Download presentation
1
Control & Automation For Super Critical Units
K.S. Sundaram NTPC, SIPAT
2
Introduction Requirements
Comparison of Auto loops -Sub Critical Vs Super Critical Feed Water Control Steam Temperature Control Unit Control Turbine Control Discussions
3
Super Critical Units Increased requirement of accuracy and resolution of DDCMIS systems. No drum, hence no energy reserve. Need to match fuel ,air and feed water accurately. Stringent requirement of temperature controls as unbalance in fuel and feed water has significant change in temperatures. Smooth changeovers between wet to dry operation and vice versa Control system should ensure smooth steady state operation. Little need for operator intervention.
4
Source :KEPRI
5
Source :KEPRI
6
Source :KEPRI
7
Comparsion Of Major Loops
Name of the loop Remarks SIPAT 660 MW Furnace Draft No major difference Blade pitch control, Hydraulic Air flow control PA Hdr. control Fuel master Cross limiting from FW VFD in feeders FW control Saturation Temp Controller TDBFP 2 X 65%, MDBFP 2X30% SH temp control FW plays a major role FW plays a major role (Trip at Temp >565 Deg) RH temp control No major difference . Spray Should be Zero Two tilts per corner (Trip at Temp>580 Deg)
8
List Of Loops For Discussion
S.N. Name of the loop Sub loops 01 Feed Water control Feed Water Master BCP / UG valve FWPCV control Separator Drains control 02 Super heater temp control Platen SH temp control SH steam temp control 03 RH steam temp control Burner tilt control Spray valves control
9
Feed Water Control Requirements
Ensure feed water flow in relation to unit demand. Adjust feed water flow to get the desired separator outlet temperature and degree of super heat. Ensure the rangeability of platen SH spray valves Incorporate the start up level demand. Ensure minimum required feed water flow. Convert the flow requirement into pump demand with compensation for pump capacities. Ensure protection for Fuel /FW ratio. Ensure the pumps are within the operating range.
10
Final Control Elements In FW Loop
Initial Condition Till Chemical Parameter Is Achieved Before BC Pump Start Condition From BC Pump Start / BLU Up To Load < 30 % WET MODE Load > 30 % DRY MODE MDBFP SCOOP/TDBFP Speed FW master in manual control. Initial FW flow at 200 T/Hr and Later 600T/Hr when WR opens to 30% Separator Level control Feed water flow control BC Pump Discharge Valve -- Feed water Valve ( Eq. to 30% Valve ) FW pressure control at upstream of valve FW pressure control at upstream of valve Full open and bypass valve opens Separator Drain Valves WR/ZR Separator Hi Level
11
Feed Water Master In Wet Mode
SEPARATOR LEVEL SET POINT FROM ULD ACTUAL LEVEL SUB PID ULD 300 SP 9 3 TO BFPS
12
Min FW Flow Control In Wet Mode
MIN. FW FLOW SET POINT FW FLOW TO ECONOMISER SUB DP ACROSS BC PUMP DP SET POINT ACROSS BC PUMP PID SUB < PID BC PUMP WILL TRIP IF DP IS < 4.5 Kg/Sqcm UG VALVE
13
FWPCV Valve Control In Wet Mode
BFP HEADER PRESSURE TRANSMITTERS SEL HIGHEST OF TDBFP SUCTION FLOWS HIGHEST OF MDBFP SUCTION FLOWS SUB FG FG > PID FWPCV
14
Separator Drains Control
MEASURED SEPERATOR LEVEL F(X) F(X) WR ZR
15
Wet Mode Operation Separator level control by BFPs and FW flow control by UG .Min FW flow set point from boiler desk. Initial level set point is 9 Mtr. WR and ZR will act as emergency control for separator level If water disappears in separator during wet mode then boiler will trip on separator level low low – 1.1 Mtr (3 Sec delay) Boiler will trip if separator outlet level goes high high in wet mode – 17.7 Mtr WR opens at 14.2 Mtr in auto ZR opens at 16.2 Mtr in auto
16
Wet Mode & Dry Mode Of Operation
Source: Doosan
17
Feed Water Control In Dry Mode
First controller acts on load dependant average DT across PDSH Its output represents the required adjustment to maintain the steam conditions, flue gas temperatures entering Platen SH so as to ensure adequate spray platen range. Second controller acts on load dependant separator temperature set point corrected by first controller. The output adjusts feed water in response to firing system disturbances. Minimum set point of 30% for safety is additionally provided.
18
FW Master In DRY Mode FG > TO BFPs ∑ ∑ BMD DSH SEP F2(x) F1(x) PI
SEPERATOR OUT STM TEMP FW Master In DRY Mode PLATEN SH DT BMD BOILER MASTER DEMAND DSH SEP SEPERATOR OUTLET TEMP SET POINT F2(x) F1(x) NOT DRY MODE SET TO ZERO PI FG ∑ PI FF SIGNAL ∑ ANY SCANNER FLAME (AND) BCP OFF 0 % A a 30 % b > T2 A TOTAL FW FLOW FWF FB SIGNAL F(x) PI Source : KEPRI TO BFPs
19
Platen DSH DT Set Point BM(%) DT 28.8 11 43.3 28 52.1 22 70.7 9 91 100
20
Source : EMERSON
21
Source : EMERSON
22
Source : EMERSON
23
Runbacks /Rundowns/Protections
Two TDBFPs – 120% One TDBFP + One MDBFP – 95% One TDBFP – 65% One MDBFP – 30% Rundown if FW deviation is high BFPS will go for pressure control when FW deviation is very high ID / FD / PA runback demand is 396 MW and turbine trip is 330 MW Protections Feed water flow low low for 10 sec ( 440 T/Hr) Vertical wall tube metal temperature Hi Hi (4/48) (479 Deg) MS / RH STEAM temperature Hi Hi 565/580 Deg All BFP off for 20 Sec
24
Platen SH Temperature Control
DT across PDSH is taken care by Feed water control. DT across FDSH and Load dependant DT SP acts on master with over/ under firing FF which is derived from comparing rate of change of fuel flow to rate of change of steam flow. Master output goes to slave via SP correction from steam flow where input is PDSH outlet with saturation temp limitation. Incase of start up only master controller will be in service.
25
Final DSH DT Set Point BM(%) DT 28.8 27 43.3 21 52.1 18 70.7 7 91 100
26
SH Temperature Profile
DIV SH PLATEN SH FINAL SH 451 440 486 480 406 540 DSH1 DSH2 15% 3%
27
Source : KEPRI
28
Final SH Temperature Control
DT across FDSH is taken care by Platen SH temperature control. Final SH O/L temp and Load dependant temp SP acts on master with over/under firing FF which is derived from comparing rate of change of fuel flow to rate of change of steam flow. Master output goes to slave via SP correction from steam flow where input is FDSH outlet with saturation temp limitation. Incase of start up only master controller will be in service.
29
Source : KEPRI
30
RH Temperature Control (Tilt)
RH O/L AVG temp and temp SP (568 DEG) with RHDSH DT correction (Max 5 DEG) correction fed to PID, PID output with airflow FF goes to 2 sets of tilt - one for wind box and other for SOFA
31
Source : KEPRI
32
RH Temperature Control By Spray
RH O/L temp and load dependant temp. SP acts on master controller. Master controller output is corrected with over/ under firing FF which is derived from comparing rate of change of fuel flow to rate of change of steam flow. Master O/P goes to slave via SP correction from steam flow where input is RHDSH outlet with saturation temp. limitation.
33
Source : KEPRI
34
Source :KEPRI
35
Source : EMERSON
36
Source : EMERSON
37
Turbine Control Speed Loop- Till synchronization (IP Rolling)
IP is Throttle governing & HP is Nozzle governing Open load loop till HP is charged Pressure Control when HP is charged Sliding Pressure Operation from 90 to 247 Kg/sqcm Achieve full load & put on CMC Salient Features: Individual EHC for individual valves No Hydraulic back up operation
38
HP BP Control
39
LPBP Control
40
References KEPRI logics EMERSON Logics
41
THANK YOU
42
FEED WATER PATH INITIAL STAGE
Back VERTICAL WW SEPARATORS FWRS STORAGE TANK ECONOMISER Spiral water walls ECO I/L HPH F L ASH T ANK WR ZR CONDENSER CEP LPH DA 42
43
FEED WATER PATH - LOAD < 30%
Back VERTICAL WW SEPARATORS STORAGE TANK HPH ECONOMISER Spiral water walls ECO I/L MIXING PIECE BCP UG
44
FEED WATER PATH – LOAD > 30%
Back FEED WATER PATH – LOAD > 30% S E P A R T O S E P A R T O VERTICAL WW HPH ECONOMISER Spiral water walls ECO I/L TO BACKPASS CONNECTING PIPES
46
CCP Auto Start And Auto Stop Conditions
Source :Doosan
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.