Download presentation
Presentation is loading. Please wait.
Published byMelvyn Fleming Modified over 9 years ago
1
Lecture 17: VAV and Terminal Reheat Systems Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to the National Renewable Energy Laboratory. All material Copyright 2002-2003 U.S.D.O.E. - All rights reserved
2
2 Purpose of this Lecture Gain an understanding of how to: Define Air Loops and Zone Equipment input for various types of fan systems VAV Terminal Reheat Review various keywords already covered and show how they interact to form a complete system definition
3
VAV Systems in EnergyPlus
4
4 VAV with Reheat and Outside Air Example Air Loop contains the Mixed Air System, Supply Fan and the Cooling Coil Outside air system will be discussed later in more detail Zone Equipment Loop contains the Splitter, VAV Box Air Distribution Unit, the zones, and the Return Air Path with the Mixer.
5
5 VAV with Reheat Air Loop Air Primary Loop, Typical Terminal Reheat 1, !- Primary Air Loop Name Reheat System 1 Controllers, !- Name: Controller List Reheat System 1 Avail List, !- Name: System Availability Manager List 1.3, !- Primary air design volumetric flow rate {m3/s} Air Loop Branches, !- Air Loop Branch List Name, !- Air Loop Connector List Name Air Loop Inlet Node, !- ReturnAir AirLoop Inlet Node Return Air Mixer Outlet Node, !- ZoneEquipGroup Outlet Node Zone Equipment Inlet Node, !- SupplyAirPath ZoneEquipGroup Inlet Nodes Air Loop Outlet Node; !- AirLoop Outlet Nodes
6
6 VAV with Reheat Controller and Branch Lists CONTROLLER LIST, Reheat System 1 Controllers, !- Name Controller:Simple, !- Controller Type 1 Main Cooling Coil Controller; !- Controller Name 1 BRANCH LIST, Air Loop Branches, !- Branch List Name Air Loop Main Branch; !- Branch Name 1
7
7 VAV with Reheat Main Branch BRANCH, Air Loop Main Branch, !- Branch Name 1.3, !- Maximum Branch Flow Rate {m3/s} OUTSIDE AIR SYSTEM, !- Comp1 Type OA Sys 1, !- Comp1 Name Air Loop Inlet Node, !- Comp1 Inlet Node Name Mixed Air Node, !- Comp1 Outlet Node Name PASSIVE, !- Comp1 Branch Control Type FAN:SIMPLE:VariableVolume, !- Comp2 Type Var Vol Supply Fan 1, !- Comp2 Name Mixed Air Node, !- Comp2 Inlet Node Name Cooling Coil Air Inlet Node, !- Comp2 Outlet Node Name ACTIVE, !- Comp2 Branch Control Type
8
8 VAV with Reheat Main Branch (cont’d) COIL:Water:DetailedFlatCooling, !- Comp3 Type Detailed Cooling Coil, !- Comp3 Name Cooling Coil Air Inlet Node, !- Comp3 Inlet Node Name Air Loop Outlet Node, !- Comp3 Outlet Node Name PASSIVE; !- Comp3 Branch Control Type
9
9 VAV with Reheat System Availability Manager SYSTEM AVAILABILITY MANAGER LIST, Reheat System 1 Avail List, !- Name SYSTEM AVAILABILITY MANAGER:SCHEDULED, !- System Availability Manager type 1 Reheat System 1 Avail; !- System Availability Manager name 1 SYSTEM AVAILABILITY MANAGER:SCHEDULED, Reheat System 1 Avail, !- Name FanAndCoilAvailSched; !- Schedule name
10
10 VAV with Reheat Supply Fan FAN:SIMPLE:VariableVolume, Var Vol Supply Fan 1, !- Fan Name CoolingCoilAvailSched, !- Available Schedule 0.7, !- Fan Total Efficiency 600.0, !- Delta Pressure {Pa} 1.3, !- Max Flow Rate {m3/s} 0.20, !- Min Flow Rate {m3/s} 0.9, !- Motor Efficiency 1.0, !- Motor In Airstream Fraction 0.35071223, !- FanCoefficient 1 0.30850535, !- FanCoefficient 2 -0.54137364, !- FanCoefficient 3 0.87198823, !- FanCoefficient 4 0.000, !- FanCoefficient 5 Air Loop Inlet Node, !- Fan_Inlet_Node Cooling Coil Air Inlet Node; !- Fan_Outlet_Node
11
11 VAV with Reheat Cooling Coil COIL:Water:SimpleCooling, Main Cooling Coil 1, !- Coil Name CoolingCoilAvailSched, !- Available Schedule autosize, !- UA of the Coil {W/K} autosize, !- Max Water Flow Rate of Coil {m3/s} 0.9, !- Leaving Relative Humidity of Coil Main Cooling Coil 1 Water Inlet Node, !- Coil_Water_Inlet_Node Main Cooling Coil 1 Water Outlet Node, !- Coil_Water_Outlet_Node Mixed Air Node 1, !- Coil_Air_Inlet_Node Main Cooling Coil 1 Outlet Node; !- Coil_Air_Outlet_Node
12
12 VAV with Reheat Cooling Coil Controller Controller:Simple, Main Cooling Coil Controller, !- Name TEMP, !- Control variable Reverse, !- Action FLOW, !- Actuator variable Air Loop Outlet Node, !- Control_Node Cooling Coil Water Inlet Node, !- Actuator_Node 0.001, !- Controller Convergence Tolerance: delta temp from setpoint {C} 0.0011, !- Max Actuated Flow {m3/s} 0.0; !- Min Actuated Flow {m3/s}
13
13 VAV with Reheat Zone Supply Air Path ZONE SUPPLY AIR PATH, TermReheatSupplyPath, !- Supply Air Path Name Zone Equipment Inlet Node, !- Supply Air Path Inlet Node Zone Splitter, !- KEY--System Component Type Zone Supply Air Splitter; !- Component Name
14
14 VAV with Reheat Zone Splitter ZONE SPLITTER, Zone Supply Air Splitter, !- Splitter Name Zone Equipment Inlet Node, !- Inlet_Node Zone 1 Inlet Node, !- Outlet_Node_1 Zone 2 Inlet Node, !- Outlet_Node_2 Zone 3 Inlet Node; !- Outlet_Node_3
15
15 VAV with Reheat Zone Return Air Path ZONE RETURN AIR PATH, TermReheatReturnPath, !- Return Air Path Name Return Air Mixer Outlet, !- Return Air Path Outlet Node Zone Mixer, !- KEY--System Component Type 1 Zone Return Air Mixer; !- Component Name 1
16
16 VAV with Reheat Zone Mixer ZONE MIXER, Zone Return Air Mixer, !- Mixer Name Return Air Mixer Outlet, !- Outlet_Node Zone 1 Outlet Node, !- Inlet_Node_1 Zone 2 Outlet Node, !- Inlet_Node_2 Zone 3 Outlet Node; !- Inlet_Node_3
17
17 VAV with Reheat Zone Equip Configuration CONTROLLED ZONE EQUIP CONFIGURATION, RESISTIVE ZONE, !- Zone Name Zone1Equipment, !- List Name: Zone Equipment Zone1Inlets, !- List Name: Zone Inlet Nodes, !- List Name: Zone Exhaust Nodes Zone 1 Node, !- Zone Air Node Name Zone 1 Outlet Node; !- Zone Return Air Node Name
18
18 VAV with Reheat Zone Equipment List ZONE EQUIPMENT LIST, Zone1Equipment, !- Name AIR DISTRIBUTION UNIT, !- KEY--Zone Equipment Type 1 Zone1TermReheat, !- Type Name 1 1, !- Cooling Priority 1; !- Heating Priority
19
19 VAV with Reheat Air Distribution Unit AIR DISTRIBUTION UNIT, Zone1TermReheat, !- Air Distribution Unit Name Zone 1 Reheat Air Outlet Node, !- Air Dist Unit Outlet Node Name SINGLE DUCT:VAV:REHEAT, !- KEY--System Component Type 1 Zone 1 VAV System; !- Component Name 1 NODE LIST, Zone1Inlets, !- Node List Name Zone 1 Reheat Air Outlet Node; !- Node_ID_1
20
20 VAV with Reheat VAV Terminal Unit SINGLE DUCT:VAV:REHEAT, SPACE1-1 VAV Reheat, !- Name of System ReheatCoilAvailSched, !- Availability schedule for VAV System SPACE1-1 Zone Coil Air In Node, !- Damper Outlet Node SPACE1-1 ATU In Node, !- Damper Inlet Node 0.33, !- Maximum air flow rate {m3/s} 0.3, !- Min air flow fraction SPACE1-1 Zone Coil Water In Node, !- Control node COIL:Water:SimpleHeating, !- Reheat Component Object SPACE1-1 Zone Coil, !- Name of Reheat Component 0.0003, !- Max Reheat Water Flow {m3/s} 0.0, !- Min Reheat Water Flow {m3/s} SPACE1-1 In Node, !- Reheat Air Outlet Node 0.001, !- Convergence Tolerance REVERSE ACTION; !- Damper Heating Action
21
21 VAV with Reheat Reheat Coil COIL:Water:SimpleHeating, SPACE1-1 Zone Coil, !- Coil Name ReheatCoilAvailSched, !- Available Schedule 300., !- UA of the Coil {W/K} 0.0003, !- Max Water Flow Rate of Coil {m3/s} SPACE1-1 Zone Coil Water In Node, !- Coil_Water_Inlet_Node SPACE1-1 Zone Coil Water Out Node, !- Coil_Water_Outlet_Node SPACE1-1 Zone Coil Air In Node, !- Coil_Air_Inlet_Node SPACE1-1 In Node; !- Coil_Air_Outlet_Node
22
Terminal Reheat Systems in EnergyPlus
23
23 TermReheat Controller and Branch Lists CONTROLLER LIST, Reheat System 1 Controllers, !- Name Controller:Simple, !- Controller Type 1 Main Cooling Coil Controller; !- Controller Name 1 BRANCH LIST, Air Loop Branches, !- Branch List Name Air Loop Main Branch; !- Branch Name 1
24
24 TermReheat Main Branch BRANCH, Air Loop Main Branch, !- Branch Name 1.3, !- Maximum Branch Flow Rate {m3/s} FAN:SIMPLE:VariableVolume, !- Comp1 Type Var Vol Supply Fan 1, !- Comp1 Name Air Loop Inlet Node, !- Comp1 Inlet Node Name Cooling Coil Air Inlet Node, !- Comp1 Outlet Node Name ACTIVE, !- Comp1 Branch Control Type COIL:Water:DetailedFlatCooling, !- Comp2 Type Detailed Cooling Coil, !- Comp2 Name Cooling Coil Air Inlet Node, !- Comp2 Inlet Node Name Air Loop Outlet Node, !- Comp2 Outlet Node Name PASSIVE; !- Comp2 Branch Control Type
25
25 TermReheat System Availability Manager SYSTEM AVAILABILITY MANAGER LIST, Reheat System 1 Avail List, !- Name SYSTEM AVAILABILITY MANAGER:SCHEDULED, !- System Availability Manager type 1 Reheat System 1 Avail; !- System Availability Manager name 1 SYSTEM AVAILABILITY MANAGER:SCHEDULED, Reheat System 1 Avail, !- Name FanAndCoilAvailSched; !- Schedule name
26
26 TermReheat Supply Fan FAN:SIMPLE:ConstVolume, Supply Fan 1, !- Fan Name FanAndCoilAvailSched, !- Available Schedule 0.7, !- Fan Total Efficiency 600.0, !- Delta Pressure {Pa} 1.3, !- Max Flow Rate {m3/s} 0.9, !- Motor Efficiency 1.0, !- Motor In Airstream Fraction Air Loop Inlet Node, !- Fan_Inlet_Node Cooling Coil Air Inlet Node; !- Fan_Outlet_Node
27
27 TermReheat Cooling Coil COIL:Water:SimpleCooling, Main Cooling Coil 1, !- Coil Name CoolingCoilAvailSched, !- Available Schedule autosize, !- UA of the Coil {W/K} autosize, !- Max Water Flow Rate of Coil {m3/s} 0.9, !- Leaving Relative Humidity of Coil Main Cooling Coil 1 Water Inlet Node, !- Coil_Water_Inlet_Node Main Cooling Coil 1 Water Outlet Node, !- Coil_Water_Outlet_Node Mixed Air Node 1, !- Coil_Air_Inlet_Node Main Cooling Coil 1 Outlet Node; !- Coil_Air_Outlet_Node
28
28 TermReheat Cooling Coil Controller Controller:Simple, Main Cooling Coil Controller, !- Name TEMP, !- Control variable Reverse, !- Action FLOW, !- Actuator variable Air Loop Outlet Node, !- Control_Node Cooling Coil Water Inlet Node, !- Actuator_Node 0.001, !- Controller Convergence Tolerance: delta temp from setpoint {C} 0.0011, !- Max Actuated Flow {m3/s} 0.0; !- Min Actuated Flow {m3/s}
29
29 TermReheat Zone Thermostat ZONE CONTROL:THERMOSTATIC, Zone 1 Thermostat, !- Thermostat Name RESISTIVE ZONE, !- Zone Name Zone Control Type Sched, !- Control Type SCHEDULE Name SINGLE HEATING SETPOINT, !- Control Type #1 Heating Setpoint with SB, !- Control Type Name #1 SINGLE COOLING SETPOINT, !- Control Type #2 Cooling Setpoint with SB; !- Control Type Name #2
30
30 TermReheat Thermostat Setpoints SINGLE HEATING SETPOINT, Heating Setpoint with SB, !- Name Heating Setpoints; !- Setpoint Temperature SCHEDULE Name SINGLE COOLING SETPOINT, Cooling Setpoint with SB, !- Name Cooling Setpoints; !- Setpoint Temperature SCHEDULE Name
31
31 TermReheat Zone Supply Air Path ZONE SUPPLY AIR PATH, TermReheatSupplyPath, !- Supply Air Path Name Zone Equipment Inlet Node, !- Supply Air Path Inlet Node Zone Splitter, !- KEY--System Component Type Zone Supply Air Splitter; !- Component Name
32
32 TermReheat Zone Return Air Path ZONE RETURN AIR PATH, TermReheatReturnPath, !- Return Air Path Name Return Air Mixer Outlet, !- Return Air Path Outlet Node Zone Mixer, !- KEY--System Component Type 1 Zone Return Air Mixer; !- Component Name 1
33
33 TermReheat Zone Splitter ZONE SPLITTER, Zone Supply Air Splitter, !- Splitter Name Zone Equipment Inlet Node, !- Inlet_Node Zone 1 Inlet Node, !- Outlet_Node_1 Zone 2 Inlet Node, !- Outlet_Node_2 Zone 3 Inlet Node; !- Outlet_Node_3
34
34 TermReheat Zone Mixer ZONE MIXER, Zone Return Air Mixer, !- Mixer Name Return Air Mixer Outlet, !- Outlet_Node Zone 1 Outlet Node, !- Inlet_Node_1 Zone 2 Outlet Node, !- Inlet_Node_2 Zone 3 Outlet Node; !- Inlet_Node_3
35
35 TermReheat Zone Equip Configuration CONTROLLED ZONE EQUIP CONFIGURATION, RESISTIVE ZONE, !- Zone Name Zone1Equipment, !- List Name: Zone Equipment Zone1Inlets, !- List Name: Zone Inlet Nodes, !- List Name: Zone Exhaust Nodes Zone 1 Node, !- Zone Air Node Name Zone 1 Outlet Node; !- Zone Return Air Node Name
36
36 TermReheat Zone Equipment List ZONE EQUIPMENT LIST, Zone1Equipment, !- Name AIR DISTRIBUTION UNIT, !- KEY--Zone Equipment Type 1 Zone1TermReheat, !- Type Name 1 1, !- Cooling Priority 1; !- Heating Priority
37
37 TermReheat Air Distribution Unit AIR DISTRIBUTION UNIT, Zone1TermReheat, !- Air Distribution Unit Name Zone 1 Reheat Air Outlet Node, !- Air Dist Unit Outlet Node Name SINGLE DUCT:VAV:REHEAT, !- KEY--System Component Type 1 Zone 1 VAV System; !- Component Name 1 NODE LIST, Zone1Inlets, !- Node List Name Zone 1 Reheat Air Outlet Node; !- Node_ID_1
38
38 TermReheat VAV Terminal Unit SINGLE DUCT:VAV:REHEAT, SPACE1-1 VAV Reheat, !- Name of System ReheatCoilAvailSched, !- Availability schedule for VAV System SPACE1-1 Zone Coil Air In Node, !- Damper Outlet Node SPACE1-1 ATU In Node, !- Damper Inlet Node 0.33, !- Maximum air flow rate {m3/s} 0.3, !- Min air flow fraction SPACE1-1 Zone Coil Water In Node, !- Control node COIL:Water:SimpleHeating, !- Reheat Component Object SPACE1-1 Zone Coil, !- Name of Reheat Component 0.0003, !- Max Reheat Water Flow {m3/s} 0.0, !- Min Reheat Water Flow {m3/s} SPACE1-1 In Node, !- Reheat Air Outlet Node 0.001, !- Convergence Tolerance REVERSE ACTION; !- Damper Heating Action
39
39 TermReheat Reheat Coil COIL:Water:SimpleHeating, SPACE1-1 Zone Coil, !- Coil Name ReheatCoilAvailSched, !- Available Schedule 300., !- UA of the Coil {W/K} 0.0003, !- Max Water Flow Rate of Coil {m3/s} SPACE1-1 Zone Coil Water In Node, !- Coil_Water_Inlet_Node SPACE1-1 Zone Coil Water Out Node, !- Coil_Water_Outlet_Node SPACE1-1 Zone Coil Air In Node, !- Coil_Air_Inlet_Node SPACE1-1 In Node; !- Coil_Air_Outlet_Node
40
40 Summary This lecture highlighted the EnergyPlus input necessary to define most VAV and Terminal Reheat systems Air loop and zone equipment input Thermostat input Fan and coil component input Controller input
Similar presentations