ASEA Model UZBLN 250/300 UZB , One resistor – asymmetrical
3MVA trafo, 44kV tap changer UZB , One resistor – asymmetrical L – Linear regulation N- at neutral 250kV impulse 300A rated
2
Asymmetrical pennant
3
Raising the voltage = up
4
Lowering the voltage = down
5
Linear regulation Linear = adding the turns or subtracting the turns
for DC testing this is important, because : Raising voltage when subtracting turns, you are switching onto position with voltage but lower resistance (due to the voltage drop) and current is higher each position (UP) Peak up - current jumps, when connecting to the point with voltage
6
Lowering - DOWN Lowering voltage Peak down - current drops
when adding turns, you switch onto the position without voltage but higher resistance, and the current is lower each position (DOWN) Peak down - current drops when connecting with point without voltage
7
Peak-up : going up T breaks S makes T makes
8
up T breaks S makes T makes
9
up T breaks S makes T makes
10
up T breaks S makes T makes
11
Peak-down : going down T breaks T makes S breaks
12
down T breaks T makes S breaks
13
down T breaks T makes S breaks
14
down T breaks T makes S breaks
15
Photos found on the internet
16
Before repair
17
After repair