Download presentation
Presentation is loading. Please wait.
Published byMerry Arnold Modified over 9 years ago
1
Control of Three-phase Active Rectifier for Wind Turbine Applications AALBORG UNIVERSITY INSTITUTE OF ENERGY TECHNOLOGY UNIVERSITY OF MARIBOR INSTITUTE OF ROBOTICS Evgen Urlep December, 2002
2
Contents Introduction System modeling and analysis LCL filter design Control design Simulation and implementation Conclusion
3
Introduction Types of Wind Turbines Horizontal axis Vertical axis Operation modes of WTG Constant Speed – Constant Frequency Variable Speed – Constant Frequency
4
Problem definition Nominal power11kW Nominal grid current16A Grid side phase voltage (rms) 230V Grid frequency50Hz DC link voltage700V DC link nominal current17A Rated values Grid connection Grid connection Stand-alone Stand-alone Design and implementation of the control scheme for the DC/AC converter in WTG in
5
Hardware configuration
6
System overview
7
Three-phase Active rectifier RL-filter
8
RL filter in rotating frame
9
Grid mode controller design
10
Active Rectifier control structure Grid connected
11
Model of the LCL filter
12
LCL filter design L I [mH]1.25 L G [mH]1.5 C F [ F] 6 RD []RD [] 4 Q c <5% Z T <10%Z b res <0.5 sw
13
Current attenuation
14
Current controller design
15
Root locus Kp=4.8Ti=8 ms
16
DC-link controller design k DC =0.7, T et =4.8ms C DC >>(T ei + 0 ), optimal symmetry criterion
17
Root locus Kp=0.35Ti=20 ms
18
Standalone control structureStand-alone
19
Main voltage controller design
20
Root locus Kp=0.1Ti=0.29 ms 1% load nominal load
21
DC-link voltage limiter T et =2.1ms, 0 =0.2ms C DC >>(T ei + 0 ), optimal symmetry criterion
22
Root-locus Kp=0.79Ti=0.092 ms
23
DC-link choper operation R DC
24
Phase angle detection Kp=80Ti=1 s
25
Simulation in grid mode
26
Steady state simulation Grid mode Generating mode Ideal phase voltage 2% 5 th + 1% 7 th harmonics
27
Simulation in stand-alone mode
28
Steady state simulation phase voltages and current at nominal power using resistive load Stand-alone mode
29
Transient simulation Stand-alone mode System startup Half of nominal load to nominal load
30
Implementation dSPACE 1103 MPPC 604e at 633Mhz MPPC 604e at 633Mhz TMS320F240 TMS320F240 16xADC-16 4 s ±10V 16xADC-16 4 s ±10V 4xADC-12 800 ns 10V 4xADC-12 800 ns 10V 8xDAC-14 bit -6 µs 10 8xDAC-14 bit -6 µs 10 7x IE interface 7x IE interface 32xI/0 32xI/0 TDE software TDE software
31
Combined control
32
ControlDesk
33
Steady state operation Grid mode Measured conditions U DC =650VU AC =220V P=11.28kWPF=0.998 I THD =6.7%U THD =2% Rectifying mode Generating mode
34
Transient operation Grid mode Nominal load system startup Disturbance rejection
35
Steady state operation Stand-alone mode Resistive load Measured conditions U DC =700 VU AC =230 V P=11 kWI AC =16.4 A I THD =3.4 %U THD =3.4 %
36
Steady state operation Stand-alone mode 3-phase diode bridge Measured conditions U DC =700 VU AC =230 V P=11 kWI AC =16.6 A I THD =25 %U THD =10 %
37
Transient operation Stand-alone mode Full load applied on the half of produced power
38
Transient operation Stand-alone mode Short-circuit startup
39
Automatic mode switch Idle mode Grid mode Stand-alone mode I-SA I-GM GM-ISA-I GM-SA I-GM:U G and /PLLe and /TRIP and START I-SA:/U G and /TRIP and START GM-I: TRIP or STOP SA-I: TRIP or STOP or PLLe GM-SA: PLLe
40
Grid mode to Stand-alone mode transition nominal load
41
Stand-alone mode to Grid mode transition
42
Conclusion Vector based control of DC/AC converter with near unity power factor was succesfully designed, simulated, implemented and verified. LCL filter was designed, implemented and tested Two different control strategies were implemented according to the operating modes A common controller design procedure is used to tune controller parameters PLL is designed to detect phase angle Two different control strategies are implemented and tested in dSPACE. Automatic mode detection and switching betwen modes can be implemented
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.