Problem # 2-3/4 A core-type transformer rated at 37.5 kVA, 2400 – 480 V, and 60 Hz has a core whose mean length is 1.07 m and whose cross-sectional area is 95 cm2. The application of rated voltage causes a magnetic field intensity of 352 A-t/m (rms), and a maximum flux density of T. Determine the number of turns in the primary and secondary. Determine the magnetizing current when operating as a step-up transformer.
2
l=1.07m A=95cm2
3
Number of Turns
4
Magnetizing Current as a Step-Up Transformer