What do we do? We serve the Building Engineering Services Sector with industry leading UKAS EN45011(ISO 17065) and accredited certification, including: NICEIC Approved Contractor Scheme SBSD Certifier of Construction (Electrical Installations to BS7671) DCLG approved Competent Persons Schemes – NICEIC BAFE Third Party Certification of those organisations involved in fire detection and fire alarm systems Micro-Generation Certification Scheme (MCS) Green Deal - installer and assessor We operate nationwide serving in excess 35,000 customers ISO / IEC 17024: Certification of persons – Gas Safe Schedule records more than 60 certification schemes NICEIC certification is second largest CB for Gas engineers with more than 62k current certificates Work with a network of 100 plus 3rd party centres nationally BG is our biggest customer with 6 centres We operate, on BG behalf, all their ACS centres within their academy. Part of the Group Competence Scheme (GCS) pilot, an alternative for ACS NICEIC is in a unique position as it offers both - The Certificate of Construction scheme and Registration is an accepted alternative route to compliance through our AC scheme which is accepted by verifiers as evidence of compliance as it is UKAS accredited to EN45011. The LABSS PROCEDURAL POLICY NOTE - PR02/2013 (draft – Updated ) provided further clarification on the definition of a competent person….. A competent person is deemed to be an installer having current membership of an accredited registration scheme operated by a recognised professional body which themselves have external accreditation through a UKAS (EN45011 or ISO/IEC17024) registration scheme or another equivalent body.
5
BS7671:2008 3rd Amendment The changes have been finalised, and the third amendment will contain a significant number of changes affecting a wide variety of electrical installation work.
6
BS7671:2008 3rd Amendment First edition – 21 July 1882
In 2008 the Seventeenth Edition, BS 7671:2008 was published. This consisted of 389 pages and 1108 Regulations. 2011 the First Amendment to BS 7671:2008 was published. This consisted of 463 pages and 1274 Regulations
7
BS7671:2008 3rd Amendment The 3rd Amendment of BS 7671 will be published on 1st January 2015 and is intended to come into effect on the 1st July 2015. Installations designed after the 30th June 2015 are to comply with BS 7671:2008 incorporating Amendment 3, 2015. Installations started after 1st January but before 30th June can be to either amendment – contract specification.
8
BS7671:2008 3rd Amendment New Numbering system:
Regulations with a 100 numbers represent CENELEC harmonized document reference numbers and; 200 numbers represent UK only regulations, e.g (a new regulation we will see again later).
9
BS7671:2008 3rd Amendment Part 2 Definitions:
The definition of competent persons will be removed, to be replaced by: Instructed person (electrically) Person adequately advised or supervised by a skilled person (as defined) to enable that person to perceive risks and to avoid hazards which electricity can create. Ordinary person Person who is neither a skilled person nor an instructed person. Skilled person (electrically) Person who possesses, as appropriate to the nature of the electrical work to be undertaken, adequate education, training or practical skills, and who is able to perceive risks and avoid hazards which electricity can create. Modified to align with international electrotechnical vocabulary and remove some overlap between skilled and competent person. These changes will be reflected throughout the wiring regulations. For example, Regulation has been changed from: "Good workmanship by competent persons or persons under their supervision and proper materials shall be used in the erection of the electrical installation. Electrical equipment shall be installed in accordance with the instructions provided by the manufacturer of the equipment." to: "Good workmanship by skilled (electrically) or instructed (electrically) persons and proper materials shall be used in the erection of the electrical installation. The installation of electrical equipment shall take account of manufacturers’ instructions."
10
BS7671:2008 3rd Amendment Chapter 41- Protection against electric shock There will be a requirement for RCD protection for socket-outlets up to 20 A, and for mobile equipment with a rated current not exceeding 32A for outdoors. An exception exists for: where, other than for an installation in a dwelling, a documented risk assessment determines that the RCD protection is not necessary. For a specific labelled or otherwise suitably identified socket-outlet provided for connection of a particular item of equipment. Risk assessment must be attached to EIC/MWEIC Details of permitted exceptions (Regulations ). Where applicable, a suitable risk assessment(s) must be attached to this certificate. for a specific labelled or otherwise suitably identified socket-outlet provided for connection of a particular item of equipment. Both the Electrical Installation Certificate and the Minor Electrical Installation Certificate will see this change. This Regulation will require, in accordance with Regulation 415.1, RCD protection for socket outlets up to 20 A (and for mobile equipment up to 32 A for use outdoors) for all installations. There is, however, an exception for RCD protection (for socket outlets up to 20 A) EXCEPT FOR DWELLINGS for a specific labelled socket outlet or where a documented risk assessment determines that RCD protection is not necessary. This means that socket outlets up to 20 A in all types of installations, including commercial, domestic and industrial, will need to be protected by a 30 mA RCD unless a risk assessment can determine that it’s not necessary, EXCEPT DWELLINGS.
11
BS7671:2008 3rd Amendment Chapter 41- Protection against electric shock Maximum earth fault loop impedances given in tables 41.2, 41.3, 41.4 and 41.6 have been revised to take account of the Cmin factor. Cmin is the minimum voltage factor to take account of voltage variations which naturally occur in a supply. Maximum earth fault loop impedances given in tables 41.2, 41.3, 41.4 and 41.6 have been revised to take account of the Cmin factor. Cmin is the minimum voltage factor to take account of voltage variations that naturally occur in a supply.
12
BS7671:2008 3rd Amendment Chapter 42 - Protection against thermal effects New regulation - Regulation Within domestic (household) premises, consumer units and similar switchgear assemblies shall comply with BS EN and shall: (i) have their enclosure manufactured from non-combustible material, or (ii) be enclosed in a cabinet or enclosure constructed of non-combustible material and complying with Regulation NOTE : ferrous metal e.g. steel is deemed to be an example of a non-combustible material This new Regulation is being introduced to help to protect against fire that can result from the overheating of connections within consumer units. Overheating can arise from loose connections and connections that have not been made correctly, for example, the connection of a cable over the insulation. The implementation date for this regulation is the 1st January This does not preclude compliance with this regulation prior to this date What impact will this have? This would mean that eventually all new consumer units installed in UK homes, i.e. within domestic (household) premises must have their enclosures manufactured from a non-combustible material, or be enclosed in a cabinet or enclosure constructed from a non-combustible material. This is likely to result in an increased use of metal enclosures. What is meant by ‘within domestic (household) premises’? It is understood that Regulation applies to consumer units and similar switchgear assemblies to BS EN inside all domestic (household) premises including their integral/attached garages and outbuildings or those in close proximity.
13
BS7671:2008 3rd Amendment Chapter 51 – Common rules, compliance with standards Regulation The addition of this regulation requires every item of equipment to be suitable for the nominal voltage and where necessary take into account the highest and/or lowest voltage likely to occur in normal service.
14
BS7671:2008 3rd Amendment Chapter 51 – Common rules, compliance with standards Regulation Compatibility The designer of the fixed installation shall ensure that the installed fixed equipment, where relevant, is designed and manufactured in accordance with the EMC Directive and, upon request, the relevant documentation shall be made available. As required by EMC Directive 2004/108
15
BS7671:2008 3rd Amendment Chapter 52 – Selection and erection of wiring systems In the light of the very real dangers to fire-fighters, a new regulation (UK only) has been included giving requirements for the methods of support of wiring systems in escape routes Wiring systems in escape routes shall be supported such that they will not be liable to premature collapse in the event of a fire A new Regulation ( ) has been included giving requirements for the methods of support of wiring systems in escape routes.
16
BS7671:2008 3rd Amendment Wiring systems in escape routes shall be supported such that they will not be liable to premature collapse in the event of a fire. Non- metalic trunking or other non metallic means of support can fail when subject to either direct flames or hot products of combustion. This may lead to wiring systems hanging across access or egress routes such that they hinder the evacuation and fire fighting activitities
17
BS7671:2008 3rd Amendment Wiring systems in escape routes shall be supported such that they will not be liable to premature collapse in the event of a fire. Non- metalic trunking or other non metallic means of support can fail when subject to either direct flames or hot products of combustion. This may lead to wiring systems hanging across access or egress routes such that they hinder the evacuation and fire fighting activitities
18
BS7671:2008 3rd Amendment Chapter 52 – Selection and erection of wiring systems The regulations concerning selection and erection of wiring systems have been re-drafted and the reference to “under the supervision of a skilled or instructed person” has been removed
19
BS7671:2008 3rd Amendment Chapter 52 – Selection and erection of wiring systems It will be a requirement that cables that are concealed in a wall or partition (at a depth of less than 50 mm) are protected by a 30 mA RCD for all installations if other methods of protection are not employed. This will apply to a cable, irrespective of the depth of that cable, in a partition where the construction of the partition includes metallic parts other than fixings. including the use of cables with either an earthed metallic covering or mechanical protection, are not employed Exceptions for cables that are part of SELV or PELV
20
BS7671:2008 3rd Amendment Chapter 55 other Equipment
A new section 557 covering Auxiliary Circuits is included for low voltage electrical installations. Auxiliary circuits are defined in Part 2 as circuits for the transmission of signals intended for the detection, supervision or control of the functional status of a main circuit.
21
BS7671:2008 3rd Amendment Section 559 luminaires and lighting installation Amendment 3 also introduces a number of changes to align the BS 7671 requirements with the both latest IEC and CENELEC standards. Examples of these changes include: moving the requirements for outdoor lighting and extra-low voltage lighting installations from Section 559 to two new sections, Section 714 and Section 715.
22
BS7671:2008 3rd Amendment Section 714 - Outdoor Lighting Installations
Amendment 3 will make only minor changes to outdoor lighting installations: One important change will be that individual circuits will be required to be isolated. Recommendations for additional protection by a 30 mA RCD for telephone kiosks, bus shelters, advertising panels and town plans. car parks; gardens; parks; places open to the public; illumination of monuments; and floodlighting.
23
BS7671:2008 3rd Amendment Section 715 - Extra-low Voltage Lighting
The Amendment 3 changes in this section include: the types of wiring systems permitted voltage drop in consumer’s installations requirements for isolation, switching and control car parks; gardens; parks; places open to the public; illumination of monuments; and floodlighting.
24
BS7671:2008 3rd Amendment Part 7 Special Installations or Locations
Section 701 locations containing a bath or shower Additional protection by the use of one or more RCDs having the characteristics specified in Regulation shall be provided for: low voltage circuits serving the location low voltage circuits passing through zones 1 and 2 not serving the location
25
BS7671:2008 3rd Amendment Section 717 Mobile and Transportable Units
Regulation has been introduced, and is based on the latest CENELEC HD. The Regulation will require: An insulation monitoring device to be installed so that automatic disconnection of the supply is provided in the case of a first fault or an RCD. An earth electrode to be installed so that automatic disconnection is provided in the case of failure of the transformer to provide electrical separation. These units may be self-propelled, towed or transportable containers or cabins, for example, technical and facilities vehicles for the entertainment industry, medical services, advertising, firefighting, workshops, offices, and transportable catering units. There are many risks associated with such units, arising from: a loss of connection to earth because of temporary cable connections; the connection to different national and local electricity distribution networks; the impracticality of establishing an equipotential zone external to the unit; open-circuit faults of the PEN conductor of PME supplies, raising the potential of all metalwork (including that of the unit) to dangerous levels; shock from high functional currents flowing in protective conductors; and vibration while the vehicle or trailer is in motion, or while a transportable unit is being moved – causing faults within the unit installation.
26
BS7671:2008 3rd Amendment Section 717 Mobile and Transportable Units
New Regulation prohibits the interconnection of units with different power supply systems. This reinforces the general rules in Parts 1 to 6 of BS 7671. New Regulation gives additional requirements for installations where the generating set may operate in parallel with other sources. This also reinforces the general rules in Parts 1 to 6 of BS 7671. These units may be self-propelled, towed or transportable containers or cabins, for example, technical and facilities vehicles for the entertainment industry, medical services, advertising, firefighting, workshops, offices, and transportable catering units. There are many risks associated with such units, arising from: a loss of connection to earth because of temporary cable connections; the connection to different national and local electricity distribution networks; the impracticality of establishing an equipotential zone external to the unit; open-circuit faults of the PEN conductor of PME supplies, raising the potential of all metalwork (including that of the unit) to dangerous levels; shock from high functional currents flowing in protective conductors; and vibration while the vehicle or trailer is in motion, or while a transportable unit is being moved – causing faults within the unit installation.
27
BS7671:2008 3rd Amendment Appendix 6 - model forms for certification and reporting The schedule of inspections (for new work only) has been replaced by examples of items requiring inspection during initial verifications (which must be appended to the electrical installation certificate). Amendment 3 also makes a small number of changes to the EICR and associated notes, including a requirement to carry out an inspection within an accessible roof space where electrical equipment is present in that roof space. The condition report has a series of inspection schedules. The inspection schedules provide a detailed breakdown of the inspection that is required on each aspect of an installation so that the work is carried out in an organised and efficient manner. For example, the schedule for domestic and similar premises will include over 60 check points. Each item that is listed on the schedule as requiring checking will be accompanied with the relevant regulation number of BS 7671 for ease of reference. In addition, the form provides a facility to indicate the outcome of the inspection of each item with either a tick (acceptable condition), a code C1 or C2 (unacceptable condition), NV (not verified), Lim (limitation) or NA (not applicable). Amendment 3 will make a small number of changes to the electrical installation condition report and associated notes, including a requirement to carry out an inspection within an accessible roof space where electrical equipment is present in that roof space. Amendment 3 will make a significant change to the certification of new work: the schedule of inspections (for new work only) has been replaced by examples of items that require inspection during initial verifications (which must be appended to the electrical installation certificate).
28
BS7671:2008 3rd Amendment Appendix 6 - model forms for certification and reporting The condition report has a series of inspection schedules. The inspection schedules provide a detailed breakdown of the inspection that is required on each aspect of an installation so that the work is carried out in an organised and efficient manner. For example, the schedule for domestic and similar premises will include over 60 check points. Each item that is listed on the schedule as requiring checking will be accompanied with the relevant regulation number of BS 7671 for ease of reference. In addition, the form provides a facility to indicate the outcome of the inspection of each item with either a tick (acceptable condition), a code C1 or C2 (unacceptable condition), NV (not verified), Lim (limitation) or NA (not applicable). Amendment 3 will make a small number of changes to the electrical installation condition report and associated notes, including a requirement to carry out an inspection within an accessible roof space where electrical equipment is present in that roof space. Amendment 3 will make a significant change to the certification of new work: the schedule of inspections (for new work only) has been replaced by examples of items that require inspection during initial verifications (which must be appended to the electrical installation certificate).
29
BS7671:2008 3rd Amendment Appendix 6 - model forms for certification and reporting The condition report has a series of inspection schedules. The inspection schedules provide a detailed breakdown of the inspection that is required on each aspect of an installation so that the work is carried out in an organised and efficient manner. For example, the schedule for domestic and similar premises will include over 60 check points. Each item that is listed on the schedule as requiring checking will be accompanied with the relevant regulation number of BS 7671 for ease of reference. In addition, the form provides a facility to indicate the outcome of the inspection of each item with either a tick (acceptable condition), a code C1 or C2 (unacceptable condition), NV (not verified), Lim (limitation) or NA (not applicable). Amendment 3 will make a small number of changes to the electrical installation condition report and associated notes, including a requirement to carry out an inspection within an accessible roof space where electrical equipment is present in that roof space. Amendment 3 will make a significant change to the certification of new work: the schedule of inspections (for new work only) has been replaced by examples of items that require inspection during initial verifications (which must be appended to the electrical installation certificate).
30
BS7671:2008 3rd Amendment Old version
31
BS7671:2008 3rd Amendment New For example, the schedule for domestic and similar premises will include over 60 check points. Each item that is listed on the schedule as requiring checking will be accompanied with the relevant regulation number of BS 7671 for ease of reference.
32
And finally …… This presentation has not included all of the changes that are included in Amendment Number 3 to BS 7671, the 17th Edition of the IET Wiring Regulations. Thank you Will I need a copy of the 3rd Amendment my next visit by the NICEIC AE or the ELECSA Assessor? Every contractor will be required to hold the current version/edition of BS 7671 at their next assessment after the 1st July 2014 Will registered contractors be offering any assistance with training? CertSure Training are developing a number of courses based on the requirements of the new standard. Online UK wide workshops EAL and City & Guilds approved courses What date must we stop designing to the old standard? Installations designed after the 30th June 2015 must be to the 3rd Amendment. Installations commissioned pre transition date can be designed and installed and tested to the previous version, but will need to be certified on old certificates inline with the design date.