Download presentation
Presentation is loading. Please wait.
Published byHugh Beasley Modified over 9 years ago
1
High & Low Pressure Watermist Systems
2
High Pressure Water Mist System Risk: Historic building – Conference Hall Type of system: Wet - Pre-action Risk: OH1 – 830 m 2 Nozzle flow rate: 27,5 l/min each Nozzle Working pressure: 100 bar System total Flow Rate: 247,5 l/min Nozzles: No. 120 Semco CEN High Height Water supply: Semco PU PAH80 ( 4 x 112 l/min)
3
High Pressure Water Mist System Risk: Archives – 3500 m 2 Type of system: Deluge – Local application Nozzle flow rate: 13 l/min each Nozzle Working pressure: 100 bar System total Flow Rate: 1027 l/min Battery No.1 : 806 l/min Battery No.2 : 611 l/min Battery No.3 Total Nozzles: 454 Ultrafog nozzles Water supply: 31 N 2 + 93 H 2 O Cylinders
4
Low Pressure Water Mist System Risk: Gas Turbine Compartment &Aux Type of system: Deluge – Local application No of Systems: 23 Italy + 17 Tunisie Nozzle flow rate: 23,5 l/min each Nozzle Working pressure: 5,5 bar System total Flow Rate: 376 l/min (GT) + 1100 (Aux) No. Of Nozzles: 16 (GT) + 43 (Aux) Discharge time: 5 min Water Supply: 1000 l + 2200 Pressurized Tanks
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.