Presentation is loading. Please wait.

Presentation is loading. Please wait.

Piping Systems.

Similar presentations


Presentation on theme: "Piping Systems."— Presentation transcript:

1 Piping Systems

2 Piping Systems SERIES LOOP MONOFLO SYSTEM DIRECT RETURN REVERSE RETURN
PRIMARY/SECONDARY SYSTEM BASIC PRIMARY SYSTEM SYSTEM SYZER

3

4 Hydronic System Open System Static Head Loss Friction Loss
Valve and Fitting Loss Atmospheric Pressure NPSH(a) vs. NPSH(r)

5 Hydronic System Open System Static Head Loss Friction Loss
Cooling Tower Static Head Loss Friction Loss Valve and Fitting Loss Atmospheric Pressure NPSH(a) vs. NPSH(r) Chiller

6 Open System Pressures Pump Pipe Friction Loss (Varies with flow) Total
Static Head Condenser Total Suction Head (Known head loss) Basin Water Level Pump

7 Backflow Preventer Storage Water Heater DHW System HW CW HW CW HW CW
Cooling Tower DHW System HW CW HW CW HW CW City Main Water Heater Water Heater Water Meter Backflow Preventer PRV Pump

8 Hydronic System Closed System Friction loss Valve and Fitting Loss
NO Static Head Loss Pressurized System

9 Closed System Pressures
Multi-Level Building 1 PSI = 2.31 Feet Head (ft) = head (psi) x 2.31 specific gravity

10 Closed System Pressures
Example: 4-Story Building 60 feet to top of system 26 PSI of Static Pressure Static Pressure (26 PSI) +Minimum Pressure (4 PSI) 30 PSI PRV setting = 30 PSI

11 Closed System Pressures
Example: Single Story Building 12 PSI fill pressure System can be 18 feet tall

12 Series Loop Piping

13 Monoflo System

14 Direct Return Pressure Calculations – Low Head Pressures (Piping in parallel) Heat Loss – Constant supply temperatures per load

15 Direct Return Piping

16 Reverse Return

17 Reverse Return Piping

18 Primary-Secondary Direct Return
Supply Secondary Pumps Primary - secondary Common Return Primary Pumps 18 18

19 Primary-Secondary Reverse Return
Terminals Terminals Terminals Supply Supply Return Secondary Pump Return Primary Chiller Pumps Common Pipe 19 19

20 Primary-Secondary-Tertiary
Zone C Zone A Zone B Tertiary Pumps Common Pipe Secondary Pumps Modulating Control Valves Optional Variable Speed Pump DP Sensor Common Pipe 20 Primary Pumps 20

21 Primary-Secondary-Tertiary Hybrid
Zone C Zone A Zone B Tertiary Pump Supply Secondary Pumps Common Pipe Primary Pumps Return

22 Primary Variable Speed
Two-position Control Valves Flow Meter DP Sensor Modulating Valve The newest tool available to the designer is primary variable speed. Floor space can be gained in the equipment room as well a increased operating efficiencies, especially in single chiller designs. Control of this type of system is much more complex and doses not lend well to many retrofit opportunities. VFD VFD VFD 22 22

23 Primary / Secondary Terminology: “Pump #1 can be referred to as the source or primary pump and pump #2 as the load or secondary pump.” – 2004 ASHRAE Systems and Equipment Handbook, page 12.7

24 The flow rate entering a tee must equal the flow rate leaving the tee!
Law of the “T” The flow rate entering a tee must equal the flow rate leaving the tee!

25 Law of the “T” 50 GPM 100 GPM 50 GPM

26 Law of the “T” 50 GPM 100 GPM 150 GPM

27 Law of the “T” 50 GPM 50 GPM 100 GPM 100 GPM 50 GPM

28 Law of the “T” 100 GPM 100 GPM 100 GPM 100 GPM 0 GPM

29 Law of the “T” 175 GPM 175 GPM 100 GPM 100 GPM 75 GPM

30 Prim. / Sec. -- Basics -- Common Pipe
PRIMARY SECONDARY

31 Prim. / Sec. -- Basics -- Common Pipe Flow
Pump OFF A B 100 gpm

32 Prim. / Sec. -- Basics -- Common Pipe Flow
Pump ON gpm 100 gpm gpm A B

33 Prim. / Sec. -- Basics -- Common Pipe Flow
Pump ON - 50 gpm A 100 gpm gpm B tee

34 Prim. / Sec. -- Basics -- Common Pipe Flow
Pump ON gpm A B 100 gpm gpm tee

35 Primary / Secondary --Bridge
SUPPLY RETURN PRIMARY / SECONDARY COMMON

36 P/S bridge - Front Loaded Common
Load = Production (flow in gpm) HWS TEMP F 500 SECONDARY PUMPS 500 OFF ON COMMON -- NO FLOW 500 500 EHW TEMP. 150 F HWR TEMP F

37 P/S bridge - Front Loaded Common
Load > Production (flow in gpm) HWS TEMP F 500 SECONDARY PUMPS 700 OFF ON MIXING 180) + 150) 500 COMMON 700 EHW TEMP. 150 F HWR TEMP F

38 Bridge Check Valve SUPPLY RETURN COMMON

39 P/S bridge - Front Loaded Common
Production > Load (flow in gpm) HWS TEMP. 180F 1000 SECONDARY PUMPS 800 ON ON COMMON 500 500 MIXING + 180) 800 Equally Loaded EHW TEMP. 156 F HWR TEMP F

40 Primary-Secondary System Relationship
SUPPLY RETURN PRIMARY / SECONDARY COMMON Step Function Linear Function

41 Single Boiler - Primary / Secondary
HWS T3 T1 Boiler 3-10 pipe diameters between Tees T2 T4 HWR Single Boiler - Primary / Secondary

42 Dual Boiler - Primary / Secondary
Boiler Control Boiler HWS HWR T1 T5 T6 T2 T3 T4 T7 Dual Boiler - Primary / Secondary

43 Dual Boiler - Primary / Secondary
HWS T5 T3 T1 Boiler Boiler T7 T4 T2 T6 HWR Dual Boiler - Primary / Secondary

44 Four Boiler Primary Secondary System
. .

45 Low Temperature Application Water Source Heat Pump or Radiant Heating
Problems: Boiler Condensation! Fire tube: 160 Water tube: 140 Copper fin tube: 105 Version #1 B&G balance valves w/ bypass line to provide high temp inlet water to boiler HWS T3 T1 Boiler 3-10 pipe diameters between Tees T2 T4 HWR Single Boiler - Primary / Secondary

46 Low Temperature Application Water Source Heat Pump or Radiant Heating
Problems: Boiler Condensation! Fire tube: 160 Water tube: 140 Copper fin tube: 105 Version #2 FPE Valve w/ bypass line to provide high temp inlet water to boiler HWS T3 T1 Boiler 3-10 pipe diameters between Tees T2 T4 HWR Single Boiler - Primary / Secondary

47 Low Temperature Applications
Alternate: Condensing Boiler

48 Primary Only Piping For boilers that can handle variable flow

49 System Syzer Calculator
Circular Slide Rule Analog Calculator Extremely Helpful Tool

50 Explanation Non-product specific Water Use Only

51 Heat Transfer Formula Q = m CP (T2 - T1) Btu / Hr =
Energy = mass flow x specific heat x Delta T lb 1 Btu °F Btu / Hr = Hr 8.34 lb 1 Btu °F lb 60 Min 1 Hour Min 1 Gallon X Gal Btu / Hr = Energy = mass flow x specific heat x Delta T Btu / Hr = 500 GPM T

52 Scale 1: Heat Transfer / Flow
1 MBH = 1000 Btu/hr Δt from 1 to 200º F

53 Scale 1 - Example Problem
Determine flow required for 150,000 Bth/hr using a 300DT. 10 gpm

54 “Tons” of refrigeration

55 Scale 1 - Example Problem
Determine flow required for 20 tons cooling using a 100Dt. 20 tons x 12,000 BTUH/ton = 240,000 BTUH or 240 MBH 48 gpm

56 Scale 2: Pipe Sizing Window Milinch Ft/100ft ASHRAE

57 Scale 2: Example Problem
Determine pipe size for 70 gpm in a typical hydronic system. 2½” Pipe 3.5’/100’ 3” Pipe 1.2’/100’

58 Scale 3: Flow Velocity Works with Scale 2

59 Scale 3: Example Problem
What is the velocity of 1600 gpm through an 8” pipe? Problems? 10+ fps

60 Scale 3: Example Problem
What is the velocity of 1600 gpm through an 8” pipe? Problems? 7 fps

61 Pipe Sizing / Fitting Pressure Drop
System Syzer Jacket Based On Hydraulic Institute Standards One Method, There Are Others!

62 Equivalent Lengths Table
11’

63 Scale 4: Description Pipe Length - TEL - 50% rule Friction Loss
Total Pressure Drop

64 Scale 4: Example Problem
What is the total pressure drop in a pipe with a TEL of 130’ and flow rate of 200 gpm? Scale 2 2.3’/100’ Or…. 2.3’/100’ x 130’ = 3’

65 Scale 4: Example Problem
The TEL of the longest circuit is 1500’. The head loss rate in the system piping is 3.4’/100’ at design flow. How much head does the pump have to provide to overcome the piping head loss? 1500’ 3.4’/100’ 50’

66 Scale 5: Flow/Head Relationship
Q1= Known (design) flow Q2 = Final flow h1 = Known (design) head h2 = Final head

67 Scale 5: Example Problem
A chiller has 12’ head loss at 100 gpm. What is its head loss at 150 gpm? 27’

68 Scale 5: Example Problem
A closed system has a flow rate of 200 gpm and a head loss of 30’. Plot the system curve. Flow vs Head

69 Plotting the System Curve


Download ppt "Piping Systems."

Similar presentations


Ads by Google