Download presentation
1
Piping Systems
2
Piping Systems SERIES LOOP MONOFLO SYSTEM DIRECT RETURN REVERSE RETURN
PRIMARY/SECONDARY SYSTEM BASIC PRIMARY SYSTEM SYSTEM SYZER
4
Hydronic System Open System Static Head Loss Friction Loss
Valve and Fitting Loss Atmospheric Pressure NPSH(a) vs. NPSH(r)
5
Hydronic System Open System Static Head Loss Friction Loss
Cooling Tower Static Head Loss Friction Loss Valve and Fitting Loss Atmospheric Pressure NPSH(a) vs. NPSH(r) Chiller
6
Open System Pressures Pump Pipe Friction Loss (Varies with flow) Total
Static Head Condenser Total Suction Head (Known head loss) Basin Water Level Pump
7
Backflow Preventer Storage Water Heater DHW System HW CW HW CW HW CW
Cooling Tower DHW System HW CW HW CW HW CW City Main Water Heater Water Heater Water Meter Backflow Preventer PRV Pump
8
Hydronic System Closed System Friction loss Valve and Fitting Loss
NO Static Head Loss Pressurized System
9
Closed System Pressures
Multi-Level Building 1 PSI = 2.31 Feet Head (ft) = head (psi) x 2.31 specific gravity
10
Closed System Pressures
Example: 4-Story Building 60 feet to top of system 26 PSI of Static Pressure Static Pressure (26 PSI) +Minimum Pressure (4 PSI) 30 PSI PRV setting = 30 PSI
11
Closed System Pressures
Example: Single Story Building 12 PSI fill pressure System can be 18 feet tall
12
Series Loop Piping
13
Monoflo System
14
Direct Return Pressure Calculations – Low Head Pressures (Piping in parallel) Heat Loss – Constant supply temperatures per load
15
Direct Return Piping
16
Reverse Return
17
Reverse Return Piping
18
Primary-Secondary Direct Return
Supply Secondary Pumps Primary - secondary Common Return Primary Pumps 18 18
19
Primary-Secondary Reverse Return
Terminals Terminals Terminals Supply Supply Return Secondary Pump Return Primary Chiller Pumps Common Pipe 19 19
20
Primary-Secondary-Tertiary
Zone C Zone A Zone B Tertiary Pumps Common Pipe Secondary Pumps Modulating Control Valves Optional Variable Speed Pump DP Sensor Common Pipe 20 Primary Pumps 20
21
Primary-Secondary-Tertiary Hybrid
Zone C Zone A Zone B Tertiary Pump Supply Secondary Pumps Common Pipe Primary Pumps Return
22
Primary Variable Speed
Two-position Control Valves Flow Meter DP Sensor Modulating Valve The newest tool available to the designer is primary variable speed. Floor space can be gained in the equipment room as well a increased operating efficiencies, especially in single chiller designs. Control of this type of system is much more complex and doses not lend well to many retrofit opportunities. VFD VFD VFD 22 22
23
Primary / Secondary Terminology: “Pump #1 can be referred to as the source or primary pump and pump #2 as the load or secondary pump.” – 2004 ASHRAE Systems and Equipment Handbook, page 12.7
24
The flow rate entering a tee must equal the flow rate leaving the tee!
Law of the “T” The flow rate entering a tee must equal the flow rate leaving the tee!
25
Law of the “T” 50 GPM 100 GPM 50 GPM
26
Law of the “T” 50 GPM 100 GPM 150 GPM
27
Law of the “T” 50 GPM 50 GPM 100 GPM 100 GPM 50 GPM
28
Law of the “T” 100 GPM 100 GPM 100 GPM 100 GPM 0 GPM
29
Law of the “T” 175 GPM 175 GPM 100 GPM 100 GPM 75 GPM
30
Prim. / Sec. -- Basics -- Common Pipe
PRIMARY SECONDARY
31
Prim. / Sec. -- Basics -- Common Pipe Flow
Pump OFF A B 100 gpm
32
Prim. / Sec. -- Basics -- Common Pipe Flow
Pump ON gpm 100 gpm gpm A B
33
Prim. / Sec. -- Basics -- Common Pipe Flow
Pump ON - 50 gpm A 100 gpm gpm B tee
34
Prim. / Sec. -- Basics -- Common Pipe Flow
Pump ON gpm A B 100 gpm gpm tee
35
Primary / Secondary --Bridge
SUPPLY RETURN PRIMARY / SECONDARY COMMON
36
P/S bridge - Front Loaded Common
Load = Production (flow in gpm) HWS TEMP F 500 SECONDARY PUMPS 500 OFF ON COMMON -- NO FLOW 500 500 EHW TEMP. 150 F HWR TEMP F
37
P/S bridge - Front Loaded Common
Load > Production (flow in gpm) HWS TEMP F 500 SECONDARY PUMPS 700 OFF ON MIXING 180) + 150) 500 COMMON 700 EHW TEMP. 150 F HWR TEMP F
38
Bridge Check Valve SUPPLY RETURN COMMON
39
P/S bridge - Front Loaded Common
Production > Load (flow in gpm) HWS TEMP. 180F 1000 SECONDARY PUMPS 800 ON ON COMMON 500 500 MIXING + 180) 800 Equally Loaded EHW TEMP. 156 F HWR TEMP F
40
Primary-Secondary System Relationship
SUPPLY RETURN PRIMARY / SECONDARY COMMON Step Function Linear Function
41
Single Boiler - Primary / Secondary
HWS T3 T1 Boiler 3-10 pipe diameters between Tees T2 T4 HWR Single Boiler - Primary / Secondary
42
Dual Boiler - Primary / Secondary
Boiler Control Boiler HWS HWR T1 T5 T6 T2 T3 T4 T7 Dual Boiler - Primary / Secondary
43
Dual Boiler - Primary / Secondary
HWS T5 T3 T1 Boiler Boiler T7 T4 T2 T6 HWR Dual Boiler - Primary / Secondary
44
Four Boiler Primary Secondary System
. .
45
Low Temperature Application Water Source Heat Pump or Radiant Heating
Problems: Boiler Condensation! Fire tube: 160 Water tube: 140 Copper fin tube: 105 Version #1 B&G balance valves w/ bypass line to provide high temp inlet water to boiler HWS T3 T1 Boiler 3-10 pipe diameters between Tees T2 T4 HWR Single Boiler - Primary / Secondary
46
Low Temperature Application Water Source Heat Pump or Radiant Heating
Problems: Boiler Condensation! Fire tube: 160 Water tube: 140 Copper fin tube: 105 Version #2 FPE Valve w/ bypass line to provide high temp inlet water to boiler HWS T3 T1 Boiler 3-10 pipe diameters between Tees T2 T4 HWR Single Boiler - Primary / Secondary
47
Low Temperature Applications
Alternate: Condensing Boiler
48
Primary Only Piping For boilers that can handle variable flow
49
System Syzer Calculator
Circular Slide Rule Analog Calculator Extremely Helpful Tool
50
Explanation Non-product specific Water Use Only
51
Heat Transfer Formula Q = m CP (T2 - T1) Btu / Hr =
Energy = mass flow x specific heat x Delta T lb 1 Btu °F Btu / Hr = Hr 8.34 lb 1 Btu °F lb 60 Min 1 Hour Min 1 Gallon X Gal Btu / Hr = Energy = mass flow x specific heat x Delta T Btu / Hr = 500 GPM T
52
Scale 1: Heat Transfer / Flow
1 MBH = 1000 Btu/hr Δt from 1 to 200º F
53
Scale 1 - Example Problem
Determine flow required for 150,000 Bth/hr using a 300DT. 10 gpm
54
“Tons” of refrigeration
55
Scale 1 - Example Problem
Determine flow required for 20 tons cooling using a 100Dt. 20 tons x 12,000 BTUH/ton = 240,000 BTUH or 240 MBH 48 gpm
56
Scale 2: Pipe Sizing Window Milinch Ft/100ft ASHRAE
57
Scale 2: Example Problem
Determine pipe size for 70 gpm in a typical hydronic system. 2½” Pipe 3.5’/100’ 3” Pipe 1.2’/100’
58
Scale 3: Flow Velocity Works with Scale 2
59
Scale 3: Example Problem
What is the velocity of 1600 gpm through an 8” pipe? Problems? 10+ fps
60
Scale 3: Example Problem
What is the velocity of 1600 gpm through an 8” pipe? Problems? 7 fps
61
Pipe Sizing / Fitting Pressure Drop
System Syzer Jacket Based On Hydraulic Institute Standards One Method, There Are Others!
62
Equivalent Lengths Table
11’
63
Scale 4: Description Pipe Length - TEL - 50% rule Friction Loss
Total Pressure Drop
64
Scale 4: Example Problem
What is the total pressure drop in a pipe with a TEL of 130’ and flow rate of 200 gpm? Scale 2 2.3’/100’ Or…. 2.3’/100’ x 130’ = 3’
65
Scale 4: Example Problem
The TEL of the longest circuit is 1500’. The head loss rate in the system piping is 3.4’/100’ at design flow. How much head does the pump have to provide to overcome the piping head loss? 1500’ 3.4’/100’ 50’
66
Scale 5: Flow/Head Relationship
Q1= Known (design) flow Q2 = Final flow h1 = Known (design) head h2 = Final head
67
Scale 5: Example Problem
A chiller has 12’ head loss at 100 gpm. What is its head loss at 150 gpm? 27’
68
Scale 5: Example Problem
A closed system has a flow rate of 200 gpm and a head loss of 30’. Plot the system curve. Flow vs Head
69
Plotting the System Curve
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.