Download presentation
1
High Speed NCM (HS-NCM)
2
HS-NCM Overview Supports 200 nodes
No limitations when using a DVC to page over the network Two node addresses per HS-NCM Compatible only with Onyx series panels (8th and 9th edition) 8th edition products can only be used in retrofit applications
3
HS-NCM Overview NFN on IP based VDSL Network (Very High Data Rate Subscriber Line) Does not use ARCnet protocol The HS-NCM is NOT compatible with the standard NCM Noti-Fire-Net Network. Supports NUP (Notifier Universal Protocol) Can be configured as a network repeater by setting address to 0 Installs in same single module bay as NCM
4
HS-NCM Overview Each HS-NCM has: Two NUP Ports Two USB Connections
ONYX FACP, NCA-2, DVC, Veri-Fire Tools and/or Gateway Two USB Connections One Host Standard A and One On-The-Go Mini AB Veri-Fire Tools External Power Connection (Remote Repeater) Ethernet Port for Future Diagnostics
5
HS-NCM Part Numbers High Speed NCM (HS-NCM) HS-NCM-MF Multimode Fiber
HS-NCM-MFSF Multimode/Singlemode Fiber HS-NCM-SF Singlemode Fiber HS-NCM-W Wire HS-NCM-WMF Wire/Multimode Fiber HS-NCM-WSF Wire/Singlemode Fiber HS-GW-EM Embedded Gateways BACNET-GW-3 NWS-3 NFN-GW-EM-3
6
HS-NCM-W VDSL Data Rate 12Mb (Variable 3Mb-24Mb Future)
Supports twisted pair wire 18AWG- 14AWG Maximum Distance 3,000 ft. NFPA Style 4 (Class B) or Style 7 (Class A) Data is regenerated at each node
7
HS-NCM-W Channel A Connection Channel B Connection USB Connections
Ground Fault Detection Switches S1 = CH A S2 = CH B NUP Ports External Power Connection
8
HS-NCM-W Wire Requirements
MUST be Twisted Pair Prefer a Data Grade Cable (Belden) Non-Shielded Wire for High Speed Communications 200 Nodes at 3,000’ Belden 5320UJ 18/2 FPL Belden 5320UM 18/2 FPLR Genesis /2 FPL Genesis /2 FPLP Genesis /2 FPLR Genesis /2 FPLP
9
HS-NCM-W Wire Requirements
200 Nodes at 2,000’ Genesis /2 FPLR 200 Nodes at 1,000’ Genesis /2 FPLR Genesis /2 FPLR Belden 5220UM 16/2 FPLR 200 Nodes at <1,000’ Genesis /2 FPLP This cable did not pass the test for 200 nodes at distances even less than 1,000’ and therefore should not be used as a network segment cable
10
HS-NCM-MF (Multi-Mode Fiber)
Data Rate of 100Mb Supports Fiber Optic Cable 62.5/125 10dB Limit 50.0/ dB Limit NFPA Style 4 (Class B) or Style 7 (Class A) Data is regenerated at each node Fiber Connectors: LC Style
11
HS-NCM-SF (Single-Mode Fiber)
Data Rate of 100Mb Supports Fiber Optic Cable 9/125 30dB Limit NFPA Style 4 (Class B) or Style 7 (Class A) Data is regenerated at each node Fiber Connectors: LC Style
12
HS-NCM-SF (Single-Mode Fiber)
NO CONVERTERS REQUIRED !!! Previous singlemode fiber segment required two NCM-F, two singlemode converters and mounting kit.
13
HS-NCM Hybrids (Wire to Fiber)
HS-NCM-WSF HS-NCM-WMF Multi-Mode fiber to Single-Mode fiber converter not shown
14
ONYXWorks™ Intel 2.0 GHz Pentium IV microprocessor 1 GB RAM 80 GB hard drive 1.44 MB floppy drive 24/10/40X CD-RW drive 19” Flatscreen LCD monitor Microsoft Windows XP
15
HS-NCS High Speed ONYXWorks
ONYXWORKS-HNMF (High Speed NFN Multi-mode Fiber) ONYXWORKS-HNSF ONYXWORKS-HNW High Speed card for ONYXWorks Add-On (Upgrade current ONYXWorks) NFN-GW-PC-HNMF NFN-GW-PC-HNSF NFN-GW-PC-HNW
16
HS-NCS Cards for ONYXWorks NOT compatible with the NCS Workstation
HS-NCS-MF HS-NCS-SF NOT compatible with the NCS Workstation For ONYXWorks only HS-NCS-W
17
HS-NCM Applications 100 DVC,NCA-2,Gateway or another FACP NUP NUP USB
2 Node Addresses USB NFN NFN Veri-Fire Tools 100 HS-NCM HS-NCM
18
HS-NCM Applications 200 Veri-Fire Tools NUP (either/or connection) NUP
USB HS-NCM 1 Node Address USB NFN NFN 200 Veri-Fire Tools HS-NCM HS-NCM
19
HS-NCM USB Limitations
USB connection for the HS-NCM is NOT supported on the fire panels until the following releases: NFS Release 14.1 NFS2-640/NFS-320 Release 15.0 USB Connections not supported on NFS-640 or NFS-3030 Do not use the USB Mini On-The-Go connection on the fire panel
20
Any Questions ?
Similar presentations
© 2025 SlidePlayer.com. Inc.