Master Examination Practice Drill #8 2011 (16) O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles.

Similar presentations


Presentation on theme: "Master Examination Practice Drill #8 2011 (16) O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles."— Presentation transcript:

1

2 Master Examination Practice Drill #8 2011 (16)

3 O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles installed in _________ require GFCI protection for personnel. O I. Bathrooms O II. Kitchens A. I only B. II only C. Neither I nor II D. Both I and II

4 QuestionAnswerReferenceNEC PG. # 1.D210.8(B)(1)&(2)51

5 O 2. Communications wires and cables shall have a voltage rating of NOT less than _____. A. 60 volts B. 120 volts C. 300 volts D. 600 volts

6 QuestionAnswerReferenceNEC PG. # 2.C800.179680

7 O 3. An emergency system is required to have NO more than ______ to have power available in the event of failure of the normal electrical supply system. A. 10 seconds B. 15 seconds C. 45 seconds D. 5 minutes

8 QuestionAnswerReferenceNEC PG. # 3.A700.12624

9 O 4. X-ray equipment installed in a hospital may be served by a hard service cord with a suitable plug provided the branch-circuit rating does NOT exceed _______. A. 15 amperes B. 20 amperes C. 30 amperes D. 50 amperes

10 QuestionAnswerReferenceNEC PG. # 4.C517.71(A), Ex.455

11 O 5. Conductors supplying more than one (1) motor shall have an ampacity of NOT less than _____ of the full-load current rating of the largest motor in the group and 100% of the full-load current ratings of all the other motors in the group. A. 125 percent B. 110 percent C. 150 percent D. 175 percent

12 QuestionAnswerReferenceNEC PG. # 5.A430.24(1)&(2)318

13 O 6. Given: A straight pull of size 4 AWG and larger conductors is to be made in a junction box that will have 3 in. conduit and two (2) 2 in. conduits entering on the same side and exiting on the opposite wall. No splices will be contained in the box. Which of the following listed junction boxes is the MINIMUM required for this installation? A. 18 in. x 12 in. B. 20 in. x 18 in. C. 24 in. x 24 in. D. 30 in. x 30 in.

14 QuestionAnswerReferenceNEC PG. # 6.C314.28(A)(1)183 3in. (largest conduit) x 8 = 24 in.

15 O 7. Given” A recreational vehicle campground has one hundred-fifty (150) campsites provided with electrical power. Twenty-five (25) of the campsites are reserved as tent sites. How many of the sites are required to have a 20-ampere, 125-volt receptacle? A. 105 B. 125 C. 150 D. None

16 QuestionAnswerReferenceNEC PG. # 7.C551.71500

17 O 8. Determine the MAXIMUM overcurrent protection permitted for size 14 AWG THWN copper motor control-circuit conductors tapped from the load side of a motor overcurrent protection device. Given: The conductors require short-circuit protection and do not extend beyond the motor control equipment enclosure. A. 20 amperes B. 25 amperes C. 30 amperes D. 100 amperes

18 QuestionAnswerReferenceNEC PG. # 8.DTbl. 430.72 (B)327

19 O 9. Where size 6 AWG THWN copper branch- circuit conductors supply a 240-volt, single- phase, 5,000 VA non-motor operated appliance, the MAXIMUM standard size circuit breaker permitted for overcurrent protection on this circuit is rated _______. A. 55 amperes B. 40 amperes C. 35 amperes D. 30 amperes

20 QuestionAnswerReferenceNEC PG. # 9.C422.11(E)(3)291 Single – phase current formula 240.6(A)91 I = Power I = 5,000 VA = 20.8 amperes x 150% = 31.2 amperes Volts Volts *NOTE – The next standard size circuit breaker with a rating of 35 amperes should be selected

21 O 10. The ampacity of size 1/0 AWG THWN/THHN, dual-rated copper conductors enclosed in rigid metal conduit (RMC) when installed underground in direct contact with the earth is _______. A. 170 amperes B. 125 amperes C. 130 amperes D. 150 amperes

22 QuestionAnswerReferenceNEC PG. # 10.D300.5(B)137 Tbl. 310.104(A)169 Tbl. 310.15 (B)(16)

23 O 11. Every electrified truck parking space intended to provide an electrical supply for transport refrigerated units shall be equipped with a _______. O I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire receptacle O II. 60 ampere, 280-volt, 3-phase, 3-pole, 4-wire receptacle A. I only B. II only C. Either I or II D. Both I and II

24 QuestionAnswerReferenceNEC PG. # 11.C626.31(C(551

25 O 12. Flexible cord is permitted to be connected to fluorescent luminaires where the cord ___________. A. Has an ampacity of at least 20 amperes B. Is visible its entire length C. Is at least a size 12 AWG D. Runs through holes in walls

26 QuestionAnswerReferenceNEC PG. # 12.B410.62(C)(1)(2)a.284

27 O 13. An outdoor motor fuel gasoline dispensing pump is considered to be a Class I, Div. 2 hazardous location up to _____ above grade level within _____ horizontally from any edge of the motor fuel pump enclosure. A. 18 inches – 10 feet B. 24 inches – 20 feet C. 24 inches – 10 feet D. 18 inches – 30 feet

28 QuestionAnswerReferenceNEC PG. # 13.ATbl. 514.3(B)(1)426

29 O 14. Determine the MAXIMUM permitted operational setting of an adjustable inverse time circuit breaker used for branch-circuit, short-circuit and ground-fault protection of a 15 hp, 208-volt, three-phase, squirrel cage, Design B, continuous-duty ac motor. Assume the rating you select will be sufficient for the starting current of the motor and exceptions need not be applied. A. 46.20 amperes B. 80.85 amperes C. 115.5 amperes D. 369.6 amperes

30 QuestionAnswerReferenceNEC PG. # 14.C430.6(A)(1)311 Tbl. 430.250338 430.52(C)(1)322 Tbl. 430.52323 FLC of motor – 46.2 amperes x 250% = 115.5 amperes

31 O 15. What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. PVC conduit? A. 10 feet B. 8 feet C. 6 feet D. 5 feet

32 QuestionAnswerReferenceNEC PG. # 15.DTbl. 352.30210

33 O 16. Unless approved for a higher voltage, surface nonmetallic raceways are NOT permitted where the voltage is _______ or more between conductors. A. 120 volts B. 150 volts C. 300 volts D. 277 volts

34 QuestionAnswerReferenceNEC PG. # 16.C388.12(3)237

35 O 17. Determine the MAXIMUM size overload protection required for a 480-volt, 3-phase, 15 hp, continuous-duty ac motor, where given the following related information. Assume the value you select will permit the overload device to carry the motor load and modification of this value is not required.  Design C  Temperature rise – 40° C  Service factor – 1.12  Nameplate ampere rating – 18 amperes A. 20.7 amperesC. 22.5 amperes B. 18.0 amperesD. 23.4 amperes

36 QuestionAnswerReferenceNEC PG. # 17.A430.6(A)(2)312 430.32(A)(1)319 FLA = 18 amperes x 115% = 20.7 amperes

37 O 18. Any pipe or duct system foreign to the electrical installation must not enter a transformer vault? Which of the following listed is NOT considered foreign to the vault? A. A roof drain B. A building water main C. An air duct passing through the vault D. An automatic fire protection water sprinkler

38 QuestionAnswerReferenceNEC PG. # 18. D450.47355

39 O 19. Given: A 50 kVA transformer with a 480- volt, 3-phase, primary and a 208Y/120 volt, 3-phase secondary is to be installed. Overcurrent protection is required on both primary and secondary side of the transformer. Determine the MAXIMUM size overcurrent protection device permitted on the primary side. A. 125 amperes B. 150 amperes C. 175 amperes D. 200 amperes

40 QuestionAnswerReferenceNEC PG. # 19.B450.3(B)348 Tbl. 450.3(B)349 240.6(A(91 3 – phase current formula I = kVA x 1000 I = 50 x 1000 = 50,000 = 60.2 amperes E x 1.732 480 volts x 1.732 831.36 60.2 amperes x 250% = 150.5 amperes *NOTE – A 150 ampere OCP device is required

41 O 20. An inverse time circuit breaker used as the disconnecting means for a 50 hp, 480- volt, three-phase continuous-duty, induction- type type ac motor shall have an ampere rating of at LEAST ________. A. 82 amperes B. 75 amperes C. 163 amperes D. 98 amperes

42 QuestionAnswerReferenceNEC PG. # 20.B430.6(A)(1)311 Tbl. 430.250338 430.110(A)332 FLC of motor = 65 amperes x 74.75 amperes

43 O 21. Circuit breakers are NOT rated to carry 100 percent of the continuous load continuously, unless they have a rating for at LEAST _________. A. 100 amperes B. 200 amperes C. 400 amperes D. 600 amperes

44 QuestionAnswerReferenceNEC PG. # 21.DTrade Knowledge

45 O 22. A fifteen (15) ft. horizontal run of rigid metal conduit (RMC) is to be installed between two enclosures located in a Class II, Division 1 hazardous location. One enclosure is dust ignition proof, the other is not. The NEC® requires a MINIMUM of _______ sealing fittings. A. None required B. One C. Two D. Three

46 QuestionAnswerReferenceNEC PG. # 22.A502.15(2)387

47 O 32. Where fuses are used for motor overload protection, if the supply system is a 3-wire, 3-phase, ac with one conductor grounded, the NEC® requires a MINIMUM of how many fuses? A. None required B. One C. Two D. Three

48 QuestionAnswerReferenceNEC PG. # 23.D430.36321

49 O 24. Conductors leading to a gasoline motor fuel dispensing pump shall be _________. A. Provided with a switch B. Red in color C. Orange in color D. Insulated with MTW insulation

50 QuestionAnswerReferenceNEC PG. # 24.A514.11(A)428

51 O 25. In general, direct-buried cables of 13,000 volts must be buried at a depth of NOT less than ______. A. 24 inches B. 30 inches C. 36 inches D. 42 inches

52 QuestionAnswerReferenceNEC PG. # 25.BTbl. 300.50, Col. 1146

53 Click here to continue to non- timed drill

54 O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles installed in _________ require GFCI protection for personnel. O I. Bathrooms O II. Kitchens A. I only B. II only C. Neither I nor II D. Both I and II

55 QuestionAnswerReferenceNEC PG. # 1.D210.8(B)(1)&(2)51

56 O 2. Communications wires and cables shall have a voltage rating of NOT less than _____. A. 60 volts B. 120 volts C. 300 volts D. 600 volts

57 QuestionAnswerReferenceNEC PG. # 2.C800.179680

58 O 3. An emergency system is required to have NO more than ______ to have power available in the event of failure of the normal electrical supply system. A. 10 seconds B. 15 seconds C. 45 seconds D. 5 minutes

59 QuestionAnswerReferenceNEC PG. # 3.A700.12624

60 O 4. X-ray equipment installed in a hospital may be served by a hard service cord with a suitable plug provided the branch-circuit rating does NOT exceed _______. A. 15 amperes B. 20 amperes C. 30 amperes D. 50 amperes

61 QuestionAnswerReferenceNEC PG. # 4.C517.71(A), Ex.455

62 O 5. Conductors supplying more than one (1) motor shall have an ampacity of NOT less than _____ of the full-load current rating of the largest motor in the group and 100% of the full-load current ratings of all the other motors in the group. A. 125 percent B. 110 percent C. 150 percent D. 175 percent

63 QuestionAnswerReferenceNEC PG. # 5.A430.24(1)&(2)318

64 O 6. Given: A straight pull of size 4 AWG and larger conductors is to be made in a junction box that will have 3 in. conduit and two (2) 2 in. conduits entering on the same side and exiting on the opposite wall. No splices will be contained in the box. Which of the following listed junction boxes is the MINIMUM required for this installation? A. 18 in. x 12 in. B. 20 in. x 18 in. C. 24 in. x 24 in. D. 30 in. x 30 in.

65 QuestionAnswerReferenceNEC PG. # 6.C314.28(A)(1)183 3in. (largest conduit) x 8 = 24 in.

66 O 7. Given” A recreational vehicle campground has one hundred-fifty (150) campsites provided with electrical power. Twenty-five (25) of the campsites are reserved as tent sites. How many of the sites are required to have a 20-ampere, 125-volt receptacle? A. 105 B. 125 C. 150 D. None

67 QuestionAnswerReferenceNEC PG. # 7.C551.71500

68 O 8. Determine the MAXIMUM overcurrent protection permitted for size 14 AWG THWN copper motor control-circuit conductors tapped from the load side of a motor overcurrent protection device. Given: The conductors require short-circuit protection and do not extend beyond the motor control equipment enclosure. A. 20 amperes B. 25 amperes C. 30 amperes D. 100 amperes

69 QuestionAnswerReferenceNEC PG. # 8.DTbl. 430.72 (B)327

70 O 9. Where size 6 AWG THWN copper branch- circuit conductors supply a 240-volt, single- phase, 5,000 VA non-motor operated appliance, the MAXIMUM standard size circuit breaker permitted for overcurrent protection on this circuit is rated _______. A. 55 amperes B. 40 amperes C. 35 amperes D. 30 amperes

71 QuestionAnswerReferenceNEC PG. # 9.C422.11(E)(3)291 Single – phase current formula 240.6(A)91 I = Power I = 5,000 VA = 20.8 amperes x 150% = 31.2 amperes Volts Volts *NOTE – The next standard size circuit breaker with a rating of 35 amperes should be selected

72 O 10. The ampacity of size 1/0 AWG THWN/THHN, dual-rated copper conductors enclosed in rigid metal conduit (RMC) when installed underground in direct contact with the earth is _______. A. 170 amperes B. 125 amperes C. 130 amperes D. 150 amperes

73 QuestionAnswerReferenceNEC PG. # 10.D300.5(B)137 Tbl. 310.104(A)169 Tbl. 310.15 (B)(16)

74 O 11. Every electrified truck parking space intended to provide an electrical supply for transport refrigerated units shall be equipped with a _______. O I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire receptacle O II. 60 ampere, 280-volt, 3-phase, 3-pole, 4-wire receptacle A. I only B. II only C. Either I or II D. Both I and II

75 QuestionAnswerReferenceNEC PG. # 11.C626.31(C(551

76 O 12. Flexible cord is permitted to be connected to fluorescent luminaires where the cord ___________. A. Has an ampacity of at least 20 amperes B. Is visible its entire length C. Is at least a size 12 AWG D. Runs through holes in walls

77 QuestionAnswerReferenceNEC PG. # 12.B410.62(C)(1)(2)a.284

78 O 13. An outdoor motor fuel gasoline dispensing pump is considered to be a Class I, Div. 2 hazardous location up to _____ above grade level within _____ horizontally from any edge of the motor fuel pump enclosure. A. 18 inches – 10 feet B. 24 inches – 20 feet C. 24 inches – 10 feet D. 18 inches – 30 feet

79 QuestionAnswerReferenceNEC PG. # 13.ATbl. 514.3(B)(1)426

80 O 14. Determine the MAXIMUM permitted operational setting of an adjustable inverse time circuit breaker used for branch-circuit, short-circuit and ground-fault protection of a 15 hp, 208-volt, three-phase, squirrel cage, Design B, continuous-duty ac motor. Assume the rating you select will be sufficient for the starting current of the motor and exceptions need not be applied. A. 46.20 amperes B. 80.85 amperes C. 115.5 amperes D. 369.6 amperes

81 QuestionAnswerReferenceNEC PG. # 14.C430.6(A)(1)311 Tbl. 430.250338 430.52(C)(1)322 Tbl. 430.52323 FLC of motor – 46.2 amperes x 250% = 115.5 amperes

82 O 15. What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. PVC conduit? A. 10 feet B. 8 feet C. 6 feet D. 5 feet

83 QuestionAnswerReferenceNEC PG. # 15.DTbl. 352.30210

84 O 16. Unless approved for a higher voltage, surface nonmetallic raceways are NOT permitted where the voltage is _______ or more between conductors. A. 120 volts B. 150 volts C. 300 volts D. 277 volts

85 QuestionAnswerReferenceNEC PG. # 16.C388.12(3)237

86 O 17. Determine the MAXIMUM size overload protection required for a 480-volt, 3-phase, 15 hp, continuous-duty ac motor, where given the following related information. Assume the value you select will permit the overload device to carry the motor load and modification of this value is not required.  Design C  Temperature rise – 40° C  Service factor – 1.12  Nameplate ampere rating – 18 amperes A. 20.7 amperesC. 22.5 amperes B. 18.0 amperesD. 23.4 amperes

87 QuestionAnswerReferenceNEC PG. # 17.A430.6(A)(2)312 430.32(A)(1)319 FLA = 18 amperes x 115% = 20.7 amperes

88 O 18. Any pipe or duct system foreign to the electrical installation must not enter a transformer vault? Which of the following listed is NOT considered foreign to the vault? A. A roof drain B. A building water main C. An air duct passing through the vault D. An automatic fire protection water sprinkler

89 QuestionAnswerReferenceNEC PG. # 18. D450.47355

90 O 19. Given: A 50 kVA transformer with a 480- volt, 3-phase, primary and a 208Y/120 volt, 3-phase secondary is to be installed. Overcurrent protection is required on both primary and secondary side of the transformer. Determine the MAXIMUM size overcurrent protection device permitted on the primary side. A. 125 amperes B. 150 amperes C. 175 amperes D. 200 amperes

91 QuestionAnswerReferenceNEC PG. # 19.B450.3(B)348 Tbl. 450.3(B)349 240.6(A(91 3 – phase current formula I = kVA x 1000 I = 50 x 1000 = 50,000 = 60.2 amperes E x 1.732 480 volts x 1.732 831.36 60.2 amperes x 250% = 150.5 amperes *NOTE – A 150 ampere OCP device is required

92 O 20. An inverse time circuit breaker used as the disconnecting means for a 50 hp, 480- volt, three-phase continuous-duty, induction- type type ac motor shall have an ampere rating of at LEAST ________. A. 82 amperes B. 75 amperes C. 163 amperes D. 98 amperes

93 QuestionAnswerReferenceNEC PG. # 20.B430.6(A)(1)311 Tbl. 430.250338 430.110(A)332 FLC of motor = 65 amperes x 74.75 amperes

94 O 21. Circuit breakers are NOT rated to carry 100 percent of the continuous load continuously, unless they have a rating for at LEAST _________. A. 100 amperes B. 200 amperes C. 400 amperes D. 600 amperes

95 QuestionAnswerReferenceNEC PG. # 21.DTrade Knowledge

96 O 22. A fifteen (15) ft. horizontal run of rigid metal conduit (RMC) is to be installed between two enclosures located in a Class II, Division 1 hazardous location. One enclosure is dust ignition proof, the other is not. The NEC® requires a MINIMUM of _______ sealing fittings. A. None required B. One C. Two D. Three

97 QuestionAnswerReferenceNEC PG. # 22.A502.15(2)387

98 O 32. Where fuses are used for motor overload protection, if the supply system is a 3-wire, 3-phase, ac with one conductor grounded, the NEC® requires a MINIMUM of how many fuses? A. None required B. One C. Two D. Three

99 QuestionAnswerReferenceNEC PG. # 23.D430.36321

100 O 24. Conductors leading to a gasoline motor fuel dispensing pump shall be _________. A. Provided with a switch B. Red in color C. Orange in color D. Insulated with MTW insulation

101 QuestionAnswerReferenceNEC PG. # 24.A514.11(A)428

102 O 25. In general, direct-buried cables of 13,000 volts must be buried at a depth of NOT less than ______. A. 24 inches B. 30 inches C. 36 inches D. 42 inches

103 QuestionAnswerReferenceNEC PG. # 25.BTbl. 300.50, Col. 1146


Download ppt "Master Examination Practice Drill #8 2011 (16) O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles."