Download presentation
Presentation is loading. Please wait.
Published byAnnis Reeves Modified over 9 years ago
1
Distribution Lightning Protection Pilot Projects Reliability Engineering Team Lightning Arrester Initiative Presented by Tim Constanzo, PE
2
Where it all started Corporate initiative to improve reliability Reliability Summit Root cause analysis methodology Relay philosophy/settings Maintenance, allocation of resources Backbone initiative (distribution system design) Lightning arresters (LA’s)
3
Problem Statement Lightning arresters (LAs) are believed to be the cause of an unacceptable frequency and duration of customer interruptions and outages.
4
Probing Questions How bad is it? Why/how are LA’s failing? How effective is current application of LA’s on system?
5
How bad is it? Estimated population: 39,000 35kV line LAs 300,000 35kV equipment LAs Total 35kV LAs: 339,000 35kV LAs issued for maintenance FYE 2005: 500 Ratio of replacements to total population: 0.15% Circuit outages in FYE 2005 LA related: 135 LA related rate of circuit outages: 8.7%
6
How/why are LA’s failing? Fishbone and Pareto graphs/Root Cause LA failure categories: Proper isolator operation (not a failure!) Design/Manufacturing defects Installation Design/Practice Thermal Runaway
7
Normal Operation Isolator designed to operate when capacity of LA is exceeded Lightning TOV No outage caused Loss of protection until replaced Reduced BIL/CFO until replaced
8
LA Design/Manufacturing Issues Poor design/manufacturing Poor seals Voids under sheds Recommendation: Revise LA standards to eliminate designs with poor seal and voids under sheds.
9
Failure due to moisture ingress
10
Installation Design Current installation design/practice Long leads wrapping around primary Reduced Insulation/BIL after isolator operates Recommendations: Shorter leads Eliminate insulating bracket
11
Tracking Failure of Bracket
12
Installation T & E Option
13
Thermal Runaway Cause: Aging zinc oxide block material Moisture ingress (most common) Effect: High leakage current Marginalized MCOV Elevated temperature Recommendations: IR patrol removal when +10°C/18°F above ambient
14
Current Application of LA’s Line arresters 27 kV/22 kV MCOV (Heavy Duty) ¼-mile spacing, all phases Equipment arresters 27 kV/22 kV MCOV (Heavy Duty) All equipment
15
Evaluating LA Application TFlash modeling cases: Baseline: no arresters Arresters @ ¼ mile, 3 phases Every pole, center phase only Every pole, raised center phase only Every pole, 3 phases
16
TFlash Results
17
Conclusions/Recommendations Discontinue current application: “¼-mile” Let attrition remove line LAs Maintain LAs protecting equipment Apply only when/where lightning is an issue Circuits requiring higher reliability High exposure Use higher voltage rated LA (27 -> 30 kV)
18
Lightning Arrestor Initiative Going Forward T&E lightning arrestor installation arrangements Static wire (no arresters) LA’s center phase only, every pole Further modeling in TFlash Evaluate costs of various arrangements
19
Questions?
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.