1 SmartLine Startup

2 Initial wirings SmartLine Initial Wirings

3 Balance Zones with a 3.9kΩ resistance
Initial wirings SmartLine Balance Zones with a 3.9kΩ resistance

4 If Zones aren’t balanced panel displays “Zone open”
Initial wirings SmartLine Fault /04 Zone Open Zone <Zone 01> If Zones aren’t balanced panel displays “Zone open”

5 Balance Dialler with a 10 kΩ resistance (between terminals 19 and 23 )
Initial wirings SmartLine Balance Dialler with a 10 kΩ resistance (between terminals 19 and 23 )

6 If Dialler isn’t balanced panel displays “Fault Dialler”
Initial wirings SmartLine Fault /01 FaultDialler If Dialler isn’t balanced panel displays “Fault Dialler”

7 Initial wirings SmartLine Balance NAC with a 47kΩ resistance

8 panel displays “Open I/O Panel NAC”
Initial wirings SmartLine Fault /01 Open I/O Panel NAC If NAC isn’t balanced panel displays “Open I/O Panel NAC”

9 SmartLine Detectors Wiring
Balance other zones with a 3.9 kΩ resistance 3.9 kΩ End of Line resistance on the last detector

10 SmartLine Callpoints Wiring
Balance other zones with a 3.9 kΩ resistance 3.9 kΩ End of Line resistance on the last callpoint

11 NAC output activates on Alarm: it can activate alarm devices
SmartLine NAC Wiring NAC output activates on Alarm: it can activate alarm devices 47 kΩ End of Line resistance on the last device

12 NAC SmartLine Fault /01 Short I/O Panel NAC If panel displays “Short I/O Panel NAC” it will need connect a diode in series (if devices haven’t it) 47 kΩ End of Line resistance on the last device

13 SmartLine Other wirings 17-18 FAULT Terminals activated on Fault.
Fault output can activate some devices

14 SmartLine 19-20 DIALER Terminals activated on Alarm.
DIALER Output can activate an external dialler.

15 SmartLine 25-26 AUX R Terminals turn off 24V on Reset
They can reset latching linear beam smoke detector

16 SmartLine 27-28-29 RELAY Terminals activated on Alarm (at default)
They can activate some devices

17 Generic Contact Wiring
SmartLine Generic Contact Wiring Alarm contact only 680Ω resistance NO Alarm Contact 3.9kΩ resistance

18 Alarm Contact and Fault Contact
Generic contact SmartLine Alarm Contact and Fault Contact 680Ω resistance NO Alarm Contact NC Fault Contact 3.9kΩ resistance

19 Detection-Line Zone Wiring
Gas Detector Wiring SmartLine Gas Detector Wiring Detection-Line Zone Wiring It have to program the Zone as “Gas (Relay Output) INE55/ING55 Detector 3.9kΩ resistance

20 SmartLine I/O 4-20mA Input Wiring
Gas Detector Wiring SmartLine I/O 4-20mA Input Wiring It have to program I/O Line as “Gas 4-20mA Input” INA55-101 board 150Ω resistance INE55/ING55 Detector 3.9kΩ zone balancing resistance

21 Generic 4-20mA Gas Detector Wiring
SmartLine Generic 4-20mA Gas Detector Wiring It have to program I/O Line as “Gas 4-20mA Input” Generic 4-20mA gas detector 4-20mA output 150Ω resistance 3.9kΩ zone balancing resistance Detector have to supply current

22 Expansion Boards Wiring
SmartLine Expansion Boards Wiring To next expansion board

23 SmartLine Expansion Zones are similar to panel ones
Expansion boards SmartLine Expansion Zones are similar to panel ones Balance Zones with a 3.9kΩ resistance

24 Espansions board SmartLine Expansion NAC output is programmable (at default output is activated on Alarm) Balance NAC with a 47kΩ resistance

25 SmartLine It have to configure expansion boards
Control Panel IN PROGRAMMiING Ver: 2.03 01/01/ :45 Enable panel programming phase

26 SmartLine Expansion boards Control Panel IN PROGRAMMING Ver: 2.03
01/01/ :45 Control Panel IN PROGRAMMING Ver: 2.03 01/01/ :45 Settings Disablement Maintenance Programming Configuration Progr. Zone Progr. Output Progr. Timer Acquire int.bus Acquire ext.bus Current Devices Extin.module O Expansion O Ok to execute Current Devices Extin.module O Expansion Ok to execute

27 SmartLine RS485 Bus Wiring Up to 4 Repeater 2 Power Station RS485 Bus
SmartLevel Power Station SmartLetUSee/LCD-Lite Repeater

28 SmartLine It have to address RS485 Bus devices RS485 Bus Address
DIP Switch Position SmartLevel Power Station SmartLetUSee/LCD-Lite Repeater

29 SmartLine It have to address RS485 Bus devices RS485 Bus
Enable SmartLevel programming phase Prog View log LED Test Reset Maintenance LED test Reset Maintenance Programming Booster Options Address RS485 Default Data SmartLevel Power Station Address: 01 SmartLetUSee/LCD-Lite Repeater Address: 02

30 SmartLine Set End of Line jumper in EOL position on the last device
RS485 Bus SmartLine Set End of Line jumper in EOL position on the last device SmartLevel Repeater SmartLevel Power Station Ripetitore SmartLetUSee/LCD-Lite

31 SmartLine It have to address RS485 Bus devices
Control Panel IN PROGRAMMING Ver: 2.03 01/01/ :45 Enable panel programming phase SmartLevel Power Station SmartLetUSee/LCD-Lite Repeater

32 SmartLine RS485 Bus SmartLevel Power Station
Centrale IN PROGRAMMAZ.!! Ver: 2.03 01/01/ :45 Control Panel IN PROGRAMMING Ver: 2.03 01/01/ :45 Control Panel IN PROGRAMMING Ver: 2.03 01/01/ :45 Settings Disablement Maintenance Programming Configuration Progr. Zone Progr. Output Progr. Timer Acquire int.bus Acquire ext.bus SmartLevel Power Station Current Devices Repeater O Power Station O Ok to execute SmartLetUSee/LCD-Lite Repeater Current Devices Repeater 2 Power Station 1 Ok to execute