FSTS Leak Rate Qualification Procedure J. Botelho Direito EN/CV/PJ 29/11/2012 FSTS - Leak Rate Qualification Procedure.

Similar presentations


Presentation on theme: "FSTS Leak Rate Qualification Procedure J. Botelho Direito EN/CV/PJ 29/11/2012 FSTS - Leak Rate Qualification Procedure."— Presentation transcript:

1 FSTS Leak Rate Qualification Procedure J. Botelho Direito EN/CV/PJ 29/11/2012 FSTS - Leak Rate Qualification Procedure

2 Leak Rate Qualification Process 29/11/2012 FSTS - Leak Rate Qualification Procedure

3 Maximum Leak Rate for the FSTS He Leak Rate [mbar.l/s] (inlet pressure of 0.1 mbar) Number of connections (or locations to be tested) Maximum leak rate per connection Condenser3.47x10 -3 301.16x10 -4 Vapour line5.62x10 -3 301.87x10 -4 Liquid line3.22x10 -4 2001.61x10 -6 Brine Circuit1.53x10 -4 1001.53x10 -6 29/11/2012 FSTS - Leak Rate Qualification Procedure

4 Validation Pressure Test 29/11/2012 FSTS - Leak Rate Qualification Procedure Thermosyphon Circuit – Return LineThermosyphon Circuit – Condenser

5 Validation Pressure Test 29/11/2012 FSTS - Leak Rate Qualification Procedure Thermosyphon Circuit – Liquid LineBrine Circuit