Calculation of PFP Thickness
Thursday, 20 April 2017
2
The thickness of fire protection required is determined by:
Duration Critical Steel Temperature Steel section size and type Hp/A ratio Thickness stated in the local or international approval
3
SI Units: Imperial (US) Units: Hp/A = M/D = = = A/V = = = W/D = = =
A/P = Heated Perimeter metres = = m-1 or /m Cross Section Area metres² Mass of Section Kilograms / metre = = kg/m² Heated Perimeter metres Heated Surface Area metres² = = m-1 or /m Volume of Steel metres³ Weight of section Pounds/foot = = lb/ft/in Heated Perimeter inches Cross Section Area = Square inches = in2/in Heated Perimeter inches All express the relationship between the amount of steel capable of absorbing heat to the area of steel surface exposed to the fire.
4
Cross Sectional Area (A = m²)
How much PFP do I need? Hp/A - Section Factors Heated Perimeter (Hp = m) Cross Sectional Area (A = m²) Low Hp/A = Thinner PFP 305 x 305 x 240 kg/m Hp/A = 1.905m / m² Hp/A = 62 m-1 For H120 (400°C): Chartek 7 = 11 mm High Hp/A = Thicker PFP 305 x 305 x 97 kg/m Hp/A = 1.789m / m² Hp/A = 145 m-1 For H120 (400°C): Chartek 7 = 16 mm
5
How much PFP do I need? How Hp/A changes with sides exposed to fire.
(Example 305 x 305 x240 Kg/m UC) Wall, Floor or Deck Wall, Floor or Deck 4 Sides exposed Hp/A= Hp/A = 62 m-1 3 Sides exposed Hp/A= Hp/A = 52 m-1 Flange only exposed Hp/A= Hp/A = 13 m-1 1.905 m 1.587 m 0.393 m m² m² m² Note: Cross Sectional Area Remains the same in all cases!
6
How to calculate an Hp/A?
The Yellow Book!
7
How to calculate an Hp/A?
8
What do I do with my Hp/A? Chartek 7 Certificate
Interchar 963 loadings Example of Certificate of Fire Approval with table of Hp/A v required PFP thickness
9
What do I do with my Hp/A? Interchar 963 loadings
10
What about other section shapes?
Wall, Floor or Deck Wall, Floor or Deck Decreasing Hp/A = Lower PFP thickness required