Question How does a temporary genset get connected to a building in an emergency? How do generator service companies connect their load bank when performing their annual testing?
7
Typical Temporary Genset Hook-Up How do cables get connected? A. Knock a hole into existing switchgear B. Run cable through the building
8
Typical Temporary Loadbank Hook-Up How do cables get connected? Most Common – Disconnect the permanent conductors from the output side of genset circuit breaker – tie in load bank cables
9
Typical Temporary Connection The problem for owners: Temp Genset DOWNTIME Damage to gear Unsecured building Outage to connect & disconnect Electrician required Load Bank Customer is exposed to an outage During connection, testing, and disconnection Cable terminations exposed during operation Excessive wear to breaker lugs – not torqued-stripped
10
Trystar Docking Stations What is a Docking Station? Termination station Quickly, Safely and Legally connect/disconnect Temporary Generators Temporary Load Banks Temporary Chillers Temporary Power
11
Go from this To this
12
Standard Construction Available from 100A to 5000A UL 50 powder coated aluminum or stainless steel enclosure Lockable rake system reduces cable theft & cable disconnection Cam lock style inputs and/or outputs, mechanical lugs, or pin and sleeve Phase rotation meter
13
Standard Docking Station Simple Camlock or Mechanical Lug connection box. Provides no isolation between sources Temporary generator Temporary load bank Temporary chiller Company switch Can be factory mounted to 3rd Party MTS and shipped pre- packaged together
15
Attaching to transfer switches Ship the transfer switch to Trystar and will mount and wire the docking station to the transfer switch. Includes 2 wire auto start terminal and phase rotation monitor. Available with battery charger and water heater outlets Available as dual purpose for load banking permanent gen
16
Docking Station With Kirk Key Kirk Key Provides isolation between sources Temporary generator Temporary load bank Temporary chiller Company switch Many variations can be achieved through multiple kirk key Interlocks
17
How does a Kirk Key System work? Key is Captive and cannot be removed while Breaker is “On” Docking station door cannot be unlocked without key
18
How does a Kirk Key System work? Once breaker is in ”Off” position captive key can be removed Key can then be used to unlock docking station door
22
Breakered Docking Stations Service Entrance Rated Distributions & Feeder Breakers Temporary Generator Breaker Temporary generator Temporary chiller Company switch Distribution breakers allow for maximum flexibility
27
Dual Purpose Docking Stations Used in conjunction with a permanent installed generator Provides temporary generator connection & temporary load bank connection Offer load dump circuitry Offers remote start capability
32
How does the Remote Start circuit work? Circuit wired in parallel with automatic transfer switch
33
How does the Load Dump circuit work? Circuit wired in parallel with automatic transfer switch position contacts
34
Rotary Docking Stations Integrated Manual Transfer Switch and Docking Station Three Position Utility-Off- Generator, Up to 1200A Option for Service Entrance Rating
36
Temporary Chiller Used to quickly connect temporary chillers Healthcare & Data Centers Company Switches Convention Center, Stadiums & Arenas Output Docking Stations
37
Gland Plates Mount to temporary gensets, ATS, or Switchgear Inlet Panels Designed to be mounted on single and double throw type disconnect switches. Accessories
38
Recap Construction: Up to 5,000A Nema 3R and 4X Used for connections: Temporary generators Load banks Chillers Output power (Company switches) Models: Generator Docking Station – with and without Kirk Key Breakered Docking Station Dual Purpose Docking Stations Rotary Docking Stations Options include: Kirk key interlocks Service entrance breakers Distribution breakers Remote start terminals Load dump terminals