© 2012 Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code and the.

Similar presentations


Presentation on theme: "© 2012 Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code and the."— Presentation transcript:

1

2 © 2012 Ted “Smitty” Smith

3  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code and the Denver Building Amendments.  If you put the slide show into slide show mode, the slides will transition automatically and allow you 3 minutes for each question. The answers will stay up for only 15 seconds. When you reach the end of the practice test there will be a slide that reads STOP.  You can then click on the slide and the questions will be repeated without the timer so that you can write down questions and answers and take notes.  During the timed section, do not worry about writing down the correct answer. Proceed through the timed section then review the questions and answer again without the timer.

4  What is the minimum required records retention duration for the fire protection inspection, test and maintenance records?  1 year  2 years  3 years  The IFC does not specify.

5  3 years 901.6.2

6  Which of the following organizations are not required to be notified in the event of a planned or emergency impairment of the fire protection system?  Notifications are not required  Fire Department  Police Department  Fire Code Official

7  Police Department 901.7

8  Given a 3500 square foot fire area nightclub with fixed seating. The club is located in a one story building. The occupant load for the building is 117. Does the building require an automatic sprinkler system?  Yes  No  No because its area is less than 5000 square feet  No, because the level of exit is at the grade level of the building

9  Yes 903.2.1.2

10  Given a 21,000 square feet fire area plastics manufacturing plant classified as a Group F-1 occupancy. The one story building will not contain high-piled combustible storage. Does the building require an automatic sprinkler system?  Yes  No  Yes, because it contains plastics  No, because the level of exit is on the first floor of the building

11  Yes 903.2.9

12  What type of signal is transmitted to indicate a fault in a monitored circuit or component in a fire alarm system according to the IFC?  Supervisory signal  Zone detection  Fault Signal  Trouble Signal

13  Trouble signal 902 and 202

14  All work on the Radio Enhancement System shall be accomplished by certified installers of companies possessing a valid Denver Fire Department License and after obtaining the appropriate permit.  True or False

15  True DBA 510.1.1.3(2)(f)

16  All portions of active or passive smoke control systems shall be capable of continued operation after detection of the fire event for a period of not less than either 15 minutes or 2 times the calculated egress time, whichever is less.  True or False

17  False DBA 909.4.6

18  All fire alarm systems shall be divided into zones. When four or more alarm zones are provided, visible annunciation shall be provided at an approved location.  True or False

19  False DBA 907.7.3

20  A permanent handset for the Fire Department Communication System shall be located in rooms containing the primary means to disconnect electrical service.  True or False

21  True DBA 907.2.13.2.2.1.1 Item 5

22  A fine will be imposed for any false or nuisance fire alarms exceeding (4) four within one year.  True or False

23  False DBA 907.1.5

24  Systems undergoing maintenance or modification shall not have any portion of the system out of service for more than (2) hours.  True or False

25  False DBA 907.1.6

26  A fire alarm project using phased replacement of an existing fire alarm system where practical difficulties are associated with replacement of fire alarm and detections systems shall not exceed 24 months from the date the fire alarm permit is issued, nor shall the total duration, including project planning, design and installation, exceed 30 months.

27  False DBA 907.16.6 Exception Item 4

28  A fire alarm systems required in the City and County of Denver shall be monitored by an approved Class II supervising station in compliance with section 916 and in accordance with Denver Municipal Code.  True or False

29  False DBA 907.1.3

30  Sufficient emergency power shall be provided to simultaneously operate two elevators for each group of elevators controlled by a common operating system.  True or False

31  True DBA 604.2.18.3

32  An approved automatic smoke detection system shall be installed in areas containing stationary storage battery systems having a liquid capacity of more than 50 gallons.  True or False

33  True DBA 907.2.23

34  In the tenant space of a covered mall the smoke detector zone may not exceed 1000 square feet.  True or False

35  False DBA 907.2.20.1.1 Item 3

36  The Fire Command Center shall be located on the ground floor and shall have an entrance that is located within 400 feet of the main building entrance.  True or False

37  False DBA 508.1.1

38  The emergency responder radio communication enhancement system shall be tested by have a minimum of (10) sampling measurements per 2,250 square meters of gross building footage.  True or False

39  True DBA 510.1.1.3 Item

40  Multiple points of silence and reset are prohibited on a single system in the City and County of Denver.  True or False

41  True DBA 907.1.4

42  Activation of the fire alarm in a Group A occupancy with an occupant load of 1000 or more per space or an occupant load of 300 or more per space with an aggregate Group A load of 1000 or more, shall initiate a signal using an emergency voice/alarm communications system.  True or False

43  True DBA 907.2.1.1

44 STOP

45  What is the minimum required records retention duration for the fire protection inspection, test and maintenance records?  1 year  2 years  3 years  The IFC does not specify.

46  3 years 901.6.2

47  Which of the following organizations are not required to be notified in the event of a planned or emergency impairment of the fire protection system?  Notifications are not required  Fire Department  Police Department  Fire Code Official

48  Police Department 901.7

49  Given a 3500 square foot fire area nightclub with fixed seating. The club is located in a one story building. The occupant load for the building is 117. Does the building require an automatic sprinkler system?  Yes  No  No because its area is less than 5000 square feet  No, because the level of exit is at the grade level of the building

50  Yes 903.2.1.2

51  Given a 21,000 square feet fire area plastics manufacturing plant classified as a Group F-1 occupancy. The one story building will not contain high-piled combustible storage. Does the building require an automatic sprinkler system?  Yes  No  Yes, because it contains plastics  No, because the level of exit is on the first floor of the building

52  Yes 903.2.9

53  What type of signal is transmitted to indicate a fault in a monitored circuit or component in a fire alarm system according to the IFC?  Supervisory signal  Zone detection  Fault Signal  Trouble Signal

54  Trouble signal 902 and 202

55  All work on the Radio Enhancement System shall be accomplished by certified installers of companies possessing a valid Denver Fire Department License and after obtaining the appropriate permit.  True or False

56  True DBA 510.1.1.3(2)(f)

57  All portions of active or passive smoke control systems shall be capable of continued operation after detection of the fire event for a period of not less than either 15 minutes or 2 times the calculated egress time, whichever is less.  True or False

58  False DBA 909.4.6

59  All fire alarm systems shall be divided into zones. When four or more alarm zones are provided, visible annunciation shall be provided at an approved location.  True or False

60  False DBA 907.7.3

61  A permanent handset for the Fire Department Communication System shall be located in rooms containing the primary means to disconnect electrical service.  True or False

62  True DBA 907.2.13.2.2.1.1 Item 5

63  A fine will be imposed for any false or nuisance fire alarms exceeding (4) four within one year.  True or False

64  False DBA 907.1.5

65  Systems undergoing maintenance or modification shall not have any portion of the system out of service for more than (2) hours.  True or False

66  False DBA 907.1.6

67  A fire alarm project using phased replacement of an existing fire alarm system where practical difficulties are associated with replacement of fire alarm and detections systems shall not exceed 24 months from the date the fire alarm permit is issued, nor shall the total duration, including project planning, design and installation, exceed 30 months.

68  False DBA 907.16.6 Exception Item 4

69  A fire alarm systems required in the City and County of Denver shall be monitored by an approved Class II supervising station in compliance with section 916 and in accordance with Denver Municipal Code.  True or False

70  False DBA 907.1.3

71  Sufficient emergency power shall be provided to simultaneously operate two elevators for each group of elevators controlled by a common operating system.  True or False

72  True DBA 604.2.18.3

73  An approved automatic smoke detection system shall be installed in areas containing stationary storage battery systems having a liquid capacity of more than 50 gallons.  True or False

74  True DBA 907.2.23

75  In the tenant space of a covered mall the smoke detector zone may not exceed 1000 square feet.  True or False

76  False DBA 907.2.20.1.1 Item 3

77  The Fire Command Center shall be located on the ground floor and shall have an entrance that is located within 400 feet of the main building entrance.  True or False

78  False DBA 508.1.1

79  The emergency responder radio communication enhancement system shall be tested by have a minimum of (10) sampling measurements per 2,250 square meters of gross building footage.  True or False

80  True DBA 510.1.1.3 Item

81  Multiple points of silence and reset are prohibited on a single system in the City and County of Denver.  True or False

82  True DBA 907.1.4

83  Activation of the fire alarm in a Group A occupancy with an occupant load of 1000 or more per space or an occupant load of 300 or more per space with an aggregate Group A load of 1000 or more, shall initiate a signal using an emergency voice/alarm communications system.  True or False

84  True DBA 907.2.1.1