Smoke Control Fire-Rated Stairwells Fireproofing of Structural Components Egress Lighting Fire-Resistive Construction Elements Fire and Smoke Dampers Emergency Power Features of Building Fire and Life Safety Alarms Sprinklers Fire-Rated Corridors Exit Access Number of Required Exits Egress Widths Occupant Loads Elevator Recall Fire Rated Doors & Frames
2
Fire Extinguisher Size Requirements Size and Placement For Class A Fires Light (Low) Hazard Occupancy Ordinary (Moderate) Hazard Occupancy Extra (High) Hazard Occupancy Minimum rated single extinguisher 2-A* 4-A† Maximum floor area per unit of A 3000 ft 2 1500 ft 2 1000 ft 2 Maximum floor area for extinguisher 11,250 ft‡ Maximum travel distance to extinguisher 75 ft
3
Fire Extinguisher Placement Requirements Size and placement for class B Hazards Basic Minimum Extinguisher Rating Maximum Travel Distance to Extinguishers ft m Light (low) 5-B 30 9.15 10-B 50 15.25 Ordinary (moderate) 10-B 30 9.15 20-B 50 15.25 Extra (high) 40-B 30 9.15 80-B 50 15.25
4
Additional Resources National Fire Sprinkler Association –http://www.nfsa.orghttp://www.nfsa.org California Association Licensed Services And Fire Equipment –http://www.calsafe.comhttp://www.calsafe.com California Automatic Fire Alarm Association – http://www.cafaa.comhttp://www.cafaa.com