Master Examination Practice Drill #8 2011 (16)
3
O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles installed in _________ require GFCI protection for personnel. O I. Bathrooms O II. Kitchens A. I only B. II only C. Neither I nor II D. Both I and II
4
QuestionAnswerReferenceNEC PG. # 1.D210.8(B)(1)&(2)51
5
O 2. Communications wires and cables shall have a voltage rating of NOT less than _____. A. 60 volts B. 120 volts C. 300 volts D. 600 volts
6
QuestionAnswerReferenceNEC PG. # 2.C800.179680
7
O 3. An emergency system is required to have NO more than ______ to have power available in the event of failure of the normal electrical supply system. A. 10 seconds B. 15 seconds C. 45 seconds D. 5 minutes
8
QuestionAnswerReferenceNEC PG. # 3.A700.12624
9
O 4. X-ray equipment installed in a hospital may be served by a hard service cord with a suitable plug provided the branch-circuit rating does NOT exceed _______. A. 15 amperes B. 20 amperes C. 30 amperes D. 50 amperes
10
QuestionAnswerReferenceNEC PG. # 4.C517.71(A), Ex.455
11
O 5. Conductors supplying more than one (1) motor shall have an ampacity of NOT less than _____ of the full-load current rating of the largest motor in the group and 100% of the full-load current ratings of all the other motors in the group. A. 125 percent B. 110 percent C. 150 percent D. 175 percent
12
QuestionAnswerReferenceNEC PG. # 5.A430.24(1)&(2)318
13
O 6. Given: A straight pull of size 4 AWG and larger conductors is to be made in a junction box that will have 3 in. conduit and two (2) 2 in. conduits entering on the same side and exiting on the opposite wall. No splices will be contained in the box. Which of the following listed junction boxes is the MINIMUM required for this installation? A. 18 in. x 12 in. B. 20 in. x 18 in. C. 24 in. x 24 in. D. 30 in. x 30 in.
14
QuestionAnswerReferenceNEC PG. # 6.C314.28(A)(1)183 3in. (largest conduit) x 8 = 24 in.
15
O 7. Given” A recreational vehicle campground has one hundred-fifty (150) campsites provided with electrical power. Twenty-five (25) of the campsites are reserved as tent sites. How many of the sites are required to have a 20-ampere, 125-volt receptacle? A. 105 B. 125 C. 150 D. None
16
QuestionAnswerReferenceNEC PG. # 7.C551.71500
17
O 8. Determine the MAXIMUM overcurrent protection permitted for size 14 AWG THWN copper motor control-circuit conductors tapped from the load side of a motor overcurrent protection device. Given: The conductors require short-circuit protection and do not extend beyond the motor control equipment enclosure. A. 20 amperes B. 25 amperes C. 30 amperes D. 100 amperes
18
QuestionAnswerReferenceNEC PG. # 8.DTbl. 430.72 (B)327
19
O 9. Where size 6 AWG THWN copper branch- circuit conductors supply a 240-volt, single- phase, 5,000 VA non-motor operated appliance, the MAXIMUM standard size circuit breaker permitted for overcurrent protection on this circuit is rated _______. A. 55 amperes B. 40 amperes C. 35 amperes D. 30 amperes
20
QuestionAnswerReferenceNEC PG. # 9.C422.11(E)(3)291 Single – phase current formula 240.6(A)91 I = Power I = 5,000 VA = 20.8 amperes x 150% = 31.2 amperes Volts Volts *NOTE – The next standard size circuit breaker with a rating of 35 amperes should be selected
21
O 10. The ampacity of size 1/0 AWG THWN/THHN, dual-rated copper conductors enclosed in rigid metal conduit (RMC) when installed underground in direct contact with the earth is _______. A. 170 amperes B. 125 amperes C. 130 amperes D. 150 amperes
22
QuestionAnswerReferenceNEC PG. # 10.D300.5(B)137 Tbl. 310.104(A)169 Tbl. 310.15 (B)(16)
23
O 11. Every electrified truck parking space intended to provide an electrical supply for transport refrigerated units shall be equipped with a _______. O I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire receptacle O II. 60 ampere, 280-volt, 3-phase, 3-pole, 4-wire receptacle A. I only B. II only C. Either I or II D. Both I and II
24
QuestionAnswerReferenceNEC PG. # 11.C626.31(C(551
25
O 12. Flexible cord is permitted to be connected to fluorescent luminaires where the cord ___________. A. Has an ampacity of at least 20 amperes B. Is visible its entire length C. Is at least a size 12 AWG D. Runs through holes in walls
26
QuestionAnswerReferenceNEC PG. # 12.B410.62(C)(1)(2)a.284
27
O 13. An outdoor motor fuel gasoline dispensing pump is considered to be a Class I, Div. 2 hazardous location up to _____ above grade level within _____ horizontally from any edge of the motor fuel pump enclosure. A. 18 inches – 10 feet B. 24 inches – 20 feet C. 24 inches – 10 feet D. 18 inches – 30 feet
28
QuestionAnswerReferenceNEC PG. # 13.ATbl. 514.3(B)(1)426
29
O 14. Determine the MAXIMUM permitted operational setting of an adjustable inverse time circuit breaker used for branch-circuit, short-circuit and ground-fault protection of a 15 hp, 208-volt, three-phase, squirrel cage, Design B, continuous-duty ac motor. Assume the rating you select will be sufficient for the starting current of the motor and exceptions need not be applied. A. 46.20 amperes B. 80.85 amperes C. 115.5 amperes D. 369.6 amperes
30
QuestionAnswerReferenceNEC PG. # 14.C430.6(A)(1)311 Tbl. 430.250338 430.52(C)(1)322 Tbl. 430.52323 FLC of motor – 46.2 amperes x 250% = 115.5 amperes
31
O 15. What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. PVC conduit? A. 10 feet B. 8 feet C. 6 feet D. 5 feet
32
QuestionAnswerReferenceNEC PG. # 15.DTbl. 352.30210
33
O 16. Unless approved for a higher voltage, surface nonmetallic raceways are NOT permitted where the voltage is _______ or more between conductors. A. 120 volts B. 150 volts C. 300 volts D. 277 volts
34
QuestionAnswerReferenceNEC PG. # 16.C388.12(3)237
35
O 17. Determine the MAXIMUM size overload protection required for a 480-volt, 3-phase, 15 hp, continuous-duty ac motor, where given the following related information. Assume the value you select will permit the overload device to carry the motor load and modification of this value is not required. Design C Temperature rise – 40° C Service factor – 1.12 Nameplate ampere rating – 18 amperes A. 20.7 amperesC. 22.5 amperes B. 18.0 amperesD. 23.4 amperes
36
QuestionAnswerReferenceNEC PG. # 17.A430.6(A)(2)312 430.32(A)(1)319 FLA = 18 amperes x 115% = 20.7 amperes
37
O 18. Any pipe or duct system foreign to the electrical installation must not enter a transformer vault? Which of the following listed is NOT considered foreign to the vault? A. A roof drain B. A building water main C. An air duct passing through the vault D. An automatic fire protection water sprinkler
38
QuestionAnswerReferenceNEC PG. # 18. D450.47355
39
O 19. Given: A 50 kVA transformer with a 480- volt, 3-phase, primary and a 208Y/120 volt, 3-phase secondary is to be installed. Overcurrent protection is required on both primary and secondary side of the transformer. Determine the MAXIMUM size overcurrent protection device permitted on the primary side. A. 125 amperes B. 150 amperes C. 175 amperes D. 200 amperes
40
QuestionAnswerReferenceNEC PG. # 19.B450.3(B)348 Tbl. 450.3(B)349 240.6(A(91 3 – phase current formula I = kVA x 1000 I = 50 x 1000 = 50,000 = 60.2 amperes E x 1.732 480 volts x 1.732 831.36 60.2 amperes x 250% = 150.5 amperes *NOTE – A 150 ampere OCP device is required
41
O 20. An inverse time circuit breaker used as the disconnecting means for a 50 hp, 480- volt, three-phase continuous-duty, induction- type type ac motor shall have an ampere rating of at LEAST ________. A. 82 amperes B. 75 amperes C. 163 amperes D. 98 amperes
42
QuestionAnswerReferenceNEC PG. # 20.B430.6(A)(1)311 Tbl. 430.250338 430.110(A)332 FLC of motor = 65 amperes x 74.75 amperes
43
O 21. Circuit breakers are NOT rated to carry 100 percent of the continuous load continuously, unless they have a rating for at LEAST _________. A. 100 amperes B. 200 amperes C. 400 amperes D. 600 amperes
44
QuestionAnswerReferenceNEC PG. # 21.DTrade Knowledge
45
O 22. A fifteen (15) ft. horizontal run of rigid metal conduit (RMC) is to be installed between two enclosures located in a Class II, Division 1 hazardous location. One enclosure is dust ignition proof, the other is not. The NEC® requires a MINIMUM of _______ sealing fittings. A. None required B. One C. Two D. Three
46
QuestionAnswerReferenceNEC PG. # 22.A502.15(2)387
47
O 32. Where fuses are used for motor overload protection, if the supply system is a 3-wire, 3-phase, ac with one conductor grounded, the NEC® requires a MINIMUM of how many fuses? A. None required B. One C. Two D. Three
48
QuestionAnswerReferenceNEC PG. # 23.D430.36321
49
O 24. Conductors leading to a gasoline motor fuel dispensing pump shall be _________. A. Provided with a switch B. Red in color C. Orange in color D. Insulated with MTW insulation
50
QuestionAnswerReferenceNEC PG. # 24.A514.11(A)428
51
O 25. In general, direct-buried cables of 13,000 volts must be buried at a depth of NOT less than ______. A. 24 inches B. 30 inches C. 36 inches D. 42 inches
52
QuestionAnswerReferenceNEC PG. # 25.BTbl. 300.50, Col. 1146
53
Click here to continue to non- timed drill
54
O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles installed in _________ require GFCI protection for personnel. O I. Bathrooms O II. Kitchens A. I only B. II only C. Neither I nor II D. Both I and II
55
QuestionAnswerReferenceNEC PG. # 1.D210.8(B)(1)&(2)51
56
O 2. Communications wires and cables shall have a voltage rating of NOT less than _____. A. 60 volts B. 120 volts C. 300 volts D. 600 volts
57
QuestionAnswerReferenceNEC PG. # 2.C800.179680
58
O 3. An emergency system is required to have NO more than ______ to have power available in the event of failure of the normal electrical supply system. A. 10 seconds B. 15 seconds C. 45 seconds D. 5 minutes
59
QuestionAnswerReferenceNEC PG. # 3.A700.12624
60
O 4. X-ray equipment installed in a hospital may be served by a hard service cord with a suitable plug provided the branch-circuit rating does NOT exceed _______. A. 15 amperes B. 20 amperes C. 30 amperes D. 50 amperes
61
QuestionAnswerReferenceNEC PG. # 4.C517.71(A), Ex.455
62
O 5. Conductors supplying more than one (1) motor shall have an ampacity of NOT less than _____ of the full-load current rating of the largest motor in the group and 100% of the full-load current ratings of all the other motors in the group. A. 125 percent B. 110 percent C. 150 percent D. 175 percent
63
QuestionAnswerReferenceNEC PG. # 5.A430.24(1)&(2)318
64
O 6. Given: A straight pull of size 4 AWG and larger conductors is to be made in a junction box that will have 3 in. conduit and two (2) 2 in. conduits entering on the same side and exiting on the opposite wall. No splices will be contained in the box. Which of the following listed junction boxes is the MINIMUM required for this installation? A. 18 in. x 12 in. B. 20 in. x 18 in. C. 24 in. x 24 in. D. 30 in. x 30 in.
65
QuestionAnswerReferenceNEC PG. # 6.C314.28(A)(1)183 3in. (largest conduit) x 8 = 24 in.
66
O 7. Given” A recreational vehicle campground has one hundred-fifty (150) campsites provided with electrical power. Twenty-five (25) of the campsites are reserved as tent sites. How many of the sites are required to have a 20-ampere, 125-volt receptacle? A. 105 B. 125 C. 150 D. None
67
QuestionAnswerReferenceNEC PG. # 7.C551.71500
68
O 8. Determine the MAXIMUM overcurrent protection permitted for size 14 AWG THWN copper motor control-circuit conductors tapped from the load side of a motor overcurrent protection device. Given: The conductors require short-circuit protection and do not extend beyond the motor control equipment enclosure. A. 20 amperes B. 25 amperes C. 30 amperes D. 100 amperes
69
QuestionAnswerReferenceNEC PG. # 8.DTbl. 430.72 (B)327
70
O 9. Where size 6 AWG THWN copper branch- circuit conductors supply a 240-volt, single- phase, 5,000 VA non-motor operated appliance, the MAXIMUM standard size circuit breaker permitted for overcurrent protection on this circuit is rated _______. A. 55 amperes B. 40 amperes C. 35 amperes D. 30 amperes
71
QuestionAnswerReferenceNEC PG. # 9.C422.11(E)(3)291 Single – phase current formula 240.6(A)91 I = Power I = 5,000 VA = 20.8 amperes x 150% = 31.2 amperes Volts Volts *NOTE – The next standard size circuit breaker with a rating of 35 amperes should be selected
72
O 10. The ampacity of size 1/0 AWG THWN/THHN, dual-rated copper conductors enclosed in rigid metal conduit (RMC) when installed underground in direct contact with the earth is _______. A. 170 amperes B. 125 amperes C. 130 amperes D. 150 amperes
73
QuestionAnswerReferenceNEC PG. # 10.D300.5(B)137 Tbl. 310.104(A)169 Tbl. 310.15 (B)(16)
74
O 11. Every electrified truck parking space intended to provide an electrical supply for transport refrigerated units shall be equipped with a _______. O I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire receptacle O II. 60 ampere, 280-volt, 3-phase, 3-pole, 4-wire receptacle A. I only B. II only C. Either I or II D. Both I and II
75
QuestionAnswerReferenceNEC PG. # 11.C626.31(C(551
76
O 12. Flexible cord is permitted to be connected to fluorescent luminaires where the cord ___________. A. Has an ampacity of at least 20 amperes B. Is visible its entire length C. Is at least a size 12 AWG D. Runs through holes in walls
77
QuestionAnswerReferenceNEC PG. # 12.B410.62(C)(1)(2)a.284
78
O 13. An outdoor motor fuel gasoline dispensing pump is considered to be a Class I, Div. 2 hazardous location up to _____ above grade level within _____ horizontally from any edge of the motor fuel pump enclosure. A. 18 inches – 10 feet B. 24 inches – 20 feet C. 24 inches – 10 feet D. 18 inches – 30 feet
79
QuestionAnswerReferenceNEC PG. # 13.ATbl. 514.3(B)(1)426
80
O 14. Determine the MAXIMUM permitted operational setting of an adjustable inverse time circuit breaker used for branch-circuit, short-circuit and ground-fault protection of a 15 hp, 208-volt, three-phase, squirrel cage, Design B, continuous-duty ac motor. Assume the rating you select will be sufficient for the starting current of the motor and exceptions need not be applied. A. 46.20 amperes B. 80.85 amperes C. 115.5 amperes D. 369.6 amperes
81
QuestionAnswerReferenceNEC PG. # 14.C430.6(A)(1)311 Tbl. 430.250338 430.52(C)(1)322 Tbl. 430.52323 FLC of motor – 46.2 amperes x 250% = 115.5 amperes
82
O 15. What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. PVC conduit? A. 10 feet B. 8 feet C. 6 feet D. 5 feet
83
QuestionAnswerReferenceNEC PG. # 15.DTbl. 352.30210
84
O 16. Unless approved for a higher voltage, surface nonmetallic raceways are NOT permitted where the voltage is _______ or more between conductors. A. 120 volts B. 150 volts C. 300 volts D. 277 volts
85
QuestionAnswerReferenceNEC PG. # 16.C388.12(3)237
86
O 17. Determine the MAXIMUM size overload protection required for a 480-volt, 3-phase, 15 hp, continuous-duty ac motor, where given the following related information. Assume the value you select will permit the overload device to carry the motor load and modification of this value is not required. Design C Temperature rise – 40° C Service factor – 1.12 Nameplate ampere rating – 18 amperes A. 20.7 amperesC. 22.5 amperes B. 18.0 amperesD. 23.4 amperes
87
QuestionAnswerReferenceNEC PG. # 17.A430.6(A)(2)312 430.32(A)(1)319 FLA = 18 amperes x 115% = 20.7 amperes
88
O 18. Any pipe or duct system foreign to the electrical installation must not enter a transformer vault? Which of the following listed is NOT considered foreign to the vault? A. A roof drain B. A building water main C. An air duct passing through the vault D. An automatic fire protection water sprinkler
89
QuestionAnswerReferenceNEC PG. # 18. D450.47355
90
O 19. Given: A 50 kVA transformer with a 480- volt, 3-phase, primary and a 208Y/120 volt, 3-phase secondary is to be installed. Overcurrent protection is required on both primary and secondary side of the transformer. Determine the MAXIMUM size overcurrent protection device permitted on the primary side. A. 125 amperes B. 150 amperes C. 175 amperes D. 200 amperes
91
QuestionAnswerReferenceNEC PG. # 19.B450.3(B)348 Tbl. 450.3(B)349 240.6(A(91 3 – phase current formula I = kVA x 1000 I = 50 x 1000 = 50,000 = 60.2 amperes E x 1.732 480 volts x 1.732 831.36 60.2 amperes x 250% = 150.5 amperes *NOTE – A 150 ampere OCP device is required
92
O 20. An inverse time circuit breaker used as the disconnecting means for a 50 hp, 480- volt, three-phase continuous-duty, induction- type type ac motor shall have an ampere rating of at LEAST ________. A. 82 amperes B. 75 amperes C. 163 amperes D. 98 amperes
93
QuestionAnswerReferenceNEC PG. # 20.B430.6(A)(1)311 Tbl. 430.250338 430.110(A)332 FLC of motor = 65 amperes x 74.75 amperes
94
O 21. Circuit breakers are NOT rated to carry 100 percent of the continuous load continuously, unless they have a rating for at LEAST _________. A. 100 amperes B. 200 amperes C. 400 amperes D. 600 amperes
95
QuestionAnswerReferenceNEC PG. # 21.DTrade Knowledge
96
O 22. A fifteen (15) ft. horizontal run of rigid metal conduit (RMC) is to be installed between two enclosures located in a Class II, Division 1 hazardous location. One enclosure is dust ignition proof, the other is not. The NEC® requires a MINIMUM of _______ sealing fittings. A. None required B. One C. Two D. Three
97
QuestionAnswerReferenceNEC PG. # 22.A502.15(2)387
98
O 32. Where fuses are used for motor overload protection, if the supply system is a 3-wire, 3-phase, ac with one conductor grounded, the NEC® requires a MINIMUM of how many fuses? A. None required B. One C. Two D. Three
99
QuestionAnswerReferenceNEC PG. # 23.D430.36321
100
O 24. Conductors leading to a gasoline motor fuel dispensing pump shall be _________. A. Provided with a switch B. Red in color C. Orange in color D. Insulated with MTW insulation
101
QuestionAnswerReferenceNEC PG. # 24.A514.11(A)428
102
O 25. In general, direct-buried cables of 13,000 volts must be buried at a depth of NOT less than ______. A. 24 inches B. 30 inches C. 36 inches D. 42 inches
103
QuestionAnswerReferenceNEC PG. # 25.BTbl. 300.50, Col. 1146