1
UPDATE ON ASSETS IN CESC’S T&D NETWORK
2
CESC’S T&D NETWORK 567 Sq. Km. Area T&D LINE (CKT. KM) 15 nos. 132 kV S/S 88 nos. 33 kV D/S 132 kV - 267 33 kV 6/11 kV
3
ASSETS IN CESC’S T&D NETWORK
YARD EQUIPMENT CABLES & O/H LINES CT PT LA TRANSFORMERS ISOLATOR SWITCHGEAR CAP. BANK BATTERY
4
CABLES & O/H LINES
5
CABLES & O/H LINES CIRCUIT KM : KV CABLES O/H LINES TOTAL 132 186 81
267 33 1102 92 1194 6 & 11 4038 87 4125
6
TYPES & SIZES OF CABLES :
KV CABLE INSULATION CONDUCTOR MATERIAL CROSS-SECTION (SQ. MM) 6 & 11 PILC AL 50, 150, 225 & 300 CU 26, 48, 97, 161 & 645 XLPE 50, 150, 240 & 300 630 33 300 & 400 161, 194 & 645 240, 300, 400 & 1000 500 & 630 132 PILC GAS FILLED 225 150, 161 & 260 400, 630 & 800
7
TRANSFORMERS
8
DISTRIBUTION TRANSFORMER
POPULATION : POWER TRANSFORMER 132/33 kV Class : 33 nos. 33/11-6 kV Class : 169 nos. 6/11 kV, 6/3.3 kV Class : 10 nos. DISTRIBUTION TRANSFORMER 6/0.42 kV Class : 4721 nos. 11/0.42 kV Class : 998 nos.
9
DISTRIBUTION TRANSFORMER
CAPACITY : POWER TRANSFORMER 132/33 kV Class : 50, 55, 75 MVA 33/11-6 kV Class : 7, 10, 15, 16, 20 MVA 6/11, 6/3.3 kV Class : 3, 5, 10, 12.5 MVA DISTRIBUTION TRANSFORMER 6/0.42 kV Class : 100, 200, 315, 400, 600 kVA 11/0.42 kV Class : 315 kVA and 400 kVA
10
TRANSFORMER AGGREGATE CAPACITY : POWER TRANSFORMER 132 kV MVA 33 kV MVA 6/11 kV MVA DISTRIBUTION TRANSFORMER MVA
11
%Z, BIL AND VECTOR GROUP :
TRANSFORMER %Z, BIL AND VECTOR GROUP : POWER TRANSFORMER 132/33 kV Class : 15%, kVp, YNd1 33/11-6 kV Class : 8-11%, 170 kVp, Dyn11 6/11, 6/3.3 kV Class : 10%, kVp, YNyn0d1 DISTRIBUTION TRANSFORMER 6/0.42 kV Class : 4-5%, kVp, Dyn11 11/0.42 kV Class :
12
DISTRIBUTION TRANSFORMER
TAP CHANGER : POWER TRANSFORMER REACTOR TYPE VARIETY RESISTOR TYPE TAP-LINK 132/33 kV 33 8 33/11-6 kV 45 1 121 3 6/11, 6/3.3 kV 10 DISTRIBUTION TRANSFORMER ALL TAP-LINK
13
DISTRIBUTION TRANSFORMER
NEUTRAL EARTHING : POWER TRANSFORMER 132/33 kV Class : HV N – SOLIDLY EARTH LV SIDE – EARTHED THRU ET 33/11-6 kV Class : LV N – SOLIDLY EARTHED FOR 11KV LV N – EARTHED THRU NER FOR 6KV 6/11, 6/3.3 kV Class : HV/LV N – SOLIDLY EARTHED ON THE SECONDARY SIDE. DISTRIBUTION TRANSFORMER 6/0.42 kV Class : LV N SOLIDLY EARTHED 11/0.42 kV Class :
14
POWER TRANSFORMER AGE-GROUP WISE POPULATION (NOS.) : AGE-GROUP
132/33 kV 33/11-6 kV 6-11/0.4 kV 0 to 5 Yrs. 4 18 5 to 10 Yrs. 2 10 to 15 Yrs. 9 37 15 to 20 Yrs. 20 20 to 25 Yrs. 5 12 25 to 30 Yrs. 1 6 30 to 35 Yrs. 35 to 40 Yrs. 40 to 50 Yrs. 50 to 60 Yrs. 31 > 60 Yrs.
15
DISTRIBUTION TRANSFORMERS
16
DISTRIBUTION TRANSFORMERS
O/T : NOS. T/H : NOS. P/T : NOS.
17
DISTRIBUTION TRANSFORMERS
PROTECTION : HT ISOLATOR HT CABLE BOX HRC FUSE ON HT HRC FUSE ON LT
18
DISTRIBUTION TRANSFORMERS
AGE-GROUP WISE POPULATION : TOTAL (nos.) 0-5 YRS (nos.) 5-10 YRS. (nos.) 10-15 YRS. (nos.) 15-20 YRS. (nos.) > 20 YRS. (nos.) 5719 1514 1199 1275 600 1131
19
SWITCHGEAR
20
COMPOUND / OIL FILLED BUSBAR (nos.)
SWITCHGEAR POPULATION : kV Class OUTDOOR CB (nos.) INDOOR SWGR GIS (nos.) AIS (nos.) COMPOUND / OIL FILLED BUSBAR (nos.) 132 80 15 33 115 27 214 66 6 & 11 1037 323
21
SWITCHGEAR INTERRUPTER : kV Class TOTAL (nos.) SF6 (nos.) 132 33
VAC. (nos.) MOCB (nos.) BOCB (nos.) 132 95 81 14 33 422 48 215 6 153 6 & 11 1360 458 463 50 389
22
SPRING-PNEU MATIC (nos.)
SWITCHGEAR OPERATING MECHANISM : kV Class TOTAL (nos.) SPRING (nos.) HYDRAULIC (nos.) PNEUMATIC (nos.) SPRING-PNEU MATIC (nos.) SOLENOID (nos.) 132 95 49 15 9 22 33 422 282 140 6 & 11 1360 1229 131
23
AGE-GROUP WISE POPULATION :
SWITCHGEAR AGE-GROUP WISE POPULATION : kV Class TOTAL (nos.) 0-5 YRS (nos.) 5-10 YRS. (nos.) 10-15 YRS. (nos.) 15-20 YRS. (nos.) > 20 YRS. (nos.) 132 95 11 26 40 8 10 33 422 84 54 72 53 159 6 & 11 1360 195 250 267 162 486
24
CAPACITOR BANK
25
CAPACITOR BANK POPULATION & CAPACITY: 132 kV 33 kV 11 kV 6 kV
NO. OF BANKS 2 13 6 56 COMMON RATING 50 MVAR 15 MVAR 4 MVAR AGGREGATE CAPACITY 100 MVAR 205 MVAR 23 MVAR 192 MVAR
26
CAPACITOR BANK PROTECTION: PROTECTION 132 kV 33 kV 11 kV 6 kV ENCLOSED
27 NON-ENCL. 2 13 29 INTERNAL FUSE 8 40 EXTERNAL FUSE 5 16
27
CAPACITOR BANK AGE-GROUP WISE POPULATION: AGE-GROUP 132 kV 33 kV 11 kV
0 - 5 YRS. 2 8 5 14 YRS. 6 YRS. 1 12 YRS. YRS. 3 YRS. YRS. YRS.
28
BATTERY
29
BATTERY RATING : FOR 132 kV SUBSTATIONS 200 - 250 Ah; 220 Volts
FOR 33/11-6 kV DISTRIBUTION STNS. 40 Ah; 110 Volts
30
BATTERY AGE-GROUP WISE POPULATION : BATTERY 0 - 5 Yrs. 5 - 10 Yrs.
220 5 9 6 2 110 29 49 11