Presentation is loading. Please wait.

Presentation is loading. Please wait.

Mr. Stephen Ho, MM - PD IMD Oct 2011

Similar presentations


Presentation on theme: "Mr. Stephen Ho, MM - PD IMD Oct 2011"— Presentation transcript:

1 Mr. Stephen Ho, MM - PD IMD Oct 2011
MTR Protection System Overview For DUAT Lines Mr. Stephen Ho, MM - PD IMD Oct 2011 4/19/2017

2 MTR 33kV Power Distribution System
Transformer, cable, switchgear, bus-bar, rectifier all need protection devices. 2 10

3 MTR 1.5kV DC Traction Power Supply
DC Protection need to grade with train service loading 2 10

4 MTR Protection in associate with Switchgear
2 10

5 MTR Power System Protection
Objectives : Discriminate and isolate the faulty power system apparatus Minimise damage to equipment Reduce the extent of personnel injuries Prevent power supply interruption to other healthy loads. 2 10

6 Protection Philosophy
Reliability Selectivity Speed Sensitivity Simplicity 2 10

7 Development of Protection Relay
Electro-mechanical Static Digital / Numerical (Protection/ Control/ Metering) 2 10

8 Key System Parameters For Protection Design
Vector Group of Transformers (e.g. Yyd0, Dyn11) Earthing (solid earth), Transformer Tap (Max/ Min) Tx Impedance voltage : 5%, 1.5kVA Fault Level : 3-phase, 25kA at 33kV 20kA at 11kV 40kA at 415V 143kA peak at 1.5kV DC 2 10

9 Protection elements Current & Voltage transformers
Auxiliary DC Power Supply Multi-cores and panel wirings Protection Relay /auxiliary / Trip / Timer Relay CB Trip Coil Local Indicators / Remote alarms 2 10

10 Protection Scheme Used at MTR
Unit Protection – Clearly define protected zone Transformer Differential Prot. Pilot Wire Prot. Bus-zone protection LV Restricted earth fault Prot. Frame Leakage Protection Directional OC Prot 4/19/2017

11 Protection Scheme Used at MTR
Non-Unit Protection – Not Clearly define protected zone Over-current & Earth Fault Prot. Directional Over-current & earth fault Prot. High set Over-current Prot. Standby earth fault Prot. 4/19/2017

12 33kV Power System Protection
Cable Feeder : Pilot wire protection (Main) IDMTL OC / Directional OC (Back-up) Bus-bar : High Impedance Differential Protection 2 10

13 Unit Protection (Cable Feeder)
Substation B Pilot Wire Substation A Substation B Pilot Wire Protection Substation A Relay Pilot Wire Pilot Wire Relay CT CT Substation B Substation A Substation A 4/19/2017

14 Unit Protection (Cable Feeder)
33kV Cable Fault Substation A Substation B Clear within 140ms 4/19/2017

15 Principle of Translay “S” Protection Relay (LAR and TKL)
Typical static circulating current feeder unit protection circuit diagram Use summation transformers with a neutral section that is tapped, to provide alternative earth fault sensitivities. Phase comparators tuned to the power frequency are used for measurement and a restraint circuit gives a high level of stability for through faults and transient charging currents. Internal faults give simultaneous tripping of relays at both ends of the line, providing rapid fault clearance irrespective of whether the fault current is fed from both line ends or from only one line end. 4/19/2017

16 Directional Over Current Relay applied at MTR
Transformer side fault Feeder side fault Feeder 33/11kV R R R 33kV/ 11kV When there have a fault at either transformer side. Current will flow into the fault side from health side. Directional relay will detect the reverse current to trip the CB to clear the fault at a shorten time. When there have a fault at the transmission line . Current will flow into the fault side from health bar. Directional relay will detect the reverse current to trip the CB to clear the fault at a shorten time. 4/19/2017

17 Principles of Directional Relay
EHV side Detect the phase angle between current flow (Ia) and voltage (Vbc) whether it is forward or reverse. If fault falls within the operating zone, trip signal will send out. 4/19/2017

18 Directional relay outlook
Over current relay “MCGG52” + Directional relay “P127” with OC & EF Applied in TKL and new extensions Directional relay with O/C “CDD” (single phase only) Applied in URL Directional relay “METI” without over current elements Applied in LAL METI 4/19/2017

19 Unit Protection (Bus-bar)
Incomers Feeders Zone 2 Zone 1 4/19/2017

20 Unit Protection (Bus-bar )
Incomers Feeders Zone 2 Zone 1 Fault at Zone-2 4/19/2017

21 33kV Bus Zone Protection Principle
Circulating current arrangement was applied. This scheme can protect both phase to phase and phase to earth fault. Operational principles: If Ig is equal to -Ih, means that it is a through fault, relay will not operate. If Ig + Ih = If = non-zero, means that the fault is in between protective zone (Bus-bar), relay will send out trip signal. Ig Ih Phase and earth fault circulating current scheme using three-element relay 4/19/2017

22 Relay and Accessories of Bus-zone Protection
Tx LV winding Metrosil Connection Diagram MFAC Relay Shunt Resistor 4/19/2017

23 33kV Bus-zone Protection Relay at MTR system
Bus Zone Relay “FAC” used at URL Bus Zone Relay “MFAC” used at LAR & TKL 4/19/2017

24 11kV Bus Bar Protection Principle
Frame-Earth Leakage Protection is used in 11kV bus-bar systems in MTR. Current type relay is used to detect the current flow. Both of Frame earth path and transformer neutral return path have detected current flow. Then, trip signal will be sent out to all CBs within the zone. Otherwise, no signal given out. Only protect the phase to earth fault. Single zone frame earth protection 4/19/2017

25 Relay used at 11kV bus-bar protection systems
URL - CAG Relay LAR - MCGG22 Relay LAR - MFAG Relay 4/19/2017

26 Power Transformer Protection (33kV AC)
33/11kV Dist Tx : Bias Differential Prot (Main) LV Restricted E/F (Main) Buchholz Surge Prot (Main) Winding/ Oil Temp High Trip (Back-up) HV Over-current Prot (Back-up) LV Standby EF Prot (Back-up) 2 10

27 Type of Distribution Transformer Protection
Fault Type Protection Used Primary winding phase-phase fault Differential and Over Current Primary winding phase-earth fault Secondary winding phase-phase fault Differential Secondary winding phase-earth fault Differential and Restricted Earth Fault Inter-turn fault Differential and Buchholz Over-heating Winding temperature Tank fault 4/19/2017

28 Transformer Protection
Substation A Substation B 4/19/2017

29 Transformer Protection
Substation A Substation B RE/F When the Tx. Star winding has a fault, The R E/F relay will be operated to trip the two breakers. 4/19/2017

30 Theory of Transformer differential Protection
It is a circulating current system, red arrow is indicated the direction of secondary current flow. Normally, no current will flow into the relay except the fault in between both current transformers. If there have a fault in between both CT, current will flow into to pick up the relay as figure 2. In MTRC power systems, only Distribution Transformers is applied. Fault Point Figure 1. Normal operation current flow in between both CT Figure 2. Internal Fault in the transformer 4/19/2017

31 Inrush current when start-up the transformer
Magnetizing inrush current containing a higher harmonic component flows, causing mal-operation of relay. Restraint second harmonic to avoid mal-operation by inrush current. Contents and current profile as below of inrush current. Magnetizing Inrush Internal Fault current (Unsaturated CT) 1st Cycle 2nd Cycle 3rd Cycle DC 73.7 58 38.8 80.4 Fundamental 100 2nd Harmonic 14.2 16.4 19.9 5.2 3rd Harmonic 8.5 7.7 13.8 3.5 4th Harmonic 5.6 6.5 3.8 2.7 5th Harmonic 1.3 5.9 2.3 Typical Magnetizing inrush waveform Relative strength of Harmonics in Typical Magnetizing-Inrush and Internal Fault Currents 4/19/2017

32 Bias Restraint characteristic of Static Relay MBCH
In order to avoid unwanted operation due to spill current and yet maintain high sensitivity for internal faults, when the difference current may be relatively small, the variable percentage bias restraint characteristic as below. Normally, setting is set at 20% ~40% of rated current depending on max tap and CT mismatch. Percentage bias characteristics Actual Bias Characteristics 4/19/2017

33 P631 outline and test plugs
Numerical Differential Relay (P631) Phase shift compensation, ratio correction and zero sequence filter was applied by software. Used star-connected line CT’s on all winding of transformers CT winding. Need no interposing CT. all winding connected directly. P631 was used at ADM, KBD and PAF. P631 outline and test plugs 4/19/2017 Connection diagram

34 Transformer LV Restricted Earth Fault
It is a unit protection scheme with circulating current system. The residual current of three line current transformers is balanced against the output of a current transformer in the neutral conductor. A large percentage of the winding can be covered when neutral is solidly earthed. Providing high speed protection against earth fault for the whole transformer with relatively simple equipment. It is applied at Distribution and Service Transformers in MTR power systems with high impedance type . Restricted Earth Fault Connection Diagram 4/19/2017

35 Outlook of REF applied in MTR
Starting from LAR, we used the high impedance relay to provide high speed and stabe protection. In URL, low impedance type relay was used . The three phase current and the neutral current become the bias inputs to a differential element. Metrosil CAG relay Shunt Resistor FAG relay High impedance relay and its components Current type (low impedance) relay 4/19/2017

36 TYPICAL RECTIFIER SUBSTATION CONFIGURATION
AC33kV 33kV / 2 x 586V RECTIFIER DC1500V DOWN TRACK OVERHEAD LINE UP TRACK 4/19/2017

37 33kV Rectifier Transformer Protection
Rectifier Tx : High Set Over-current Prot (Main) Rectifier Over-current Prot (Back-up) IDMT OC/ EF Prot (Back-up) 2 10

38 Purpose of rectifier protection
The Protection of a rectifier differs from that of conventional current maximum application. A large number of rectifiers can withstand relatively long periods of over-charge without incurring damage, generally 150% for 2 hours and 300% for 1 minute. Connection Diagram 4/19/2017

39 Rectifier Protection Characteristics
Typical settings for the TMS area: Light industrial service TMS=0.025 Medium duty service TMS=0.1 Heavy duty traction TMS=0.8 The high set is typically set at 8 times rated current as this ensures HV AC protection will discriminate with fault from HV and LV sides. Operating Curve for Rectifier Curve 4/19/2017

40 Types of Rectifier Protection Relays
Midos Relay (MCTD) Micom Relay (P122) 4/19/2017

41 11 kV Circuit / Transformer Protection
Cable Feeder : IDMT OC/EF Prot (Main) Bus-bar : Frame Earth Leakage Prot 11kV/415V Service Tx : IDMT/ Inst OCEF Prot (Main) LV REF Prot (Main) Buchholz surge Prot (Main) Winding/ Oil Temp High Trip (Back-up) 2 10

42 LV Circuit Protection (415V/ 660V )
Cable Feeder/ Bus-section : IDMT OC/EF (Main) Bus-bar : LV Standby EF Prot. 2 10

43 Over Current Relay application
Normally, Earth Fault relay applied at chiller system, 3 phase with earth fault used at LV board systems and 2 phase with earth is used at 11kv side with balance load systems (e.g. service transformers). Earth Fault CT Connection 3 phase with Earth Fault CT Connection 2 phase with Earth Fault CT Connection Earth Fault Relay (CDG) 3 ph & E/F Relay (Micom 121) 2 Ph & E/F Relay (MCGG52) 4/19/2017

44 Others O/C Relay used in MTR system
Micom Relay (P122 URL new relay alternative) Midos Relay (MCGG52 LAR used) Micom relay P127 (Directional relay used at KTT new 33kV board) Numerical Relay (KCEG used at TKL & DRL) 4/19/2017

45 Discrimination by Time
Breaker nearest to the fault opened first. Time interval between relay time setting must be long enough to ensure that the upstream relay do not operate before the circuit breaker. Radial System with time discrimination 4/19/2017

46 Time Grading Principle for IDMT protection
Grading Formula : Grading Margin – = 0.1*(T1 + T2) SM (sec) T1 : Upstream Protection Operation Time T2 : Downstream Protection Operation Time SM : safety margin Apply in Radial- Fed Circuits Margin : Relay/ CT error + Overshoot time + CB Op. Time for Downstream KCGG 142 got additional 40ms for its pick-up element 4/19/2017

47 Numerical relays (For New Extension)
What is Numerical Relay? - Microprocessor to replace analog circuit used in static relays to implement relay functions What is major difference between numerical relay and EM/static relay? - Numerical Relay operate on digital input, multi-characteristic curve and has memory, which can reproduce fault incidences for post-fault analysis. How about Data Processing and Trip Decision Making ? Microprocessor to implement protection algorithm and tripping logic Minimum Operation Time 20~40ms. 4/19/2017

48 Numerical Relay Architectures
4/19/2017

49 Features of KCGG/ KCEG 142 4/19/2017

50 Characteristic Curves of KCGG/ KCEG
4/19/2017

51 Curves of KCGG/ KCEG 142 4/19/2017

52 AREVA Micom P-series Numerical Relay
4/19/2017

53 Protection feature of Micom P121
4/19/2017

54 Protection feature of Micom P121
4/19/2017

55 Fault Record of Micom Series Relay
4/19/2017

56 Download Setting by use of Micom S1
4/19/2017

57 1.5kV DC Power System Protection
Cable Feeder : DTL / Instant. OC (Main) Direct acting OC (Main) Rate of rise OC (Main) IDMT OC (Back-up) Under-volt (Back-up) Thermal OL (Back-up) Bus-bar : Frame Earth Leakage Prot 2 10

58 KBD & TWD - DC Switchgear Board
SEPCOS Relay DC Circuit Breaker 4/19/2017

59 Basic Configuration Of Sepcos Relay
Power supply board Analog input board LED indication A Stat 0v 2 4 d4/dt J1 J2 J3 J4 VPC 196 Output I 1 OK i 3 d3/dt R H A Io L m MELCHER The Power Partners output Fast VIUC VMI 12 VMI 12 VMO 12 VMO 12 Slot 10 Slot 11 Slot 12 & 13 Slot 14 & 15 CPU Board Input board Output board (each board occupy two slots 4/19/2017 Slot 12 to 15 Software Slot 10 and 11 Basic Configuration

60 DC Type Numerical Relay (Protection &Control)
Control : Inter-trip send, CB close/open, auto-reclose, anti-pumping Protection (feeder) Ufeeder monitoring (Track Alive)  DDL (I, T) positive protection  DDL (I, T) negative protection x Ufeeder min protection  Thermal protection x Imax+ protection  Imax- protection  Reverse current protection x (For incomer CB)  4/19/2017

61 DC Inter-trip Arrangement
D/A, dI/dt, Imax+, UV, IDMT, Thermal OL (LAR/TKL) UV (URL) Inter-trip Signal 1500V OHL Running Rails 4/19/2017

62 Question & Answer End of Presentation Thank You 4/19/2017


Download ppt "Mr. Stephen Ho, MM - PD IMD Oct 2011"

Similar presentations


Ads by Google