Presentation is loading. Please wait.

Presentation is loading. Please wait.

INSULATION TESTER CALIBRATION Using the 3200 Electrical Test Calibrator.

Similar presentations


Presentation on theme: "INSULATION TESTER CALIBRATION Using the 3200 Electrical Test Calibrator."— Presentation transcript:

1

2 INSULATION TESTER CALIBRATION Using the 3200 Electrical Test Calibrator

3 The 3200 has five functions for calibrating insulation testers : 1.High value resistance output for insulation testing (0 MOhms to 2,000MOhms) 2.Measurement of the insulation test voltage 3.Low value resistance for continuity testing (0.1 Ohm to 20.0 Ohms Variable, 100 Ohms & 1kOhm Fixed Ranges) 4.Insulation test current measurement 5.A.C. voltage output at 100V, 200V, 240V, 300V and 400V Dedicated inputs and test buttons for Insulation Testers provides safe, convenient connection & operation INSULATION TESTER CALIBRATION Overview

4 1.CONNECT TESTER TO INSULATION TESTER TERMINALS 2.SET CONTINUITY RANGE ON TESTER 3.SET CONTINUITY RESISTANCE ON 3200, EG. 1 OHM 4.MEASURE RESISTANCE USING TESTER INSULATION TESTER CALIBRATION Continuity Resistance

5 1.CONNECT TESTER TO INSULATION TESTER TERMINALS 2.SET CONTINUITY RANGE ON TESTER 3.MEASURE CONTINUITY CURRENT FROM TESTER NOTE : 1 OHM RANGE MUST BE SET ON 3200 TO ENABLE CURRENT MEASUREMENT CURRENT MEASUREMENT MODE ENABLED BY USING 1 OHM CONTINUITY RANGE INSULATION TESTER CALIBRATION Continuity Current

6 1.CONNECT TESTER TO INSULATION TESTER TERMINALS 2.SET INSULATION RANGE ON TESTER 3.SET INSULATION RESISTANCE ON 3200, EG. 10 MOHM 4.MEASURE RESISTANCE USING TESTER INSULATION TESTER CALIBRATION Insulation Resistance

7 1.CONNECT TESTER TO INSULATION TESTER TERMINALS 2.SET INSULATION TEST VOLTAGE RANGE ON TESTER 3.MEASURE INSULATION TEST VOLTAGE & CURRENT FROM TESTER BY SELECTING THE VOLTAGE MEASUREMENT FUNCTION USING THE SOFT KEY (SHOWN BELOW) VOLTAGE / CURRENT MEASUREMENT ENABLED BY USING THE SOFT KEY INSULATION TESTER CALIBRATION Insulation Test Voltage


Download ppt "INSULATION TESTER CALIBRATION Using the 3200 Electrical Test Calibrator."