1 Open Building Information Monitoring
Andrew Krioukov David Culler

2 Previously: Manual Instrumentation
Fed Jiang, Jorge Ortiz, Stephen D.Haggerty, 4/12/11 CPS 2011

3 Cory Hall Sensors & Meters
10 Dent PowerScout electrical meters ModBus, RS-485 2 Power Standards Labs meters Ethernet 2 ION 6200 meters 70 ACME receptacle meters /LoWPAN/IP 4 rooftop solar, temp sensors Obvius steam meter

4 Continuous Commissioning
sMAP: Narrow Waist Personal Feedback Modeling Continuous Commissioning Control Visualization Applications Actuation Location Storage Debugging Authentication JSON, HTTP sMAP CSV, HTTP HTML, HTTP Bacnet/IP ModBus RS-485 Remove Apogee, add later Differing Schemas, Encodings and Transport

5 Sutardja Dai Hall ~140k sq. feet Siemens Apogee BMS WattStopper
BACnet/IP 5886 sense/control points Built up systems set the stage for a new way of collecting building information New buildings such as SDH have extensive instrumentation already, how to tap in? Next: How we accessed the data What we obtained Issues along the way

6 Network Sensors, Actuators Controllers Internet Modem Remote Login
Gateway sMAP Siemens P2 over RS-485 sMAP – homogeneous interface, higher level JSON encoding, extensible schema, human & machine readable BACnet – fixed format, binary encoding, tunneled over IP low level Apogee Server BACnet/IP

7 Network Internet Remote Login Gateway sMAP Remote Login, BACnet/IP
sMAP – homogeneous interface Apogee Server WattStopper Server Modem BACnet/IP

8 BACnet/IP Protocol Schema Methods Devices Objects Types Properties
Discovery Read Write

9 Schema Object Types (50 total): Analog – Float
Device ID Analog – Float Binary – Boolean (e.g. relay state) Multi-state – Enum (e.g. high/med/low) Object ID, Type Num Property ID Property ID Input – Sensor input (e.g. temp) Output – Control output (e.g. valve pos) Value – Variable (e.g. setpoint) Object ID All binary IDs Query by binary ID Schedule

10 Schema Properties (344 total): Units (190 total): PROP_PRESENT_VALUE
PROP_DESCRIPTION PROP_LOCATION PROP_UNITS PROP_SCALE PROP_LOW_LIMIT Units (190 total): Area Electrical Frequency Length Light Mass Mass Flow Power Pressure Temperature Time Torque Velocity Volume Volumetric Flow All binary

11 Data 1358 control settings 2291 meters/sensors 2165 control outputs
Set points, Relays (lights, pumps, etc), Schedules 2291 meters/sensors Power (building, floor, lights, chiller, pumps, etc) Current, voltage, apparent, real, reactive, peak Temp (rooms, chilled water, hot water) Air volume Alarms, Errors 2165 control outputs Dampers, valves, min/max flow, fan speed, PID parameters 72 other

12 Extendable to other Buildings
Center for the Built Environment Other buildings on campus NY Times Building

13 Emergency Lights and Recepticals
Data MSB MS41A (FAB Process Tool) MS41B (FAB Mech)) MD42A EX-6 EX-7 ELEV-4 SCHWP-1 SCHWP-2 CWP-1 CWP-2 PVP-1 PVP-2 PCWP-1 PCWP-2 CHP-1 CDAC-1 CDAC-2 SF-1 SF-2 SF-3 RO/DI Acid Wash RAHU-1 thru 26 ATS-E02 EOCD41B CAC-1 CAC-2 CITRIS Server Room BDF IDF-3 IDF-6 MDC-UPS-Bypass ATS-EL ELCD41A Emergency Lights and Recepticals ELMD47A EF-1 EF-2 EF-3 EF-4 CB4A CL42A CL43A CL44A CL45A CL46A CL47A CR27A CR26A CR25A CR24A CR23A CR22A Gold – electric meters Blue – systems, building components being measured Metering based on physical connections not logical organization

14 Power Breakdown Building Power

15 Issues Naming & Metadata Encoding – binary Schema – fixed Security
Based on underlying physical controllers Encoding – binary Schema – fixed Security Schema – constrained Very fragile – security, Name

16 Security Issues Internet Remote Login Gateway sMAP Remote Login,
BACnet/IP Apogee Server WattStopper Server Modem BACnet/IP

17 Questions

18 Sutardja Dai Building Power
MSA MSB AH1A &1B CAC 1&2 ELEV 4 CITRIS Server Room CHP 2&3 IDF 3-6 SF.2 BDF CH-1 Lev. 2-7 Lighting and Receptacles CP-1 FAB HVAC Load 800kW – 1MW