LINKS SURVIVAL POWER AUX POWER VOLTAGE LIMITS LINE CHARGE MVAR LINE

Similar presentations


Presentation on theme: "LINKS SURVIVAL POWER AUX POWER VOLTAGE LIMITS LINE CHARGE MVAR LINE"— Presentation transcript:

1 LINKS SURVIVAL POWER AUX POWER VOLTAGE LIMITS LINE CHARGE MVAR LINE
CURRENTS AUX POWER

2 Permissible Voltage Limits
Voltage Under Normal Condition Max permissible Voltage at the far end of lines normally kept energized from one end Nominal (kV) Max Min kV 132 148 145 120 245 220 245 200 420 400 420 360 735/765 800 700 800

3 Line Charging MVAR Voltage Conductor used Line Charging MVAR
800kv Class Four Bersimis 2.91MVAR/km 400kV Twin Moose MVAR/km 220kV Zebra MVAR/km

4 Approx. Fault Contribution at HV Bus of GT by:-
Approximate Voltage rise at Recieving end per 100km of uncompensated line 0.75 kV for 132kV S/C panther 1.5 kV for 220kV S/C Zebra 3.0kV for 400kV Twin Moose Approx. Fault Contribution at HV Bus of GT by:- 60 MW ( Hydro) 280 MVA 120 MW (Thermal) 490 MVA 210 MW (Thermal) 735 MVA 500 MW (Thermal) MVA Approx. %Voltage rise/fall at a bus due to removal/addition of a reactor of cap. dQ MVAR = dQ*100 / Fault MVA of the Bus 300 MVAR INJECTION ON A 5000 MVA BUS WOULD CAUSE A 24 KV RISE!

5 Some Important and Useful Thumb Rules
Approx. Line Charging MVAR 132kV Panther: 5 MVAR/100km/ckt 220kV Zebra : 14 MVAR/100km/ckt 400kV Twin Moose: 55 MVAR/100km/ckt Approx. Line Current 132kV: A/MVA 220kV: A/MVA 400kV: A/MVA Approx. Voltage drop per 100kM per 100Amp flow at 0.9 p.f. Lag 5 kV for 132kv S/C Uncompensated Line 3 kV for 220kV S/C Uncompensated Line 1.5kV for 400kV S/C Uncompensated Line

6 SURVIVAL POWER REQUIREMENT
The survival power requirement of 120 MW unit is of the order of KW while the requirement of 210 MW unit is of the order of KW and for 500 MW unit, it is in the order of KW. As a general rule, the survival power requirement would be around % of the unit capacity.

7 AUXILLARY REQUIREMENT
The start up power is the power required for the auxiliaries while the generating unit is restored. The requirement of start up power by various units is as follows : Nuclear & Thermal: 7 to 8% of the unit capacity Hydro : 0.5 to 1% of the unit capacity Gas : 1.5 to 2%of the unit capacity The start up power requirement for starting the thermal units is considerably high as the major auxiliaries like BFP, ID Fan. FD fan, CW pumps etc. are of bigger size and the starting torque is considerable. In case of hydro units, the requirement of start-up power is not significant as there are very few auxiliaries.