Presentation is loading. Please wait.

Presentation is loading. Please wait.

Per Unit Representation Load Flow Analysis Power System Stability Power Factor Improvement Ashfaq Hussain.

Similar presentations


Presentation on theme: "Per Unit Representation Load Flow Analysis Power System Stability Power Factor Improvement Ashfaq Hussain."— Presentation transcript:

1 Per Unit Representation Load Flow Analysis Power System Stability Power Factor Improvement
Ashfaq Hussain

2 8.1 Per Unit Representation
Sometimes it is more convenient to represent the value of current, voltage, impedance, power in per unit(pu) value rather than in Amps, Volts, Ohms, kW. It is unit less. It is the ratio of same dimension Per unit value is the ratio of an actual value to a reference value(Base value) Apu= (Aactual/Abase) Some times per unit quantities is mentioned as per cent quantity by multiplying a factor of 100.

3 pu=actual/base Apu= (Aactual/Abase) Ipu= (Iactual/Ibase)
Vpu= (Vactual/Vbase) Spu= (Sactual/Sbase) Ppu= (Pactual/Sbase) Qpu= (Qactual/Sbase) Zpu= (Zactual/Zbase) Rpu= (Ractual/Zbase) Xpu= (Xactual/Zbase)

4 pu=actual/base If any two of the I, V, Z, S is known, remaining two could be found out. Z= V/I Zbase= (Vbase/Ibase) Zb= (Vb/Ib) Zb= (V2b/Sb) Zpu= (Vpu/Ipu) Spu= VpuI*pu

5 Example 8.1 A 5 KVA 400/200 V, 50Hz, single phase transformer has the primary and secondary leakage reactance each of 2.5 ohm. Determine the total reactance in per unit. Sb= 5000 VA Primary Base Voltage Vb1 = 400 V Secondary Base Voltage Vb2 = 200 V X1e=X1+a2X2 a=N1/N2=400/200=2 X1e=X1+a2X2= * 22 =12.5 ohm

6 Example 8.1 A 5 KVA 400/200 V, 50Hz, single phase transformer has the primary and secondary leakage reactance each of 2.5 ohm. Determine the total reactance in per unit. Xpu= (Xactual/Zbase) Zb1= (V2b1/Sb)=4002/5000=32 ohm Xpu= (Xactual/Zbase)= 12.5/32 = pu X1pu = X1/Zb1 X2pu = X2/Zb2

7 Sudden Test A 7 KVA 1000/250 V, 50Hz, single phase transformer has the primary and secondary leakage reactance each of 5 ohm. Determine the total reactance in per unit.

8 Advantages of per unit representation
ordinary parameters vary considerably with variation of physical size, terminal voltage and power rating etc. while per unit parameters are independent of these quantities over a wide range of the same type of apparatus. In other words, the per unit impedance values for the apparatus of like ratings lie within a narrow range. It provide more meaningful information. The chance of confusion between line and phase values in a three-phase balanced system is reduced. A per unit phase quantity has the same numerical value as the corresponding per unit line quantity regardless of the three-phase connection whether star or delta. Impedances of machines are specified by the manufacturer in terms of per unit values.

9 Advantages of per unit representation
5. The per unit impedance referred to either side of a single-phase transformer is the same. 6. The per unit impedance referred to either side of a three -phase transformer is the same regardless of the connection whether they are ∆-∆, Y-Y or ∆-Y. 7. The computation effort in power system is very much reduced with thee use of per unit quantities. 8. Usually, the per unit quantities being of the order of unity or less can easily be handled with a digital computer. Manual calculation are also simplified. Per unit quantities simply theoretical deduction and give them more generalizes forms.

10 14.1 Load Flow Analysis Load flow analysis is the determination of current, voltage, active and reactive volt-amperes at various points in a power system operating under normal steady-state or static conditions. This is made to plan the best operation and control of the existing system as well as to plan the future expansion to keep pace with the load growth. Information from load flow studies serve to minimize the system losses and to provide a check on the system stability.

11 14.2 Load Flow Problem The variables: Magnitude of the voltage |Vi|
Phase angle of the voltage, δi Active Power, Pi Reactive Volt-amperes, Qi The Buses: Swing Bus or reference bus or slack bus Generator bus or voltage control bus or PV bus Load bus or PQ bus.

12 14.3 Bus Admittance Matrix I1= (V1-V2)/z12 +(V1-V3)/z31 I2= (V2-V1)/z21+(V2-V3)/z32 -I3= (V3-V1)/z31+(V3-V2)/z32

13 I1= (V1-V2)/z12 +(V1-V3)/z31 I1= V1/z12 +V1/z31 -V2/z12 - V3/z31
14.2 Bus Admittance Matrix I1= (V1-V2)/z12 +(V1-V3)/z31 I1= V1/z12 -V2/z12+ V1/z31 - V3/z31 I1= V1/z12 +V1/z31 -V2/z12 - V3/z31 I1= V1y12 +V1y31 -V2y12 - V3y31 I1= (V1-V2)/z12 +(V1-V3)/z31  I1= V1(y12 +y31) -V2y12 - V3y31 I2= (V2-V1)/z21+(V2-V3)/z32 I2= V2(y12 +y23) –V1y12 - V3y23 -I3= (V3-V1)/z31+(V3-V2)/z23 -I3= V3(y31 +y32) –V1y31 – V2y23

14 14.2 Bus Admittance Matrix I1= (V1-V2)/z12 +(V1-V3)/z31  I1= V1(y12 +y31) -V2y12 - V3y31 I2= (V2-V1)/z21+(V2-V3)/z32 I2=–V1y12 + V2(y12 +y23) - V3y23 -I3= (V3-V1)/z31+(V3-V2)/z23 -I3= –V1y31 – V2y23+ V3(y31 +y32) I1= (y12 +y31) -y12 - y31 I2= –y12 + (y12 +y23) - y23 -I3= –y31 –y23 +(y31 +y32)

15 8.2 Bus Admittance Matrix

16 8.2 Bus Admittance Matrix

17 Stability Ability of a system to reach a normal or stable condition after being disturbed. Steady state Gradual and small disturbance Transient Sudden and large distrubance

18 Steady State Satbility
Static stability- Automatic and inherent Dynamic stability- Artificial

19 Stability Limit Stability Limit: the maximum power that can be transferred in a network between sources and load without loss of synchronism. Steady State Stability Limit (Gradual increase or decrease of small load ) Transient Stability Limit (Sudden or large disturbance) Rapidity if disturbance is responsible for loss of synchronism. Transient Stability Limit is lower than Steady State Stability Limit

20 Infinite BUS A bus that has constant voltage and constant frequency regardless the load.

21 Power Angle Curve Pe= Pe max sin δ; is the power angle

22 Swing curves δ versus time in seconds is called the swing curve.

23 Ashfaq Husain Electrical Power Systems Capter 26

24 26.1 Introduction P is real power, S is Apparent power, V is the line voltage, I is the line current and cosφ is the power factor. P=Scosφ cosφ = P/S=P/VI I= P/(Vcosφ) Current is inversely proportional to the power factor. Decrease of power factor will increase the amount of current

25 26.2 Disadvantages of a low power factor
Uneconomical Higher energy loss Poor voltage regulation

26 26.3 Causes of low power factor
Inductive load make the current lagged behind the voltage. Thus a lagging power factor. Motors: 3φ induction motor operates at 0.8 lagging at full load and 0.2 to 0.3 at light load. 1φ operates at 0.6 lagging/ Due to magnetizing current, power factor is low at light load. Arc lamps, electric discharge lamps, industrial heating furnaces, welding equipment operate at low lagging power factor.

27 26.5 Power factor improvement by static capacitor
Figure 26.1 and 26.2

28 26.6 Capacitor rating calculations
Equation 26.1 to 26.10 Example 26.1 to 26.4

29 26.8 Advantages and limitations of static capacitor
Robust Easy to install Occupy little space No need special foundation Practically loss free Easy maintenance Manufactures in very small size Efficient and trouble free solution Over compensation of light load unless special arrangement for automatic switching of the capacitor are provided

30 26.9 Location of the capacitor
Connecting separate capacitor for each load. Alternative: Installing capacitor bank for a group of load. Larger motors needs individual corrections.


Download ppt "Per Unit Representation Load Flow Analysis Power System Stability Power Factor Improvement Ashfaq Hussain."

Similar presentations


Ads by Google