Indoor Firing Ranges Training Education Recommended Practices
2
NAFA Firing Range Guidelines l Purpose l Scope l Background
3
Ranges Potential Health Issues l OSHA n Permissible Exposure Limits (PEL) n 50 micrograms per M 3 / 8 hour period l Lead / Blood Poisoning n Fatigue, Headaches, Sleepiness n Metallic Taste, Poor Appetite, Uneasy Stomach n Toxic by Inhalation, absorption or ingestion
4
Range Areas of Potential Lead l Shooters Station l Area 15’ Down Range l Target Area
5
Shooters Station l Point of highest airborne concentration l Each shot fired releases harmful gases
6
Area 15 Feet Down Range l EPA found greater than 90% of heavier dusts settle from air stream l Becomes extremely contaminated l Should not enter without protective gear per OSHA
7
Target Area l Fragmentation of lead from bullets is highest l Bullet Capture
8
Ventilating Ranges 50-100 fpm Sufficient Levels of Outside Air Negative Pressure In Range Area Isolated Ventilation
9
Typical Range Diagram
10
System Designs Single Pass System Simplest Design 100% Outside Air Re-circulating System Filter & Re-introduced Exhaust for Negative Pressure Down Range -Filtered Make-up Air 10% less than Exhaust
11
Filtration Requirements Two Concerns for HVAC Makeup Air Exhaust Air
12
Makeup Air ASHRAE Standard 52.2 Minimum Efficiency Reporting Value (MERV) 14 Designed at 400 fpm
13
Exhaust Air Re-circulated Air Recommended MERV 14 Pre-filter HEPA 99.97% per Institute of Environmental Sciences and Technology
14
Filter Framing Systems
15
Molecular Filtration l Traces of Oxide Compounds l Make-up Dilutes Gases l Molecular Filtration Advisable on Re-circulated Air l Make-up Air of 30% Recommended to Prevent Buildup of Nitrogen & Carbon
16
System Startup and Maintenance l NAFA Recommended Practice n DOP Test HEPA Filter l Filter Service n Filter Evaluation (gauges) –Multiple gauges or Single n Precautions & Employee Protection –Wear Protective Equipment –Never sweep as a cleaning method n Filter Disposal –Wrapped in two layer 6 mil poly & seal w/ duct tape –Disposed of in accordance w/ local, state & federal regulations
17
Conclusions l The discharge of firearms in the confined space of a firing range releases significant particulate and molecular contaminants into the air l These contaminants can be very harmful to shooters and range employees l Well designed HVAC systems can greatly improve the safety of these spaces l System maintenance by qualified specialists is a key consideration to ensure a healthy environment in firing ranges
18
National Air Filtration Association l Over 210 air filtration manufacturers and distributors l United States and 10 foreign countries l NAFA Guide to Air Filtration l NAFA Installation, Operation, and Maintenance of Air Filtration Systems Manual l Website – www.nafahq.orgwww.nafahq.org