FOAM APPLICATION TECHNIQUES
HOSTED BY THE Jefferson County Fire and Rescue Training Academy
3
TACTICS DO NOT START A FOAM OPERATION IF YOU DO NOT HAVE ENOUGH FOAM. (The fire will not go out and you will just waist foam) *INSTEAD, ATTEMPT TO PROTECT EXPOSURES OR EVACUATE IF YOU HAVE AN ETHANOL FIRE, USE AR-FOAM IF AT A FIXED FACILITY, ASK THE PEOPLE THAT WORK THERE FOR HELP. (They are the experts with the product on fire.)
4
OBJECTIVES TERMS HOW FOAM WORKS FOAM GENERATION TYPES OF FOAM
APPLICATION RATES FOAM EQUIPMENT PRACTICAL EVOLUTION
5
What is Foam? NFPA- 11 describes Foam as an aggregate of air filled bubbles and is lower in density than flammable liquids. Must be able to- Flow Freely Have a high resistance to heat Fuel tolerance Form a tough, cohesive blanket Must hold water
7
Smothering: prevents release of vapors
Foam’s Extinguishing Characteristics Smothering: prevents release of vapors Separating: creates a barrier between the fuel and fire Cooling: lowers temperature of the fuel
8
Limitations of Foam Foam solution is 94%-97% water Cannot be used on:
Electrical fires Three Dimensional Fires Pressurized Gases Combustible Metals
9
Kinds of Foam Protein Fluroprotein Film Forming Protein (FFFP)
Aqueous Film Forming Foam (AFFF) Alcohol Resistant AFFF (ARFFF)
10
Aqueous Film Forming Foam (AFFF)
Good penetrating characteristics Can be used with non-aerating nozzles Spreads a vapor-sealing film over fuels Can be pre-mixed Can be mixed with antifreeze Good low temperature viscosity May be applied directly on fuel surface, applied indirectly, or used with subsurface injection
11
Foam Delivery Systems In-Line Eductors Around the Pump Eductor
Compressed Air Foam System By-Pass Line Eductor
12
Most commonly used Attached to pump or at some point in the hose lay
In-line Foam Eductors Most commonly used Attached to pump or at some point in the hose lay The foam concentrate inlet to the inductor must be no more than six feet above the surface of the liquid foam concentrate
13
Venturi Principle in Eductors
As water at a high pressure passes over a reduced opening, it creates a low pressure near the outlet side of the eductor The low pressure creates a suction which draws the foam concentrate into the water stream.
14
VENTURI PRINCPLE- VACUUM CREATED WITHIN THE DEVICE BY MANIPULATING WATER VELOCITY.
SUPPLY TUBE IS CONNECTED TO THE VACUUM CHAMBER AND PLACED IN THE FOAM CONCENTRATE. BECAUSE OF THIS, EDUCTOR IS APPROX. 65% EFFICIENT.
15
ALL NOZZLES DO NOT PRODUCE SAME QUALITY BLANKET.
WHAT MIGHT APPEAR TO BE A GOOD BLANKET, MAY BE DRAINING OUT QUICKLY AND REQUIRE FREQUENT RE-APPLICATION. ASPIRATING FOAM NOZZLE MINS; STRUCTURAL NOZZLE WITH ATTACHMENT- 10MINS. STRUCTURAL FOAM NOZZLE- 1 MINUTE
16
REMEMBER MATCH NOZZLE TO EDUCTOR MAINTAIN 200 PSI INLET PRESSURE
17
Back Pressure should not exceed 70% of inlet pressure
HYDRAULICS Back Pressure should not exceed 70% of inlet pressure Back Pressure=NP+FLH+FLE 250’ of 1.75” and 0’ elevation FLH= psi + 0= 130 psi FLE= 70 psi 130psi + 70 psi= 200 psi
18
Foam Production Foam must be proportioned with water and aerated with air to be used effectively Most fire fighting foams are designed to be mixed at 3% to 6% concentrate in water
20
Foam & Foam Streams To be effective, foam concentrates must be matched to the fuel to which they are applied
21
DETERMINE TYPE OF LIQUID
POLAR SOLVENTS- .16 GPM SQ. FT. HYDROCARBONS GPM SQ. FT.
22
HOW MUCH FOAM - NFPA 11 DETERMINE SQUARE FOOTAGE
10 FT. X 1OO FT.= 1000 SQ. FT. 2. DETERMINE TYPE OF LIQUID POLAR SOLVENT- .16 GPM/SQ. FT. HYDROCARBONS- .10 GPM/SQ.FT.
23
APPLICATION RATES hydrocarbon fuels
3. DETERMINE AMOUNT OF FOAM CONCENTRATE. 100 GPM X .O3 = 3 Gal. Foam/Min. 4. AMOUNT REQUIRED FOR 15 MIN. 3 GPM X 15 MIN. = 45. Gal of Foam will be required.
24
APPLICATION RATES hydrocarbon fuels
Determine amount of water needed 100 GPM X .97 = 97 GPM 97 X 15 = 1455 Gallons of Water
25
Foam Application Methods
Roll – On Method Bank Down Technique Rain – Down Method DO NOT PLUNGE
29
FOAM APPLICATION SCBA SWEEPING MOTION DO NOT PLUNGE FOAM
DO NOT WALK IN LIQUID DO NOT TURN YOUR BACK TO FLAMMABLE DO PRESERVE THE FOAM BLANKET
30
Causes of Poor Foam Generation
Eductor and Nozzle Mismatch Too Much Hose between Eductor & Nozzle Nozzle Elevation Partially closed Nozzle Shut Off Kinked Discharge Line
31
Fuel Mixture comprised of 85% ethanol and 15 % gasoline
Fires should be treated differently than traditional gasoline fires- These mixtures are polar/water-miscible flammable liquids ( ie- they mix readily with water) Degrade effectiveness of fire-fighting foam which is not alcohol- resistant Refer to Guide 127 ( Flammable Liquids Polar/Water Miscible) of 2004 ERG
32
PRACTICAL FOAM HOOK-UP EDUCTOR MAKE SURE NOZZLE MATCHES EDUCTOR
SET METERING DEVICE SET FLOWING PRESSURE INSERT PICK-UP TUBE INTO FOAM
33
QUESTIONS?
45
DETERMINE AMOUNT OF FOAM CONCENTRATE
600 GPM X .03 = 18 GAL. FOAM MIN.
46
Fluoroprotein Foam Good water-retention capabilities
W Excellent heat resistance W Not affected by freezing & thawing W Can be mixed with antifreeze W Good fluidity on fuel surface
47
Do not allow foam to plunge into burning liquids.
Protein Foam W Excellent water-retention capabilities W High heat resistance and re-ignition resistance W Performance can be affected by freezing and thawing W Can be mixed with antifreeze W Can be made resistant to alcohol Do not allow foam to plunge into burning liquids.