Download presentation
Presentation is loading. Please wait.
Published byGary Heath Modified over 9 years ago
1
Tuesday, March 28, 2000 Connecting the MLC9000 to the Allen Bradley SLC500 via Modbus
2
Equipment and Software Needed MLC 9000 BCM with Modbus and appropriate number LCM’s AB SLC 5/03 CPU or higher, Power Supply and Rack -5/03 is smallest CPU to support M0/M1 file transfer ProSoft MCM3150 Modbus Communications Card RSLogix 500 Programming Software for SLC500 Programming Cable for SLC500 West.RSS Driver File Communication Cable between MLC9000 and MCM3150 Card
3
SLC500 Backplane Communications Basics n SLC 500 is a modular PLC – Racks can be configured with a wide variety of modules n PLC CPU receives information from modules in rack via one of two ways – I/O Transfer n Used with Analog or Digital I/O Modules where small amounts of information are being passed – Block Transfer via M0/M1 Files n Used for large blocks of data n M0/M1 files are local to the module n Information must be transferred form M0/M1 files into usable registers – Process is known as Block Transfer
4
SLC500 Backplane Communications Basics M0M1 Integer File Block Transfer Example........................
5
Setting Up the ProSoft 3150-MCM Verify Jumpers are in position for RS485 2-Wire (Factory Default)
6
Setting Up Communications between PC and SLC500 From Start Menu, start RSLinx under Rockwell Software Under Communications, select Configure drivers
7
Setting Up Communications between PC and SLC500 From Available Driver Types select 1747-PIC/AIC+ Driver
8
Setting Up Communications between PC and SLC500 Set station number to 31, pick open comm. port on PC
9
Setting Up Communications between PC and SLC500 Close window then reboot PC to start driver
10
Loading the Driver for the 3150-MCM From Start Menu, load RSLogix 500
11
Loading the Driver for the 3150-MCM Select File, then Open and select the directory that West.RSS is stored in.
12
Loading the Driver for the 3150-MCM
13
From Menu Bar on Left, Double-Click on IO Configuration Verify Configuration for correct number of racks and position of modules
14
Loading the Driver for the 3150-MCM From Menu on left, under Data Files, double-click on N255 West Adjust N255:110 to the proper number of loops in the system
15
Loading the Driver for the 3150-MCM N255:111-N255:142 Contain the Modbus Addresses for up to 32 loops Adjust these files to match Modbus Addresses of LCM’s
16
Loading the Driver for the 3150-MCM To begin download, first go to communications menu and select System Comms
17
Loading the Driver for the 3150-MCM Select PLC to download program to Select Download
18
Loading the Driver for the 3150-MCM Select OK to begin download
19
Loading the Driver for the 3150-MCM Press Yes to Go Online
20
Completing Communications between 3150- MCM and MLC9000 MLC9000 to ProSoft 3150-MCM Cable Pin-out (RS485) 3150-MCMMLC 9000 95 (A) 14 (B) 53 (GND) 7 8
21
Diagnostics on 3150-MCM Eight indicator lights on module used as communications diagnostics
22
MLC 9000 Parameters N250 File used to hold parameters read from MLC 9000 loops 1-16 N250:XXX-address of parameter to be accessed Read-Only data, to be used by PLC or HMI for reference File N251 used for loops 17-32
23
MLC9000 Parameters Alarm Words are broken down into sixteen read accessible bits Bits are accessed through address format N250:XXX/XX
24
MLC9000 Parameters N254 File used for data to be written to MLC9000 N254:XXX-address format used for accessing write data Data has Read/Write capabilities, can be manipulated by PLC or HMI
25
MLC9000 Parameters Control Bits are broken down into 16 Read/Write bits Parameters are addressed in N254:XXX/XX format
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.