Lecture 8: Schedules and Internal Heat Gains Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to the National Renewable Energy Laboratory. All material Copyright 2002-2003 U.S.D.O.E. - All rights reserved
2
2 Importance of this Lecture to the Simulation of Buildings Every building is different in many ways: Location/exterior environment Construction/building envelope Space usage/interior environment HVAC system Thermal simulation requires information about the functions taking place inside the building and how these might add or subtract heat from the zones Thermal simulation requires information on air leakage to and from the building to determine its effect on the building heating and cooling needs Nothing is constant inside a building—people come and go, lights and equipment gets turned on and off, etc.—and the thermal simulation needs details on what is happening through the day and year within a building
3
3 Purpose of this Lecture Gain an understanding of how to internal heat gains impact and space and how to specify them People, Lights, Equipment, etc. Infiltration Schedules
4
4 Keywords Covered in this Lecture ScheduleType DaySchedule WeekSchedule Schedule People and AngleFactorList Lights Equipment—Electric, Gas, Hot Water, Steam, Baseboard (scheduled), Other Exterior Equipment Infiltration
5
5 Schedules In general, schedules are a way of specifying how much or many of a particular quantity is present or at what level something should be set, including: Occupancy density Occupancy activity Lighting Thermostatic controls Shading element density
6
6 Schedules (cont’d) For internal gains, schedules allow us to come a little closer to the real variation of building quantities than single values % of peak occupancy reality how we account for internal gains average peak
7
7 Schedules in EnergyPlus EnergyPlus uses a hierarchy of schedule pieces to create unique schedules DaySchedule: 24 hour period of schedule values WeekSchedule: Consists of various DaySchedule definitions for an entire week Schedule: Consists of various WeekSchedule definitions for an entire year ScheduleType: Optional feature that allows for some validation and limitation of schedules (avoid mistakes)
8
8 ScheduleType ScheduleType, Any Number; !- ScheduleType Name ScheduleType, Fraction, !- ScheduleType Name 0.0:1.0, !- range CONTINUOUS; !- Numeric Type ScheduleType, Temperature, !- ScheduleType Name -60:200, !- range CONTINUOUS; !- Numeric Type ScheduleType, Control Type, !- ScheduleType Name 0:4, !- range DISCRETE; !- Numeric Type Used to validate schedule values (optional) Notes:Maximum and minimum of range (inclusive) separated by colon Discrete refers to distinct integer values Continuous to any value in the range
9
9 DaySchedule DAYSCHEDULE, OC-1, !- Name Fraction, !- ScheduleType 0.0, !- Hour 1 0.0, !- Hour 2 0.0, !- Hour 3 0.0, !- Hour 4 0.0, !- Hour 5... 1.0, !- Hour 17 1.0, !- Hour 18 0.0, !- Hour 19 0.0, !- Hour 20 0.0, !- Hour 21 0.0, !- Hour 22 0.0, !- Hour 23 0.0; !- Hour 24 The day description is simply a name and the 24 hourly values associated with that name Other forms DaySchedule:Interval DaySchedule:List Can handle subhourly schedule changes Hour 1 is Midnight to 1am
10
10 WeekSchedule WEEKSCHEDULE, ActWeekSchd, !- Name ActDaySchd2, !- Sunday DAYSCHEDULE Name ActDaySchd1, !- Monday DAYSCHEDULE Name ActDaySchd1, !- Tuesday DAYSCHEDULE Name ActDaySchd1, !- Wednesday DAYSCHEDULE Name ActDaySchd1, !- Thursday DAYSCHEDULE Name ActDaySchd1, !- Friday DAYSCHEDULE Name ActDaySchd2, !- Saturday DAYSCHEDULE Name ActDaySchd3, !- Holiday DAYSCHEDULE Name ActDaySchd4, !- SummerDesignDay DAYSCHEDULE Name ActDaySchd4, !- WinterDesignDay DAYSCHEDULE Name ActDaySchd3, !- CustomDay1 DAYSCHEDULE Name ActDaySchd3; !- CustomDay2 DAYSCHEDULE Name The week description has an identifier and 12 names corresponding to previously defined DaySchedules
11
11 Schedule SCHEDULE, OCCUPY-1, !- Name Fraction, !- ScheduleType OC-WEEK, !- Name of WEEKSCHEDULE 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Annual schedule contains an identifier and the names and from-thru dates of the week schedules associated with the annual schedule Up to 52 week schedules can be specified, allowing unique specification of every day of the year Other forms WeekSchedule:Compact Schedule:Compact Repeat as needed
12
12 Complete Schedule Specification Example of an EnergyPlus Schedule: ScheduleType, Any Number; DaySchedule, Weekday, Any Number, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.10, 0.50, 1.00, 1.00, 1.00, 1.00, 0.50, 1.00, 1.00, 1.00, 0.50, 0.10, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00; DaySchedule, Weekend, Any Number, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00, 0.00; WeekSchedule, Office Occupancy Schedule, Weekend, Weekday, Weekday, Weekday, Weekday, Weekday, Weekend, Weekend, Weekend, Weekend, Weekend, Weekend; Schedule, Office Occupancy Schedule, 1, 1, 12, 31;
13
13 Types of Internal Gains People Lights Equipment Infiltration See “Input Output Reference” – Space Gains
14
14 Heat Additions from Internal Gains Sensible vs. Latent Sensible—energy addition associated with (dry- bulb) temperature change in zone Latent—energy addition associate with moisture/humidity change in zone Sensible Heat Gains Convection Thermal (Long Wavelength) Radiation Visible (Short Wavelength) Radiation (generally lights only)
15
15 People Peak Value Schedule Radiant fraction (remainder of sensible gain is convection) Activity level schedule (W/person) Total heat gain—broken up into sensible and latent fractions within the program automatically Thermal comfort reports Fanger Pierce Two-Node Kansas State University Two-Node
16
16 People: Example PEOPLE, EAST ZONE, !- Zone Name 3.000000, !- Number of People BLDG Sch 1, !- Number of People SCHEDULE Name (real--fraction) 0.3000000, !- Fraction Radiant Activity Sch, !- Activity level SCHEDULE Name (units W/person) EAST ZONE, !- PEOPLE Group Name ZoneAveraged, !- MRT Calculation Type, !- Surface Name/Angle Factor List Name Work Eff Sch, !- Work Efficiency SCHEDULE Name (0.0-1.0,real) Clothing Sch, !- Clothing Insulation SCHEDULE Name (real) Air Velo Sch, !- Air Velocity SCHEDULE Name (units m/s, real) Fanger; !- Thermal Comfort Report Type (Fanger, Pierce, KSU) Options are ZoneAveraged, SurfaceWeighted, or AngleFactor; determines the position that MRT is calculated at (center of zone, near a surface, or at a particular point through user supplied angle factors) Apply only to thermal comfort models, not the heat balance
17
17 People: Other Notes Estimating the Number of People Based on type of space/activity See ASHRAE Standard 62 for estimates Example: 7 people/100m 2 for an office setting Estimating the Activity Level Based on activity within the zone See ASHRAE Handbook of Fundamentals, Thermal Comfort Chapter or Nonresidential Cooling and Heating Load Calculation Procedures Chapter for estimates Example: 115W/person for seated, light office work Estimating the Percent Radiant Common values range from 30-40% (0.3-0.4)
18
18 AngleFactorList Allows user to specify angle factors for various surfaces to define influence on Mean Radiant Temperature (MRT) for thermal comfort evaluation AngleFactorList, West Wing Angle Factors, !- Angle Factor List Name West Wing, !- Zone Name Zone001:Surf001, !- Surface Name 1 0.20, !- Angle Factor 1 Zone001:Surf002, !- Surface Name 2 0.20, !- Angle Factor 2 Zone001:Surf003, !- Surface Name 3 0.20, !- Angle Factor 3 Zone001:Ceiling001, !- Surface Name 4 0.15, !- Angle Factor 4 Zone001:Floor001, !- Surface Name 5 0.25; !- Angle Factor 5
19
19 Lights Peak Value (all sensible) Schedule Radiant, visible, replaceable, return air fractions (remainder is convection) Meter end use category LIGHTS, EAST ZONE, !- Zone Name BLDG Sch 3, !- SCHEDULE Name 1464.375, !- Design Level {W} 0.0000000E+00, !- Return Air Fraction 0.2000000, !- Fraction Radiant 0.2000000, !- Fraction Visible 0.0000000E+00, !- Fraction Replaceable GeneralLights; !- LightsEndUseKey
20
20 Lights: Other Notes Estimating the Input for Lighting Level Count the number and wattage of bulbs in zone Estimate using information from: Typically ranges from 1.0 – 2.0 W/ft 2, example: 1.3 W/ft 2 for office setting ASHRAE Standard 90.1 ASHRAE Handbook of Fundamentals, Nonresidential Cooling and Heating Load Calculation Procedures Chapter
21
21 Electric Equipment Peak Value Schedule Latent fraction is fraction of total Radiant and lost fractions of sensible only (remainder of sensible is convection) ELECTRIC EQUIPMENT, NORTH ZONE, !- Zone Name BLDG Sch 2, !- SCHEDULE Name 2928.751, !- Design Level {W} 0.0, !- Fraction Latent 0.3, !- Fraction Radiant 0.0; !- Fraction Lost Basically, energy that does not affect the zone heat balance (vented to exterior environment)
22
22 Electric Equipment: Other Notes Estimating the Input for Design Level See ASHRAE Handbook of Fundamentals, Nonresidential Cooling and Heating Load Calculation Procedures Chapter for approximate levels for individual components Note: Nameplate ratings are generally not good estimates of power consumption of electrical equipment (example—nameplates might add up to 35 W/m 2 but actual consumption might only be 8W/m 2 in an office setting)
23
23 Other Types of Equipment Other equipment types in EnergyPlus that have same input format as Electric Equipment (just a different keyword) Gas Equipment Hot Water Equipment Steam Equipment Other Equipment
24
24 “Scheduled” Baseboard Heaters Moderately controllable baseboard heaters that do not interact with the rest of the HVAC system Keyword is “Baseboard Heat” Baseboard Heat is first priority and will react based on outside dry-bulb temperature and input definition Baseboard that interacts with the HVAC system and controlled based on zone temperature under the following keywords: BASEBOARD HEATER:Water:Convective BASEBOARD HEATER:Electric:Convective
25
25 Baseboard Heat Example Example of Baseboard Heat usage: Response: BASEBOARD HEAT, North Zone, !- Zone Name Baseboard Availability Schedule, !- SCHEDULE Name 15000, !- Capacity at low temperature in W (> 0) 32, !- Low Temperature in degrees C 0, !- Capacity at high temperature in W (>= 0) 65, !- High Temperature in degrees C 0.3; !- Fraction Radiant (remainder of heat is convective) Outside Dry-Bulb Temperature Baseboard Output (W) 0 5000 10000 15000 3040506070
26
26 Exterior Equipment Convenient way to account for elements on exterior of building that add to overall energy consumption of site but do not affect heat balance of any zones ExteriorLights ExteriorFuelEquipment ExteriorWaterEquipment ExteriorLights, !- only used for reporting, does not affect loads Outside Lighting, !- Descriptive Name ExtLightingSched, !- SCHEDULE Name 200.0; !- Design Level (Watts)
27
27 Infiltration What is it? Definition: uncontrolled or unintended flow of outdoor air into a building due to… Cracks and other unintentional openings Normal use of exterior doors Through building materials
28
28 Infiltration (cont’d) What it’s not: Exfiltration: uncontrolled flow of indoor air out of the building, caused by “pressurizing” the building through a mechanical system (no effect on zone heat balance but effect on HVAC system) Ventilation: purposeful opening of windows or doors to promote air exchange with the outside environment (see future lecture)
29
29 Infiltration: Causes Cause: pressure differential Flow of mass from higher pressure to lower pressure area Driving forces: Wind Buoyancy or “stack” effect HVAC system Note: all of these can vary based on location within a building
30
30 Accounting for Infiltration Heat Gain/Loss Difficult to estimate More sophisticated estimates generally take a form similar to: Q=c( p) n Estimation based on either ACH or “crack” method See ASHRAE Handbook of Fundamentals, Ventilation and Infiltration Chapter for more details
31
31 ACH: Air Changes per Hour Definition: fraction of room air volume exchanged with outside air in a given hour An ACH of 1.0 means that the entire air volume of a space is replaced with outside air each hour Heat gain/loss can be significant Effect moderated by energy storage within the building
32
32 Infiltration in EnergyPlus INFILTRATION, !- Infiltration is specified as a design level which is modified !- by a schedule fraction, temperature difference and wind speed: !- Infiltration = Idesign * Fschedule * !- (A + B*|Tzone-Todb| + C*WindSpd + D * WindSpd**2) West Wing, !- Zone Name CONSTANT, !- SCHEDULE Name (Fschedule in Equation) 0.12, !- Design Volume Flow Rate in m3/s (Idesign in Equation) 1.0, !- Constant Term Coefficient (“A” in Equation) 0.0, !- Temperature Term Coefficient (“B” in Equation) 0.0, !- Velocity Term Coefficient (“C” in Equation) 0.0; !- Velocity Squared Term Coefficient (“D” in Equation) Example from an IDF file:
33
33 Summary Schedules are a vital part of EnergyPlus input and play a role in the definition of many different components Schedules are a hierarchy of: Day schedules Week schedules Schedules Scheduled heat gains/losses such as People, Lights, Equipment, Infiltration, etc. can have a significant impact on conditions within a zone and must be taken into account