1 2704 V6.0 software - June 2003 Hardware compatibility –New micro-board required New Features –Boiler TDS functions –Programmer enhancements –Other little.

Similar presentations


Presentation on theme: "1 2704 V6.0 software - June 2003 Hardware compatibility –New micro-board required New Features –Boiler TDS functions –Programmer enhancements –Other little."— Presentation transcript:

1 1 2704 V6.0 software - June 2003 Hardware compatibility –New micro-board required New Features –Boiler TDS functions –Programmer enhancements –Other little things to make life easier

2 2 Boiler TDS What is Boiler TDS? –TDS (total dissolved solids) is the measurement of particles in a fluid. For example water in a steam boiler. Why do we need to control it? –High TDS causes foaming on the surface of the water. This reduces boiler efficiency and contaminates the steam system. Steam Feedwater Continuous Blowdown TDS Probe Bottom Blowdown Water Steam

3 3 2704 TDS Functions TDS Measurement –TDS is derived from conductivity measurement in  S/cm –New conductivity input module, order code TD TDS Control –Continuous control »Temperature compensated TDS reading in PPM or  S/cm@25°C »Probe deterioration alarm »Reduced probe scale build up »Simple calibration functions –Timed bottom blowdown »Uses real time clock to initiate blowdown »Can be networked in multiple boiler installations »Complies with PM60 - UK standard concerning multiple boiler installations

4 4 2704 Programmer Ability to run Asynchronous Profiles –Up to 3 setpoint profiles –Each profile has its own timebase –20 stored programs per profile –16 Digital outputs per profile –Option “A” in Loops/Program field Program Run Groups –Ability to store 20 groups –Common Run, Hold & Reset Advanced Editing –Insertion/deletion of segments –Copy/paste of programs Custom naming of digital events Increase to 60 Synchronous Programs Profile 1 Profile 2 Profile 3

5 5 Synchronous Programmer Loop 1Loop 2Loop 3 Programmer Run Hold Reset Digital events x 16 PSP1 PSP2 PSP3

6 6 Asynchronous Programmer Loop 1Loop 2Loop 3 PSP1 Profile x 20 Run Hold Reset Digital events x 16 PSP2 Profile x 20 PSP3 Profile x 20 Digital events x 16 Run Hold Reset Run Hold Reset Run Hold Reset Program Groups x 20

7 7 Other Little Things Patch Wiring –Any parameter can now be ‘soft’ wired –Available in Toolkit level 1 32 Analogue operators in Toolkit level 2 50 User values –10 in standard 2704 –30 in Toolkit level 1 –50 in Toolkit level 2 New multiple input block –6 inputs - average, max, min or sum of inputs »Can be used as 6 input OR or AND gate –3 blocks in 2704 »1 in Toolkit level 1 »3 in Toolkit Level 2

8 8 Other Little Things - Continued 100 User text strings 100 Master communications parameters –16 Slave devices Option for Local SP Ramp servo to WSP Additional EI-Bisync parameters