Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National.

Similar presentations


Presentation on theme: "Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National."— Presentation transcript:

1

2 Ted “Smitty” Smith

3  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National Fire Alarm and Signaling Code and the Denver Building Amendments.  If you put the slide show into slide show mode, the slides will transition automatically and allow you 3 minutes for each question. The answers will stay up for only 15 seconds. When you reach the end of the practice test there will be a slide that reads STOP.  You can then click on the slide and the questions will be repeated without the timer so that you can write down questions and answers and take notes.  During the timed section, do not worry about writing down the correct answer. Proceed through the timed section then review the questions and answer again without the timer.

4  In the absence of a specific performance based design criteria, smooth ceiling smoke detector spacing shall be a nominal _________ feet.

5  30 feet 17.7.3.2.3.1

6  Signals with carbon monoxide detectors transmitted to a fire alarm system shall be permitted to be _____________________________ signals.

7  Supervisory 23.8.4.7

8  When a supervising station receives a trouble signal they must dispatch personnel with in ________ hours to initiate maintenance, if necessary.

9  4 hours 26.3.7.4

10  Complete records of all signals received by a supervising station shall be kept for a period of ________________.

11  1 year 26.4.6.1

12  A type public alarm system shall be required where the number of all alarms required to be retransmitted exceeds _____________ per year.

13  2500 27.5.2.1.2

14  A fire alarm system installed in an occupancy that does not require a fire alarm system shall ____________________________.  A. comply with NFPA 72  B. not be required to comply with NFPA 72  C. comply with chapters 17 and 18 of NFPA 72 only  D. comply with the NEC only

15  A. comply with NFPA 72 (23.2.3.1)

16  A class A circuit in a protected premises using physical conductors shall be installed so that the outgoing and return conductors are routed separately unless for a distance not to exceed __________ feet where the conductors enter or exit the initiating device, notification appliance, or control unit enclosures.  3  6  10  15

17  10 (23.4.2.2 List item 1)

18  A class B circuit in protected premises shall be designed and installed in a manner to ensure so that a _____________________ signal shall annunciate in the condition of an open or ground condition in the wiring.  Supervisory  Alarm  Trouble  None of the above

19  Trouble (23.5.2)

20  Actuation of alarm notification appliances or emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ____________ after the activation of an initiating device.  5 seconds  10 seconds  30 seconds  1 minute

21  10 seconds (23.8.1.1)

22  Signals from a carbon monoxide detectors and carbon monoxide detection systems transmitted to a fire alarm system shall be permitted to be ______________________ signals.  Alarm  Trouble  Supervisory  Indicative

23  Supervisory (23.8.4.7)

24  Visible notification signals _______________________ be required in exit stair enclosures and exit passageways.  Shall  Shall not

25  Shall not (23.8.6.2.1)

26  The evacuation signal ____________________ be required to operate in elevator cars.  Shall  Shall not

27  Shall not (23.8.6.2.4)

28  As applies to guard’s tour supervisory service, the system shall automatically transmit a delinquency signal within ________________ after the predetermined actuation time if the guard fails to actuate a tour station as scheduled.  10 seconds  30 seconds  5 minutes  15 minutes

29  15 minutes (23.16.4)

30  The occurrence of any single fault at the protected premises that disables transmission between any low-power radio transmitter and the receiver/ fire alarm control unit shall cause a latching trouble signal within ____________.  10 seconds  30 seconds  60 seconds  200 seconds

31  200 seconds (23.18.4.2)

32  A fire alarm system must be supplied by a minimum of __________ independent and reliable power supplies.  One  Two  Three  Four

33  Two (10.5.3.2)

34  A coded alarm signal shall consist of not less than__________ complete rounds of the number transmitted.  One  Two  Three  Four

35  Three (10.9.3)

36  A coded supervisory signal shall be permitted to consist of ___________ rounds of the number transmitted to indicate a supervisory off-normal condition.  One  Two  Three  Four

37  Two (10.11.1.1)

38  Two way telephone communications circuit installation conductors shall be monitored for ______________ fault conditions that would cause the telephone communications circuit to become fully or partially inoperative.  Ground fault  Open fault  Both ground fault and open fault  None of the above

39  Open fault (10.17.2.2.1)

40  Spot type smoke detectors shall be located on the ceiling, or if on a side wall, between the ceiling and ___________ inches down from the ceiling to the top of the detector.  6 inches  12 inches  18 inches  24 inches

41  12 inches ( 17.7.3.2.1)

42  The lamps and LED’s for the control equipment of a Mass Notification System shall be visually inspected ________________________________.  Monthly  Quarterly  Semi-annually  Annually

43  Semi-Annually (Table 14.3.1 Page 57)

44

45  In the absence of a specific performance based design criteria, smooth ceiling smoke detector spacing shall be a nominal _________ feet.

46  30 feet 17.7.3.2.3.1

47  Signals with carbon monoxide detectors transmitted to a fire alarm system shall be permitted to be _____________________________ signals.

48  Supervisory 23.8.4.7

49  When a supervising station receives a trouble signal they must dispatch personnel with in ________ hours to initiate maintenance, if necessary.

50  4 hours 26.3.7.4

51  Complete records of all signals received by a supervising station shall be kept for a period of ________________.

52  1 year 26.4.6.1

53  A type public alarm system shall be required where the number of all alarms required to be retransmitted exceeds _____________ per year.

54  2500 27.5.2.1.2

55  A fire alarm system installed in an occupancy that does not require a fire alarm system shall ____________________________.  A. comply with NFPA 72  B. not be required to comply with NFPA 72  C. comply with chapters 17 and 18 of NFPA 72 only  D. comply with the NEC only

56  A. comply with NFPA 72 (23.2.3.1)

57  A class A circuit in a protected premises using physical conductors shall be installed so that the outgoing and return conductors are routed separately unless for a distance not to exceed __________ feet where the conductors enter or exit the initiating device, notification appliance, or control unit enclosures.  3  6  10  15

58  10 (23.4.2.2 List item 1)

59  A class B circuit in protected premises shall be designed and installed in a manner to ensure so that a _____________________ signal shall annunciate in the condition of an open or ground condition in the wiring.  Supervisory  Alarm  Trouble  None of the above

60  Trouble (23.5.2)

61  Actuation of alarm notification appliances or emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ____________ after the activation of an initiating device.  5 seconds  10 seconds  30 seconds  1 minute

62  10 seconds (23.8.1.1)

63  Signals from a carbon monoxide detectors and carbon monoxide detection systems transmitted to a fire alarm system shall be permitted to be ______________________ signals.  Alarm  Trouble  Supervisory  Indicative

64  Supervisory (23.8.4.7)

65  Visible notification signals _______________________ be required in exit stair enclosures and exit passageways.  Shall  Shall not

66  Shall not (23.8.6.2.1)

67  The evacuation signal ____________________ be required to operate in elevator cars.  Shall  Shall not

68  Shall not (23.8.6.2.4)

69  As applies to guard’s tour supervisory service, the system shall automatically transmit a delinquency signal within ________________ after the predetermined actuation time if the guard fails to actuate a tour station as scheduled.  10 seconds  30 seconds  5 minutes  15 minutes

70  15 minutes (23.16.4)

71  The occurrence of any single fault at the protected premises that disables transmission between any low-power radio transmitter and the receiver/ fire alarm control unit shall cause a latching trouble signal within ____________.  10 seconds  30 seconds  60 seconds  200 seconds

72  200 seconds (23.18.4.2)

73  A fire alarm system must be supplied by a minimum of __________ independent and reliable power supplies.  One  Two  Three  Four

74  Two (10.5.3.2)

75  A coded alarm signal shall consist of not less than__________ complete rounds of the number transmitted.  One  Two  Three  Four

76  Three (10.9.3)

77  A coded supervisory signal shall be permitted to consist of ___________ rounds of the number transmitted to indicate a supervisory off-normal condition.  One  Two  Three  Four

78  Two (10.11.1.1)

79  Two way telephone communications circuit installation conductors shall be monitored for ______________ fault conditions that would cause the telephone communications circuit to become fully or partially inoperative.  Ground fault  Open fault  Both ground fault and open fault  None of the above

80  Open fault (10.17.2.2.1)

81  Spot type smoke detectors shall be located on the ceiling, or if on a side wall, between the ceiling and ___________ inches down from the ceiling to the top of the detector.  6 inches  12 inches  18 inches  24 inches

82  12 inches ( 17.7.3.2.1)

83  The lamps and LED’s for the control equipment of a Mass Notification System shall be visually inspected ________________________________.  Monthly  Quarterly  Semi-annually  Annually

84  Semi-Annually (Table 14.3.1 Page 57)


Download ppt "Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National."