Presentation is loading. Please wait.

Presentation is loading. Please wait.

PRESENTED BY THE ELECTRICAL

Similar presentations


Presentation on theme: "PRESENTED BY THE ELECTRICAL"— Presentation transcript:

1 PRESENTED BY THE ELECTRICAL
4 HOUR 2008 NEC CODE CHANGES PRESENTED BY THE ELECTRICAL TRAINING CENTER IN-SERVICE TRAINING #

2 Article 100, Entire Code Grounding and bonding terms have been redefined and simplified for clarity and improved usability. Bonded (Bonding) – Revised Ground – Revised Grounded (Grounding) – Revised Grounded, Effectively – Deleted Grounding Conductor, Equipment (EGC) – Revised Grounding Electrode – Revised Grounding Electrode Conductor – Revised Ungrounded – New 4/17/2017

3 Photo: IAEI Archives

4 4/17/2017

5

6 Photo: IAEI Archives 4/17/2017

7

8

9 Article 100 – Ground Ground. The earth.
The term ground has been revised and simplified for clarity and improved usability. 4/17/2017

10 Article 100 – Ground The earth 4/17/2017

11

12

13 Article 100 Grounding Electrode
Grounding Electrode. A conducting object through which a direct connection to earth is established. 4/17/2017

14 Photo: IAEI Archives

15

16

17 Article 100 – Kitchen New definition of the term kitchen has been added to Article 100. Kitchen. An area with a sink and permanent facilities for food preparation and cooking. A sink and permanent provisions for food preparation and cooking are required for an area to qualify as a kitchen. 4/17/2017

18 Photo: IAEI Archives

19

20

21

22

23 110.12(A) Unused Openings The words cable or raceway have been deleted to extend the requirements to all unused openings other than those necessary for operation of the equipment. 110.12(A) Unused Openings. Unused openings, other than those intended for the operation of equipment, intended for mounting purposes, or permitted as part of the design for listed equipment shall be closed to afford protection substantially equivalent to the wall of the equipment. Where metallic plugs or plates are used with nonmetallic enclosures, they shall be recessed at least 6 mm (¼ in.) from the outer surface of the enclosure. 4/17/2017

24 Photo: IAEI Archives

25

26

27

28

29 Photo: IAEI Archives

30 Photo: IAEI Archives

31

32

33 Chapter Two Wiring and Protection 4/17/2017

34

35 Photo: IAEI Archives

36

37

38 210.5(C) Ungrounded Conductors
Where a premises wiring system is supplied by more than one nominal voltage system, each branch circuit is required to be identified by phase or line and system. This identification shall be used at all termination, connection, and splice points. The means of identification is required to be permanently posted at each branch-circuit panelboard or similar branch-circuit distribution equipment. 4/17/2017

39 Photo: IAEI Archives

40 Ground-fault circuit interrupter protection requirements apply
to receptacles that are not readily accessible. Applies to dwelling unit garages and unfinished basements, and accessory buildings. 4/17/2017

41 210.8(B) Other Than Dwelling Units
All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in (1) through (5) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors See Code text for exceptions. 4/17/2017

42 Photo: IAEI Archives

43 210.8(B)(5) Sinks Other than Dwelling Units
Receptacles installed within 1.8 m (6 ft) of the outside edge of a sink are required to be protected by ground-fault circuit-interrupter protection. Exception No. 2 to (5): For receptacles located in patient care areas of health care facilities other than those covered under 210.8(B)(1), GFCI protection shall not be required. 4/17/2017

44 Photo IAEI Archives

45 210.8(C) Boat Hoists GFCI protection shall be provided for outlets not exceeding 240 volts that supply boat hoists installed in dwelling unit locations. 4/17/2017

46 Photo: IAEI Archives

47 210.12(B) Dwelling Units Dwelling Units. All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways , or similar rooms or areas shall be protected by a listed arc-fault circuit interrupter, combination-type, installed to provide protection of the branch circuit. Comments from Comment responding to “Explanation of Negative” comments from CMP-2 members on Proposal which expanded AFCI requirements in dwelling unit for the 2008 NEC. Log #2192 NEC-P02 Final Action: Accept in Principle in Part (210.12(B)) _____________________________________________________________ Submitter: Vince Baclawski, National Electrical Manufacturers Association (NEMA) Comment on Proposal No: 2-142 Recommendation: Continue to Accept the Proposal as submitted. Substantiation: As noted in the substantiation, it is time to expand the use of AFCI. This comment is intended to address the comments with the negative votes by Mr. Becker, Mr. Brown, Mr. Nenninger, and Mr. Purvis. Mr. Becker questions the reliability of AFCIs and whether there is enough data on the effectiveness of AFCI to justify expansion. There are over 20,000,000 AFCI in service and the number grows daily. This is a large base and manufacturers are not aware of reliability issues and Mr. Becker does not present any data supporting his claim of a reliability issue nor has he provided any information to the manufacturers supporting this claim. Relative to the effectiveness of AFCI, there are situations where AFCIs are detecting arcing situations and protecting the circuit. The devices are functioning and are effective. Mr. Becker states that substantiation must provide a demonstrable link between the present installation of AFCIs in bedrooms and a reduction of fires before expansion. The effort to quantify a reduction in fires and the use of AFCI will forever be difficult (as it would be with other products) and code making bodies have been careful over the years not to withhold advancements in safety for this type of justification. AFCIs do detect arcing situations that if not detected could develop into dangerous situations where a fire could occur. The branch/feeder devices introduced in the 2002 Code provided a significant improvement in safety and the change to combination devices in 2008 will increase this safety level further. AFCI technology is relatively new and will continue to develop and increase the level of safety. Mr. Becker questions whether AFCIs provide any protection beyond that provided by a standard circuit breaker. AFCI devices function in a range of protection outside of that provided by standard circuit breakers so there is no question that there is additional protection beyond what is provided by a standard circuit breaker. Combination devices function to detect arcing situations well below the handle rating of the circuit breaker. Mr. Becker raised a question about installing GFCIs on branch circuits protected by AFCIs but it is unknown what the issue or question is. GFCIs can be, and have been, installed on the same circuit since AFCIs were introduced. There is no issue and, indeed, some AFCIs have been designed to include 5ma GFCI protection. Mr. Brown’s negative comments indicate that the issue is purely dollars and cents. He does not seem to question that AFCIs provide additional safety, but questions whether the increased safety is worth the cost. It should be noted that home builders took similar positions when GFCI and smoke alarm requirements were introduced. The same argument is occurring presently with sprinkler protection for dwellings. If all of these issues were viewed only as a dollars and cents issues, we would not have many of the safety improvements we have today. If one applied this same type of analysis as justification for overcurrent protection of circuits, you would arrive at the conclusion that there is no justification for having any overcurrent protection - fuse or circuit breaker - on every circuit. A circuit breaker trip in a dwelling is relatively rare and the number of trips relative to the number installed is infinitesimally low. The same type of dollars and cents analysis would likely show that GFCI and smoke detectors were not justified. If homeowner’s insurance was evaluated on the same basis that Mr. Brown uses, the numbers would probably indicate that the cost of insurance far exceeds the losses and, therefore, no one should purchase insurance. Mr. Brown notes that until data is available to indicate that AFCIs are directly related to saving society monetary loss that AFCIs should not be required. That logic would result in codes and standards that would have no safety provisions. Mr. Nenninger questions the timing of expansion. AFCIs have been required in the 2002 and 2005 Code so there is significant experience with the devices (20,000,000+ installed). It is true that the 2008 Code will require a new type of device with expanded safety, but that does not justify not moving forward with expansion of AFCI. Mr. Purvis comments that field problems, manufacturer recalls, nuisance trips, and lack of support are reasons to not include AFCI in the NEC. Relative to field problems there have been some trips with AFCI and while many of these were due to actual arc faults there have been some trips that can be attributed to improper wiring or a specific issue with a connected load. In the instances where there was a question about utilization equipment, AFCI manufacturers have responded to these and made adjustments to the AFCI, if possible and warranted, and the result has been that there are few actual unwanted trip issues reported today. When GFCIs were first introduced, there were numerous complaints of nuisance trips (any trip is a nuisance and many of these were valid trips due to ground faults) but what if GFCI were never added to the Code because of perceived nuisance tripping issues? Relative to recalls, there was a single AFCI recall from one manufacturer. Although this was due to the specific performance of a component and not the AFCI design, the manufacturer responded quickly and effectively. It should also be noted that in this instance the push-to-test function of the AFCI did exactly as it was supposed to do and indicated that the device had a problem with the arc detection function. The idea that a product recall means that the concept should be removed from the market is not logical. None of us would have an automobile today under this concept. The issue of local adoption is indicated as lack of support and, therefore, somehow important in including this in the Code. Local adoption is many times driven for reasons other than safety - e.g., politics - and should not be an issue in what the NEC does. It is also noteworthy that far more jurisdictions have adopted AFCI than those that have not. The need for AFCI in new houses is questioned because of improvements in wiring. Wiring practices do continue to improve, but unintended things happen in new installations. Systems also continue to age and they are often modified. A perfect installation where nothing goes wrong with the wiring and the loads would not need a circuit breaker or fuse to protect the circuit, but it is understood that the system needs protection against various modes of faults that can occur. The AFCI is an extension of this safety. Panel Meeting Action: Accept in Principle in Part Panel Statement: See panel action and statement on Comment 2-85. Ballot Results: Affirmative: 9 Negative: 3 4/17/2017 47

48

49

50

51

52 Photo: IAEI Archives

53 240.24(B) Occupancy The two exceptions have been rewritten into positive text and the section has been arranged to provide a more logical layout for improved clarity and application of the overcurrent device accessibility requirements. When electric service is provided by and continuously supervised by building management personnel, the branch-circuit overcurrent devices supplying guest rooms or guest suites without permanent provisions for cooking shall be permitted to be accessible to only authorized management personnel. 4/17/2017

54 Photo: IAEI Archives

55

56

57

58

59

60

61

62

63 Wiring Methods and Materials
Chapter Three Wiring Methods and Materials 4/17/2017

64

65 Photo: IAEI Archives

66

67 Photo: IAEI Archives

68

69

70

71

72 Photo: IAEI Archives

73 4/17/2017

74 4/17/2017 Photo: IAEI Archives

75 4/17/2017

76 4/17/2017

77 330.10(A)(11) Uses Permitted Type MC cable is permitted for use in wet locations where a corrosion-resistant jacket is provided over the metallic sheath. c. The insulated conductors under the metallic covering are listed for wet locations and a corrosion-resistant jacket is provided over the metallic sheath. 4/17/2017

78 Photo: IAEI Archives

79

80

81

82

83 Photo: IAEI Archives

84 Photo: IAEI Archives

85

86

87 Equipment for General Use
Chapter Four Equipment for General Use 4/17/2017

88 Capable of Being Locked in the Open Position
The rules for required disconnecting means have been revised to address the specific characteristics of disconnects that are capable of being locked in the open position. The provision for adding a lock is required to remain with the switch or circuit breaker whether the lock is installed or not. The provision should be inherent to the equipment or be an accessory feature that is provided by the manufacturer for establishing the locking capability. 4/17/2017

89

90 Photo: IAEI Archives

91 Photo: IAEI Archives

92 Photo IAEI Archives

93

94 406.4(G) Voltage Between Adjacent Devices
A new subdivision (G) covering voltage between adjacent receptacles has been added to Where voltages between adjacent receptacles in ganged enclosures exceed 300, identified and securely fastened barriers are required between the devices. 4/17/2017

95 Photo: IAEI Archives

96 406.8(A) and (B)(1) Damp and Wet Locations
Standard nonlocking receptacles in 125- and 250-volt configurations are required to be listed weather-resistant type. A new second sentence has been added in 406.8(A) and 406.8(B)(1) and a new FPN follows each section. All nonlocking 15- and 20-ampere, 125- and 250-volt receptacles shall be listed weather-resistant type. 4/17/2017

97

98 Photo: IAEI Archives

99

100 Courtesy of Pass & Seymour/Legrand

101

102

103

104

105 410.16 Luminaires in Clothes Closets
(A)(3) Surface-mounted fluorescent or LED luminaires identified as suitable for installation within the storage area. (C)(1) 300 mm (12 in.) for surface-mounted incandescent or LED luminaires…or on the ceiling. (C)(3) 150 mm (6 in.) for recessed incandescent or LED luminaires…or the ceiling. (C)(5) Surface-mounted fluorescent or LED luminaires shall be permitted to be installed in the storage space where identified for this use. 4/17/2017

106 suitable for installations in clothes closets.
Listed LED luminaires suitable for installations in clothes closets. 4/17/2017 Photos: Courtesy Of Ardee Lighting

107 410.30(B)(1) Handhole (1) A pole shall have a handhole not less than 50 mm × 100 mm (2 in. × 4 in.) with a cover suitable for wet locations to provide access to the supply terminations within the pole or pole base. 4/17/2017

108 Photo: IAEI Archives

109 Photo: IAEI Archives

110 4/17/2017

111 Photo: IAEI Archives Thomas and Betts

112 Photo: IAEI Archives

113 Photo: IAEI Archives

114

115 411.3 Listing Required This section has been revised to include a subdivision (A) covering listed systems, and a subdivision (B) covering field assemblies using listed parts. In (B) the luminaires, power supply, and luminaire fittings (including the exposed bare conductors) of an exposed bare conductor lighting system installation shall be listed for use as part of the same identified lighting system. 4/17/2017

116 Photo: IAEI Archives

117

118 422.52 Electric Drinking Fountains
Electric drinking fountains shall be protected with ground-fault circuit-interrupter protection. Bottled water coolers are not affected by this rule. 4/17/2017

119 Photo: IAEI Archives

120

121

122 Photo: IAEI Archives

123

124 480.5 Disconnecting Means A disconnecting means shall be provided for all ungrounded conductors derived from a stationary battery system over 30 volts. The disconnecting means shall be readily accessible and located within sight of the battery system. 4/17/2017

125 Photo: IAEI Archives

126 Chapter Five Special Occupancies 4/17/2017

127 511.2 Major Repair Garage A building or portions of a building where major repairs, such as engine overhauls, painting, body and fender work, and repairs that require draining of the motor vehicle fuel tank are performed on motor vehicles, including associated floor space used for offices, parking, or showrooms. 4/17/2017

128 511.2 Minor Repair Garage A building or portions of a building used for lubrication, inspection, and minor automotive maintenance work, such as engine tune-ups, replacement of parts, fluid changes (e.g., oil, antifreeze, transmission fluid, brake fluid, air conditioning refrigerants), brake system repairs, tire rotation, and similar routine maintenance work, including associated floor space used for offices, parking, or showrooms. 4/17/2017

129 Photo: IAEI Archives

130

131 517.32(C)(3) Alarm and Alerting Systems
Section (C) has been revised to include a new list item (3) under alarm and alerting systems. Mechanical, control, and other accessories, such as dampers and some motors, required for effective life safety shall be permitted to be supplied by the life safety branch. 4/17/2017

132 Photo: IAEI Archives

133

134

135

136 Chapter Six Special Equipment 4/17/2017

137

138 Photo: IAEI Archives

139 Photo: IAEI Archives

140

141 620.21(A)(3)(e) Elevators Flexible Cords and Cables
Flexible cords and cables are permitted in machine rooms or spaces and control rooms or spaces without raceways under the following conditions: They are not longer than 1.8 m (6 ft). They are flame-retardant. They are protected from physical damage. They are part of the elevator equipment or driving machine. 4/17/2017

142

143

144 Photo: IAEI Archives 4/17/2017

145 645.2 Definition Abandoned Supply Circuits and Interconnecting Cables.
Installed supply circuits and interconnecting cables that are not terminated at equipment and not identified for future use with a tag. 4/17/2017

146 Photo: IAEI Archives

147

148 Photo: IAEI Archives

149

150

151

152

153 Protection Hydromassage bathtubs and their associated electrical components shall be on an individual branch circuit(s) and protected by a readily accessible ground-fault circuit interrupter. All 125-volt, single-phase receptacles not exceeding 30 amperes and located within 1.83 m (6 ft) measured horizontally of the inside walls of a hydromassage tub shall be protected by a ground-fault circuit interrupter(s). 4/17/2017

154 Photo: IAEI Archives

155 Photo: IAEI Archives

156

157

158

159

160

161

162 Chapter Seven Special Conditions 4/17/2017

163

164 Photo: IAEI Archives

165

166

167

168 Communications Systems
Chapter Eight Communications Systems 4/17/2017

169

170 800.24 Mechanical Execution of Work
Listed and non-listed securing methods and hardware are permitted to be used with network-powered broadband communications circuits. Cable ties are now recognized as a securing means for NPBCS cables. 4/17/2017

171 Photo: IAEI Archives

172

173

174 800.156 Dwelling Unit Communications Outlet
At least one communications outlet is required to be installed within a dwelling unit. The wiring for this communication outlet shall be routed to the service provider demarcation point of the dwelling unit. 4/17/2017

175 Photo: IAEI Archives

176 Photo: IAEI Archives

177

178 THINK SAFETY THE END


Download ppt "PRESENTED BY THE ELECTRICAL"

Similar presentations


Ads by Google