1 © 2006 Swagelok Company. IS CAN Bus – CiA WD 103 Update Low Cost, Intrinsically Safe Transducer Bus Enabling NeSSI Gen II Rick Ales and Doug Nordstrom Swagelok Company

2 © 2006 Swagelok Company. Swagelok confidential. For internal use only. MPC Gen II Architecture V T P A NeSSI Device Sample System Flow Sensors Sensor Analyzer Manager SAM IS NeSSI ™ Bus Remote Operator Station Ethernet Analyzer Hazardous Area Class 1 Div 1 (Zone 1)

3 © 2006 Swagelok Company. Swagelok confidential. For internal use only. IS CAN Major Parameters The CAN signaling spec.ISO11898-1,2 & CiA301 Co-cabled 10m maxSingle power source only 3.3V Transceiver1/3 the Power Power bus specification P+F RSD2-PSD-EX4.43 M12 or M8 Connectors2 Power and 2 CAN wires Area ClassificationClass 1 Div 1 (Zone 1) Entity Parameters V OC (V)I SC (A)GroupsC O (uF)L O (uH) A, B (IIC) (Acetylene & Hydrogen) 0.810 9.5Vdc1.0 A C (IIB) (ethylene) 2.440 D (IIA) (propane) 6.480

4 © 2006 Swagelok Company. Swagelok confidential. For internal use only. CiA WD103 Organization Joshua PearlIXXAT Co. Chairman Reiner ZitzmannCAN in AutomationSecretary Swagelok ABB Siemens Texas Instruments Pepperl + Fuchs Turck Parker Hannifin Circor www.smartshs.org

5 www.circortech.com Complete, Modular, Ready Today CIRCOR Tech NeSSi™ Product Development & Market Snapshot Patrick Lowery IFPAC 2007, 1.29.07

6 www.circortech.com Complete, Modular, Ready Today Progress  At present, CIRCOR Tech has built and lab tested several different categories of sample system devices based on the Siemens I 2 C Maxum™ GC Digital Bus  Pressure Sensor  Solenoid Pilot Valve  Fluid temperature probe  Pressure, flow combination sensors  2 nd iteration with IS design circuits are in process for  All the above components, plus  Multi-variable sensor (Pressure, temp, flow)  Low-powered combi-valve for closed loop, IS (Zone 1, Div 1), flow and pressure control  Filter monitoring modules Maxum™ is a trademark of Siemens Energy and Automation

7 www.circortech.com Complete, Modular, Ready Today CIRCOR Tech “NeSSi-Bus” Devices

8 www.circortech.com Complete, Modular, Ready Today Progress  In addition, preparations are being made to test power supply schemes for low powered CAN Bus as per the CiA (CAN in Automation) Intrinsically Safe CAN Bus Working Group  Working network of sensors, valves, and control devices will be online in late Feb according to proposed IS power supply and communication scheme  CIRCOR Tech Core sensing and control modules will have different bus flavors available according to end user or analyzer OEM preference (I2C, CAN Bus, Modbus, RS- 485)  Will be working with CAN and other PLC and/or hybrid controller companies to bring control solutions for retrofit activity outside of smart GC’s

9 www.circortech.com Complete, Modular, Ready Today  Mainstream customers will not adopt a “discontinuous” technology without:  Having the “whole product concept” fulfilled Having the entire core product (s) augmented by EVERYTHING that is needed for the customer to have a compelling reason to buy Distributors or sales people skilled in the new technology Good warranty, strong company, and strong support 2 nd Sources and a Competitive Marketplace  This includes the product (s) along with training, support, manuals, cables, connectors, accessories, additional hardware and software, etc.  Example: One cannot implement an IS CAN Bus solution without a certified IS Power Supply, an IS CAN Bus Isolator Repeater, Special Cabling, Wiring Documentation, and Config. Software What’s Next?

10 www.circortech.com Complete, Modular, Ready Today What’s Next?  Example of IS CAN Bus Network (courtesy of CiA IS CAN Bus working group Needs further development and certifications Being developed

11 www.circortech.com Complete, Modular, Ready Today  What is still needed to fulfill the Whole Product Concept for Digital Bus?  More power supply components  Repeaters, Isolators, and Barriers  Connectors and Cabling  Configuration Management Software  A Standalone SAM (Sensor Actuator Manager) for non-GC analyzer applications with HMI  What is needed for overall NeSSi system success?  End users must “change behavior” in order to adopt a discontinuous technology innovation  At a certain point, innovation must cease to allow customer to digest what is currently being offered. Otherwise, they are waiting on the next revision What’s Next?

12 www.circortech.com Complete, Modular, Ready Today  Examples of what to expect  Digital bus system maintenance will require software and hardware interaction between analyzer and sample system  Could get stuck in information overload mode if streaming data is provided rather than mission critical decision making information  Sample system purge systems go away, potentially exposing the digital devices to concentrated chemical vapors continuously  Compromises may have to be made to make digital bus sensors cost effective in these extreme environments IP65 ratings a necessity, corrosive resistance a must, 85 deg C operation Hot Swap, Plug and play, C1D1, Zone 1 (possibly Zone 0) certifications become necessary Digital devices must be field addressable rather than “software addressable” which means that windows, access ports, must be available Some sort of visual indication of system health would be desirable rather than going back and forth between SHS and analyzer CAN IT ALL BE ACHIEVED COST EFFECTIVELY??? What’s Next?

13 www.circortech.com Complete, Modular, Ready Today  Examples of what to expect, cont.  Energy budgets will become important due to the relatively high cost per milliwatt of special IS power supplies  Terms like “average cost per node”, and “average power per node”, will used to as a technical selling advantages for smart digitally controlled sample systems  Multi-function, multi-variable devices will be leveraged to gather multiple pieces of information with a single bus node, minimizing connection cost  Digital bus node functionality and failure modes (FMEA) will have to be taken into account when performing system design and safety reviews of smart sample systems  Will integrators adopt this responsibility quickly? What’s Next?