1 Proposed Changes to the RTF’s Heat Pump Specifications Impact on Estimated Deemed Savings and C&R Discount Program Credits.

Similar presentations


Presentation on theme: "1 Proposed Changes to the RTF’s Heat Pump Specifications Impact on Estimated Deemed Savings and C&R Discount Program Credits."— Presentation transcript:

1 1 Proposed Changes to the RTF’s Heat Pump Specifications Impact on Estimated Deemed Savings and C&R Discount Program Credits

2 2 PNW Climates Are Different Than That Used for ARI Ratings ARI performance ratings (SEER & HSPF) are based on climates that do not match the Northwest’s. –Heating Zone 1 climate is warmer than the rating location – HSPF is higher than label –Heating Zones 2 & 3 climates are colder than the rating location – HSPF is lower than label –All of the Cooling Zones in NW has lower humidity than the rating location – SEER is lower than label

3 3 Climate Adjusted HSPF

4 4 Duct Leakage and Insulation Levels Have Interactive Affects on System Efficiency Duct leakage and conductive losses reduce heat pump capacity. Duct leakage and conductive losses increase “buffer space” temperatures. As a result, duct location, duct leakage and insulation levels must all be modeled to determine overall “duct system” efficiency.

5 5 Duct “System” Assumptions Four Duct Configurations –Crawlspace – Supply ducts 100% outside conditioned space –½ Basement - Supply ducts 50% outside conditioned space –Full Basement - Supply ducts 100% inside conditioned space –Manufactured Home - Supply ducts 100% outside conditioned space Three Levels of Leakage –10% - Base –7.5% - RTF –5% - PTCS Two Levels of Duct Insulation –R-4 – Base –R-11 (R-8 installed) – RTF & PTCS

6 6 Duct System Efficiency Adjusted HSPF – All Ducts Outside Conditioned Space

7 7 Duct System Efficiency Adjusted HSPF – > 50% Ducts Outside Conditioned Space

8 8 Duct System Efficiency Adjusted HSPF – Manufactured Home Supplies Outside Conditioned Space

9 9 Duct System Efficiency Adjusted HSPF – All Ducts Inside Conditioned Space

10 10 Commissioning Heat Pumps – Adjustments for Improper Air Flow and Refrigerant Charge Field studies of heat pump and air conditioner installations reveal –Over/Under Charging of Refrigerant –Low air flow across evaporator coils RTF Specifications require: –Air flow verification using either flow plate or “temperature rise” & “volt/amp” methods –Refrigerant charge verification “according to manufacturer’s instructions” PTCS Specifications require: –Air flow verification using flow plate (TrueFlow) –Refrigerant charge verification using SubCool/SuperHeat in AC mode.

11 11 Commissioning Adjusted HSPF

12 12 Control Impact Assumptions Base Case Assumptions –Combination Timer Defrost (20%) & Demand Defrost (80%) –Some (20%) of systems have w/low ambient temperature compressor “cutouts” –Some (20%) systems have resistance backup tied to “first stage” of heat pump RTF Assumptions –Demand Defrost Only –Some (20%) systems have outside thermostats which limit “backup” above 35F –No resistance backup tied to “first stage” of heat pump PTCS Assumptions –Demand Defrost Only –All systems have outside thermostats which limit “backup” above 35F

13 13 Control Adjusted HSPF

14 14 Cumulative Adjusted HSPF – All Ducts Outside Conditioned Space

15 15 Cumulative Adjusted HSPF – 50% Ducts Outside Conditioned Space

16 16 Cumulative Adjusted HSPF – All Ducts Inside Conditioned Space

17 17 Cumulative Adjusted HSPF – Manufactured Homes – All Supplies Outside Conditioned Space

18 18 SEER Adjustment High performance air conditioning equipment is designed to “de-humidify” by recovering latent energy (heat of condensation) ARI Test Conditions assume inside temperature of 80F and outside temperature of 82F and relative humidity @100%, 90% and 80% Preliminary research appears to show that SEER ratings, when adjusted for the PNW “dry-summer” climate are about 65% of nameplate

19 19 Other Factors That Are Changing RTF’s Heat Pump Savings Revised estimates of “post-weatherization” space heating use –Reduced loads Revised estimate of air conditioning loads –New estimates based on hourly modeling of specific prototypes Better calibration with metering studies for space heating and cooling

20 20 Pre1980 Construction “Post Weatherization” Forced Air Furnace Space Heating Use

21 21 Post79/Pre93 Construction Forced Air Furnace Space Heating Use

22 22 Post92 Construction Forced Air Furnace Space Heating Use

23 23 Revised Estimates of Air Conditioning Loads Are Lower (e.g.,Pre1980 Construction)

24 24 Revised Estimates of Air Conditioning Load Are Lower (e.g., Post92 Construction)

25 25 Some Revised Estimates of Air Conditioning Load Are Higher and Lower (e.g.,Post79/Pre93 Construction)

26 26 Overall Implications for C&R Discount Values Difference Between “PTCS” Heat Pump (or CAC) Installations & Non-“PTCS” Installations Increases Difference between Non-PTCS Heat Pump (or CAC) Installations and “Baseline” Installations Decreases

27 27 Air Source Heat Pump Savings for Pre1980 FAF w/o CAC with PTCS

28 28 Air Source Heat Pump Savings for Post79/Pre93 FAF w/o CAC with PTCS

29 29 Air Source Heat Pump Savings for Post1992 FAF w/o CAC with PTCS

30 30 Air Source Heat Pump Savings for Pre1980 FAF w/o CAC – with RTF Specification

31 31 Air Source Heat Pump Savings for Post79/Pre93 FAF w/o CAC – with RTF Specifications

32 32 Air Source Heat Pump Savings for Post1992 FAF w/o CAC – with RTF Specifications

33 33 Air Source Heat Pump Savings for Pre1980 FAF w/o CAC – with PTCS vs. RTF Specifications

34 34 Air Source Heat Pump Savings for Post79/Pre93 FAF w/o CAC – with PTCS vs. RTF Specifications

35 35 Air Source Heat Pump Savings for Post1992 FAF w/o CAC – with PTCS vs. RTF Specifications

36 36 City of Richland Savings Estimates Based on sub-metered data on 54 homes Average house size = 2071 sq.ft. Average savings = 5552 kWh/yr – (2.7 kWh/sq.ft./yr) Average HSPF = 8.24 Un-reported Pre-conversion space conditioning use and CAC system

37 37 RTF Estimates Compared to City of Richland’s Analysis – Heating Only Savings City of Richland Original w/PTCS Revised w/PTCS Original w/o PTCS Revised w/o PTCS House Size 2,071 – 2,136 1,600 - 2,200 Savings (kWh/yr)5,552 – 6,706 8,560 – 10,062 5,184 – 8,530 7,532 – 8,899 4,537 – 7,467 Savings/Ton (kWh/yr) 1,828 - 2,154 2,853 – 2,875 1,728 – 2,437 2,511 – 2,543 1,512 – 2,143 Savings/sq.ft./ floor area 2.7 – 3.1 4.6 - 5.3 3.2 – 3.9 4.0 - 4.7 2.8 - 3.4

38 38 Recommendations Adopt revised deemed savings estimates for air source heat pump conversions (and heat pump and CAC efficiency upgrades) Consider using kWh/sq.ft./yr as “deemed unit” rather than kWh/yr/home Revise assumptions in Heat Pump HSPF and CAC SEER “Tradeoff Calculator” to match deemed savings analysis


Download ppt "1 Proposed Changes to the RTF’s Heat Pump Specifications Impact on Estimated Deemed Savings and C&R Discount Program Credits."