Dynamic Resistance Measurement
As a tool for OLTC Condition assessment
2
The dynamic LTC function provides
Graphical results on a PC that makes easy identification of LTC faults in contact resistance, contact timing, make before break mechanism timing and diverter issues, etc. The LTC does not have to be drained or opened up to achieve this diagnostics.
3
Content of this presentation
Introduction History + WG Tap changers + failures + why test Test method Case studies Good OLTC Bad OLTC Demagnetization
4
What is an OLTC? Standard defines OLTC as
3.14 load tap changer (LTC): A selector switch device, which may include current interrupting contactors, used to change transformer taps with the transformer energized and carrying full load.
5
BASICS What is DRM? Dynamic vs Static
6
Static – dynamic : golf ball
Click for video
7
Dynamic resistance measurement principles
Fast sampling record of the test current Transition time
8
The result is a graph
10
Basic test issues Types of regulation Static vs. dynamic
Types of switching cycle Static vs. dynamic Continuous vs. step by step Why a sudden jump in step by step mode Instrument and computer Presentation of RMO TD
11
Presentation on References and Working group activities
History and purpose History and purpose History and purpose Presentation on References and Working group activities
12
Presentation on DC testing Parameters variation
Testing transformers Presentation on DC testing Parameters variation
13
CASE STUDIES GOOD and BAD Diverter switch Four resistors
Vacuum / One resistor Arcing tap switch Series transformer Reactance type Wavering trace a contact problem
14
Specific types MR type M MR type R, T, D MR type VRC MR type V
MR type VV MR type RMV ABB UZ ABB type VUCGRN ASEA UZB Fuller UK type? English Electric UK type? Waukesha type UZD
15
Interesting cases ELPROM Bulgaria, see > motor current issue SMUD
PG&E Bellehaven Gill Malaysia discontinuity bad spring UK change over switch mis-adjustment MR type RMV gassing
16
Presentations on various problems and issues when testing
17
This section deals with:
Simulation of defects in Ireland Testing OLTC w/o transformer Motor current analysis Neutral operation (2+2/3+1 positions) Open or shorted secondary Main contact vs. Main switching contact Powering the instrument (motor influence)
18
Various problems Runaway – stabilization Small ripple Saturation
High interference signal The ratio of the two Saturation Arcing Regulator Switching oscillations
19
Presentation on removal of remanent magnetism
Demagnetization Presentation on removal of remanent magnetism
20
Conclusions Not for everyone Need to know what one is doing Quick
Straight forward Visible problem indication
21
The end