level: warning, shutdown) Coolant Temp. (two level: warning, shutdown) Fuel Level (two level: warning, shutdown) …
24
Summary The InteliSys offers solutions to applications you have never dreamed of. GAC Leaves it up to You to Make the Intelligent Choice!!