SIPROTEC 4 Distance Protection 7SA522 and 7SA6
Productmanager Distance Protection Michael Claus EV S V 13 Nürnberg H Phone: Fax:
2
SIPROTEC 4 - What it means
is a family of numerical Protection, Control and Automation Devices from
3
Distance protection: Past and Present
Experience 7SA510 7SA511 7SA513 SIPROTEC 4 Software System System 7SA522 7SA6 Oben links: Stückzahlen 7SA510:2500 7SA511:20000 7SA513:2000 Unten: Liefereinsatz Sommer 2000 Requirements SIPROTEC 4 Hardware Platform Variability
4
SIPROTEC 4 Distance Protection 7SA522 and 7SA6
7SA SA6 One family of distance protection for all voltage applications
5
SIPROTEC 4 Distance protection
7SA610 7SA SA522 7SA SA522 7SA61 + 7SA522 Protection 4-line display MV, HV and EHV 7SA631 7SA632 7SA63 Protection + local control integrated graphic display mainly MV 7SA641 7SA642 7SA64 Protection + local control detached control panel mainly MV All core functions are available in all the housing versions
6
SIPROTEC 4 Distance Protection, Scope of functions (1)
ANSI-No. 21, 21N 68 FL Distance Protection full scheme measurement with sophisticated loop selection fast three phase and single phase tripping with/without parallel line compensation special filtering for CVT transients special algorithm for detection and compensation of CT saturation Low demand on CT specification Power swing blocking/out-of-step tripping Fault Locator with/without parallel line compensation en513all7
7
SIPROTEC 4 Distance Protection, Scope of functions (2)
85-21 50N, 51N, 67N 85-67N WI 50, 51 50N-2, 51N-2 ANSI-No. Universal teleprotection interface (PUTT, POTT, Blocking, Unblocking, DTT...) High resistance earth fault protection for earthed systems Teleprotection interface for earth fault protection (Directional comparison, Blocking, Unblocking) Weak infeed protection (Echo and Trip) Overcurrent protection DMTL/IDMTL as parallel or emergency function en513all8
8
SIPROTEC 4 Distance Protection, Scope of functions (3)
ANSI-No. 59, 27 1) 50HS 50-STUB 79 25 50BF 49 2) Voltage protection 1) Fast tripping with switch-onto-fault condition (12 ms) STUB Bus Overcurrent protection Single and three pole multishot automatic reclosure Synchro-check Circuit-breaker failure protection Thermal overload protection 2) Earth fault detection in compensated/isolated systems 2) 1) 7SA522: Overvoltage, 7SA6: Over- and Undervoltage 2) available only in 7SA6
9
SIPROTEC 4 Distance Protection, Scope of functions (4)
ANSI-No. 74TC 86 FR 47 Trip Circuit Supervision Lock Out Oscillographic Fault Recording (total length 15 s) Voltage Phase Sequence Interfaces Time synchronization (IRIG-B, DCF77) User interface#1 (on the front for DIGSI 4) User-(Service-)interface #2 (on the rear, DIGSI 4/Modem) System interface (IEC /Profibus FMS/others) Remote relay interfaces #1 (planned for teleprotection*) 1) Remote relay interfaces #2 (planned for teleprotection*) 1) available only in 7SA522 * available approx. 1st Q/01
10
SIPROTEC 4 Distance Protection, Monitoring
Operating system monitoring Auxiliary voltage failure Measured value detection Buffer battery Hardware–Watchdog Software–Watchdog Working memory Program memory Parameter memory Sampling frequency 1/5 A–setting Calibration data Earth current transformer sensitive/normal Modules (I/O Boards) Plausibility monitoring Current sum Current symmetry Open conductor Fuse Failure 1- / 2-pole failures 3-pole failures Voltage sum Voltage symmetry Voltage phase rotation ! new
12
SIPROTEC 4 Distance Protection
Quadrilateral Characteristic 5 Zones (time delayed) optionally: - Forward - Reverse - Non-directional Dependant Zone Z1b for Teleprotection and Auto-recloser Prevention of load encroachment
13
SIPROTEC 4 Distance Protection: Overall Trip Time Curves at SIR = 30
14
SIPROTEC 4 Distance Protection, Data window position, Adaptive Measuring Algorithm
15
SIPROTEC 4 Distance Protection Function: Difference 7SA522 - 7SA6
for solid earthed systems quadrilateral and/or MHO characteristic (MHO circle for specific markets, quadrilateral is preferred) full market introduction: 1999 primary market outside continental Europe 7SA6 for systems with solid grounding or reactance (compensated) / isolated treatment of system starpoint fault detection selectable as either I>, Z<, U/I and U/I/ Market introduction: Summer 2000 Primary market continental Europe
16
SIPROTEC 4 Distance Protection 7SA522
Mho Characteristic 5 Zones optionally: - Forward - Reverse Dependant Zone Z1b for Teleprotection and Auto-recloser Prevention of load encroachment
17
SIPROTEC 4, Distance Protection Parallel-line compensation: connection and setting
18
Patented power swing detection provides secure operation with swing frequencies of up to 6 Hz
Example: 400 kV 400 km fPS 2 Hz 3-pole fault
19
SIPROTEC 4 Distance Protection: Fault locator
20
SIPROTEC 4 Distance Protection: Phase segregated Teleprotection
2 2 L2-E Z1 Z1B L1-E 1 1 A B Z1 Z1B A1 trips single-phase in L1 with a phase-segregated L1-receive-signal Maximum of Selectivity Note: 3 binary channels for both directions are requested or (in preparation) one serial link
21
SIPROTEC 4 Distance Protection: Teleprotection with three-terminal lines
Software provides teleprotection of three-terminal lines without additional logic
22
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Earth (zero sequence) current protection, 4 stages 3 definite-time stages 1 inverse-time stage: IEC, logarithmic inverse or ANSI characteristic this stage can also be used as a 4th definite-time stage Directional determination with 3V0 and/or Ipol of an earthed power transformer Directional determination with V2 and I2 (negative sequence) Sensitive 3I0-measurement with a dynamic from A to 100 x In Elimination of higher harmonics with special digital filters Inrush-stabilisation with I0/100Hz Teleprotection: Directional comparison, Blocking or Unblocking Operation with weak infeed trip and echo Instantaneous trip after switch-onto-fault
23
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Definite-time characteristic
24
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Tripping characteristic Logarithmic Inverse t T3I0pmax (P3145) T3I0p (P3144) 3I0p(P3140) Example: t = ln(3I0 / 3I0p) T3I0min (P3141) 3I0p Startpoint(P3154) 3I0 / 3I0p
25
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
26
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Inverse-time characteristic: IEC
27
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Filter characteristic for stages 3I0>>> and 3I0>>
28
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Filter characteristic for stages 3I0> and Inverse time stage
29
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
30
SIPROTEC 4 Distance Protection: Permissive overreach transfer trip (POTT)
TS
31
SIPROTEC 4 Distance Protection STUB protection for 11/2-circuit breaker arrangement
Release of STUB-stage with open line isolator:
32
SIPROTEC 4 Distance Protection: Auto-reclosure
Auto-reclosure (AR) TRIP 1-pole 3-pole RE- CLOSE * TRIP RE- CLOSE final TRIP ON OFF 1st dead time 2nd dead time T2-act T1-act tzone-delay * ADT = Reclosure, when AR at the remote end was successful DLC = Reclosure only on dead line RDT = Reduced dead time, if trip had occurred with zone extension
33
Synchronism-check application examples functions
(separately settable for AR and - combination with internal or manual closing) external AR - program selection via parameters: - activation also for manual closing synchro-check / U1 > U2 < / (settable) U1 < U2 > / U1 < U2 < / overrule - asynchronous switching (settable) all programs separately settable via binary inputs - synchronous monitoring time, after which the closing will be blocked (settable) parameters measurement - voltages U<, U>, U evaluation of the fundamental wave - f synchronous switching ( Hz) - insensitive against harmonics - f asynchronous switching ( Hz) for dead line check all three phases are controlled - (1° °) engersyn1
34
SIPROTEC 4 Distance Protection: Breaker failure protection
2 stages Internal initiation and via binary inputs Extremely short reset time: approx. 10ms End-fault protection Pole discrepancy supervision
35
SIPROTEC 4 Distance Protection
7SA522 with light or electrical exchangeable upgradeable
37
SIPROTEC 4 - Distance Protection
Safe operation, reduced training requirements User friendly Operation Fits all applications Flexible Functionality and Open Communication System concept SIPROTEC and SICAM One Family
38
Distance Protection 7SA522 What makes these devices so attractive ?
Log. IN 1 Log. IN 2 Log.IN3 Logic inputs from the matrix to CFC Logic outputs to the configuration matrix F1 F2 >1 CFC Log.OUT1 Full Logic Functionality Additional logic Interlocking Measured values processing
39
Distance Protection 7SA522 What makes these devices so attractive ?
I1 :400.9A f:50.0Hz U1:12.22kV P :+8.03MW cos Q :+2.64MVar Comprehensive measured value processing L A Max450.1A L A Max421.2A L A Max431.4A E A % IL UL-E UL-L L L L
40
Distance Protection 7SA522 What makes these devices so attractive ?
The easy handling with DIGSI 4