1 ENERCOV SYSTEMS By YF Yap Enercov Co. Humidity Control Concept

2 ENERCOV (SUZHOU) Co Ltd Block B, B6-7, Suhong Ind Square,
#81 Suhong West Road, Suzhou Industrial Park, JiangSu, China 2. ENERCOV (THAILAND) Co Ltd 52/1 Moo 13 Krungthep-Kreeta Road, Sapansung, Bangkok 10250 Thailand Humidity Control Concept 3. ENERCOV (SINGAPORE) Co Ltd 80 Genting Lane #06-02, Genting Block, Ruby Industrial Complex, Singapore

3 SPECIALISTS TEMPERATURE , HUMIDITY & CONTROLS We are
Humidity Control Concept

4 Desiccant Application Enercov Application Enercov’s Control System
Presentation Details Company Policies Desiccant Application Enercov Application Enercov’s Control System Enercov’s Components Proposals to NTU Job References Conclusion Questions & Answers Humidity Control Concept

5 Company Policy Assist our customers to reach the best
solution for your needs. Design your unit. Use Good Quality Components. Assemble and Start Up. Provide Good After Sales Service. Customer Satisfaction. Humidity Control Concept

6 Desiccant Application
Humidity Control Concept

7 Desiccant Wheel --------------------------------------------------
Humidified Exhaust Air Humidity Control Concept Outside Air Dehumidified Air into CleanRoom Humidified Room Air

8 Desiccant Advantages It can be used for very low
Room Dew Point Temp < 4 deg C It can be used to achieve RH < 10% Disadvantages High Power Consumption due to Heating Element. Steps control and not analog. High Maintenance Cost. Need to change filter and Desiccant. Loose Desiccant can contaminate the supply air . 5. Need big floor space. Humidity Control Concept

9 ANNUAL SAVINGS Humidity Control Concept

10 ENERCOV means ENERGY RECOVERY Humidity Control Concept

11 DX Coil Evaporator Coil Humidity Control Concept

12 ENERCOV SYSTEM Evaporator Coil Condenser Coil Chilled Water Coil
Humidity Control Concept Semi Hermetic Compressor

13 Refrigeration Cycle Diagram
Humidity Control Concept

14 Psychometric Explaination
Outdoor Condition Cooling Humidity Control Concept Heating Room Condition

15 DX Coils Advantages Uses Energy Recovery. Very little energy wasted.
VSD control. Analog Control. Most cost effective to control RH above 30%. Low Maintenance Cost. Wash the coil with water. No contamination to supply air due to no direct contact media. 6. DX coils is build into the AHU. Need less space. Disadvantages Limitations to control RH below 30% RH due to minimum suction gas temp of 3 deg C. Humidity Control Concept

16 IS NOT COMPLETE WITHOUT
ITS SOUND SIMPLE BUT ALL THIS THINGS IS NOT COMPLETE WITHOUT TOTAL CONTROL Humidity Control Concept

17 Conventional Air Conditioner
& Desiccant Control Room RH Sensor Activate when RH above 55%. Signal send to DDC. Activate to ON the Desiccant Unit. 3 stages heater in Desiccant Unit fully ON. RH of Room Drops to 50%. Then , 1 stage heater OFF. Once RH drops below 45% , 3 stages heater OFF. Once RH above 55% , 3 stages heater ON again. This system uses STEP CONTROL and NOT ANALOG CONTROL. MOST IMPORTANTLY Control DEHUMI- DIFICATION & COOLING SEPARATELY. Humidity Control Concept

18 Conventional Air Conditioner
Humidity Control Concept Biosafety Laboratory Concept

19 Humidity Control Concept
RESULTS WITH ENERCOV SYSTEM Humidity Control Concept Humidity Control Concept

20 RESULTS WITH ENERCOV SYSTEM
Humidity Control Concept

21 Before we can start to CONTROL
We must know What are the CONTROL MODE Humidity Control Concept

22

23 Process of the Air Humidity Control Concept Humidification Cooling
Heating Dehumidification

24 ENERCOV SYSTEM CONTROL Dehumidification, Cooling,
Heating & Humidification to keep Temperature and Relative Humidity of the ROOM as CONSTANT as POSSIBLE. Humidity Control Concept

25 DX COILS Hot Gas Reheat, Hot Gas Bypass, VSD & DDC Controls System
ENERCOV Humidity Total Control Concept DX COILS Hot Gas Reheat, Hot Gas Bypass, VSD & DDC Controls System Humidity Control Concept

26 Hot Gas Bypass System Hot Gas Bypass System (HGBP)
Humidity Control Concept Hot Gas Bypass System (HGBP) Prevents often of compressor cycling on/off and maintains a very constant of humidity control level.

27

28

29 Advanced Controls System
Advanced cooling capacity management with compressor & fan variable speed control drive lets us manage widely range of system partial heat load 40%-100% without recycling of compressor. Humidity Control Concept

30 TOTAL CONTROL TEMPERATURE 22 +-1 deg Celcius RELATIVE HUMIDITY 50 +- 5% RH
DDC PROGRAMMABLE 4 x 20 LCD Display Temperature & Humidity Sensor Pco1 Controller

31 Controls System Controls Network Diagram (Option)
Humidity Control Concept Controls Network Diagram (Option)

32 High Quality Components Used
Air Handling Unit – Carrier, Robatherm, etc Humidity Control Unit Carlyle Compressor CAREL Controller, Panel & Sensors CAREL Steam Humidifier Others Humidity Control Concept

33 ROBATHERM AHU Humidity Control Concept

34 CARRIER AHU Humidity Control Concept

35 HUMIDITY CONTROL UNIT Humidity Control Concept

36 CAREL CONTROLLER, PANEL & SENSORS
DDC PROGRAMMABLE 4 x 20 LCD Display Humidity Control Concept Temperature & Humidity Sensor Pco1 Controller

37 CAREL STEAM HUMIDIFIER
Humidity Control Concept

38 DANFOSS VSD Humidity Control Concept

39 CARLYLE COMPRESSOR SELECTION
Humidity Control Concept

40 NANYANG TECHNOLOGICAL
We would like to Proposed to the TOP MANAGEMENT of NANYANG TECHNOLOGICAL UNIVERSITY ( NTU ) Humidity Control Concept

41 DESIGN ASSUMPTIONS for ASB3AHU01
Room Temp & RH at 22 C & 40%-50% RH Floor Area metre square Room Height 3 metre No of Occupants 50 persons Exhaust Air litre/sec Total Cooling Load 78 kW Sensible Heat Ratio 0.85 Humidity Control Concept

42 EXISTING SYSTEM TOTAL POWER is 103.5 kW
TRANE AHU MUNTERS Heating Elements & Motors 98 kW Motor kW

43 PROPOSE ENERCOV SYSTEM
Enercov Unit AHU AND

44 CONTROLLER, PANEL & SENSORS
ENERCOV’S CONTROL CONTROLLER, PANEL & SENSORS DDC PROGRAMMABLE 4 x 20 LCD Display Humidity Control Concept Temperature & Humidity Sensor Pco1 Controller

45 SCHEMATIC DIAGRAM Humidity Control Concept

46 ENERCOV CONTROL ITEMS Two sets of Sensors Temperature & Humidity
One at Supply Air and One in the Room. Solenoid Valve to Control The Reheat Coil. Control Valve to Control Chilled Water Coil. Solenoid Valve to Control the HotGassBypass. Temp Sensor for Air Off Chilled Water Coil. Temp Sensor for Air Off DX Cooling Coil. Others Humidity Control Concept

47 Control Points Schedule
Humidity Control Concept

48 ENERCOV SYSTEM CONTROL
Temperature and RH sensor activate. Send signal to DDC Controller. Control Valve for Chilled Water Coil OPEN Fully. If RH not met, Compressor will be ON. DX Cooling Coil will dehumidify the air. If Air temp too low, solenoid valve OPEN too allow HOT GAS to REHEAT the air. Once the desired TEMPERATURE and RH are met, the SYSTEM will be STABLELIZED. Humidity Control Concept

49 Psychometric Process ENERCOV ENERCOV Humidity Control Concept
DX Cooling Coil ( 20kW Only ) Humidity Control Concept MUNTER’S Dehumid ( 98 kW) ENERCOV DX Heating Coil

50 ENERCOV FLEXIBILITY DX Cooling Coil Chilled Water Coil
Total Cooling kW Sensible Heat Rat Sensible Heat kW Latent Heat kW Chilled Water Coil 48.4 kW 0.94 45.5kW 2.9kW Humidity Control Concept Range for Sensible Heat kW to kW Range for Latent Heat kW to kW

51 CONTROL Dehumidification, Cooling, Temperature and Relative Humidity
ENERCOV SYSTEM CONTROL Dehumidification, Cooling, & Heating to keep Temperature and Relative Humidity of the ROOM as CONSTANT as POSSIBLE. Humidity Control Concept

52 Humidity Control Concept
RESULTS WITH ENERCOV SYSTEM Humidity Control Concept Humidity Control Concept

53 TOTAL CONTROL TEMPERATURE 22 +/-1 deg Celcius 40%-50% RH
and RELATIVE HUMIDITY 40%-50% RH Humidity Control Concept

54 JOB REFERENCES Humidity Control Concept

55 JOB REFERENCES Takeda Lace Co Ltd Bangkok.
Biological Safety Lab Level 3 in Ministry of Health Thailand. NSM Factory Co Ltd. UL & CE Standard Testing Room Bangkok. Ministry of Medicine Thailand Vaccine Production Class Humidity Control Concept

56 Takeda Lace Co Ltd Temperature 24 deg C +/- 1 deg C
Relative Humidity 65% +/- 2% RH DDC micro processor based control system Steam Humidifier capacity control Cooling / Heating / Dehumidification / Hum are controlled in proportional linearity. Humidity Control Concept

57 Takeda Lace Co Ltd Humidity Control Concept

58 Ministry of Health Thailand
2. Biological Lab Safety 3 Ministry of Health Thailand Temperature 23 deg C +/- 1 deg C Relative Humidity 50% +/- 5% RH Room Pressure Clean Room Pa Room Pressure Clean Room + 20 Pa 100% Outdoor Air Intake DDC micro processor based control system Hot gas bypass system Humidity Control Concept

59 Ministry of Health Thailand
Biological Lab Safety 3 Ministry of Health Thailand Humidity Control Concept

60 Ministry of Health Thailand
Biological Lab Safety 3 Ministry of Health Thailand Humidity Control Concept

61 3. NSM Factory Co Ltd Temperature 27 deg C +/- 1 deg C
Relative Humidity < 40% RH Double series evaporator coils system Hot gas by pass system DDC micro processor based control system Humidity Control Concept

62 4. UL & CE Standard Testing Room
( Air Conditioner Performance Testing Room Btu/Hr ) Room Temperature Error +/- 1 deg C Room Humidity Error +/- 5% RH Steam Humidifier capacity control Cooling / Heating / Dehumidification / Hum are controlled in proportional linearity. Humidity Control Concept

63 UL & CE Standard Testing Room
Humidity Control Concept

64 UL & CE Standard Testing Room
Humidity Control Concept

65 UL & CE Standard Testing Room
Humidity Control Concept

66 5. Vaccine Production Clean Room Class 10000
Room Temperature < 22 deg C Room Humidity 50% +/- 10% RH Room Pressure 10 – 20 Pa GMP Clean Room Class 10000 Air Change per Hour 30 Cooling / Heating / Dehumidification / Hum are controlled in proportional linearity. Humidity Control Concept

67 Vaccine Production Clean Room Class 10000
Humidity Control Concept

68 CONCLUSION Humidity Control Concept

69 TEMPERATURE & RELATIVE HUMIDITY
TOTAL CONTROL ON THE TEMPERATURE & RELATIVE HUMIDITY Humidity Control Concept Humidity Control Concept

70 SUMMARY OF ENERCOV SYSTEM
CONTROL TEMPERATURE & RH by CONTROLLING COOLING, HEATING, DEHUMIDIFICATION SILMULTANEOSLY. USES MICROPROCESSOR CONTROL. HAVE MORE THAN 20 POINTS SENSOR & CAN BE ADJUSTED TO MEET DESIRED TEMPEARATURE & RH OF THE ROOM. USER FRIENDLY. ASSURANCE THAT TEMPERATURE 22 C +/- 1 deg C. ASSURANCE RELATIVE HUMIDITY 40% - 50% RH. Humidity Control Concept

71 ENERCOV is providing a BRAIN CONTROL
for the Air Conditioning System to CONTROL the Temperature 22 -/+ 1 deg C and Relative Humidity % RH & Save at least 70% Energy Compare To Desiccant Unit Humidity Control Concept

72 SAVE ENERGY THE EARTH ITS our JOB to PROTECT for the
FUTURE of OUR CHILDREN SAVE ENERGY Thank you