Desiccant Cooling A good deal for everyone Henrik Näsström
2
In general 2015-08-292 Creates air cooling from district heating An alternative to traditional methods Can make incoming air colder from 30°C to 15°C. Using district heating instead of electricity No noisy compressor or condenser, no environmentally harmful refrigerants Built using proven standard components Requires large ventilation space
3
Economy 2015-08-293 More expensive than conventional units (30-50%) Very good heat recovery Increased basis for environmentally friendly electricity due to CHP Equal investment costs (in this case) Lower operating costs (in this case)
4
Components
5
Evaporative air coolerDrying rotor
6
Evaporative cooler If you add 1 gram of water to 1 kg of air you reduce the air temperature 2,5°C Drying rotor If you take away 1 gram of water from 1 kg of air you increase the air temperature 3,3°C Physics
7
30 ºC 10 g/kg 40 ºC 7 g/kg 25 ºC 7 g/kg 25 ºC 10 g/kg 20 ºC 12 g/kg 17,5 ºC 10 g/kg 55 ºC 12 g/kg 35ºC 12 g/kg 45ºC 15 g/kg Function
8
ROOM 45,055,035,020,025,0 15,512,5 10,5 Delta T =7,5 Delta X =0,5 30,040,025,017,5 10,07,0 10,0
9
Heating demand of 540 MWh in a building 80% efficiency for a conventional ventilation gives a need of 108 MWh 90% efficiency with desiccant cooling system provides a heating requirement of 54 MWh In summer it need about 30 - 45 MWh of heat to create desiccant cooling 0,7 – 1,0 kWh of heat to generate 1 kWh of cooling Example
10
Consumption