1 EWWD-MBYNN EWLD-MBYNN
Water-cooled EWLD-MBYNN Condenserless Applied Systems Sales

2 EWWD-MBYNN EWLD-MBYNN
Water-cooled EWLD-MBYNN Condenserless Contents A. Equipment Overview B Capacity Range C Operation Range D. Specifications E. Construction F. Options & Kits Applied Systems Sales

3 Double Circuit (2 Compressors)
A. Equipment Overview Condenserless Unit EWWD MBYNN EWLD MBYNN EWWD MBYNN EWLD MBYNN Single Circuit Double Circuit (2 Compressors) Large Chillers: R-134a Daikin stepless single screw compressor All components optimized for use with R-134a Water heat exchangers: Brazed Plate Evaporator and Shell & Tube Condensor Double refrigeration circuit (from 340kW) Applied Systems Sales

4 B. Capacity Range – EWWD~MBYNN
Model CC kW HP Single circuit (1 compressor) Double circuit (2 compressors) Applied Systems Sales

5 B. Capacity Range – EWLD~MBYNN
Model CC kW HP Single circuit (1 compressor) Double circuit (2 compressors) Applied Systems Sales

6 C. Operation Range – EWWD~MBYNN
For EWWD 240/280/500/520/540 °C LWC 60 For EWWD 120/180/360/440 50 Water-Cooled Range 44 40 Start-up area 30 25 20 Glycol Water LWE 15 -4 4 7 16 °C -10 10 20 Applied Systems Sales

7 C. Operation Range – EWLD~MBYNN
°C TC For EWLD 240/260/480/500/540 62 60 For EWLD 120/170/340/440 55 50 49 Condenserless Range 40 Start-up area 30 25 20 Glycol Water LWE 15 -2 4 7 16 °C -10 10 20 Applied Systems Sales

8 Single Screw Compressor
D. Specifications Daikin Stepless Single Screw Compressor Brazed Plate Evaporator pCO2 Control Platform Shell & Tube Condenser Applied Systems Sales

9 D. Specifications -> Refrigerant
EWWD~MBY Pure Refrigerant -> No Glide ODP = 0 Chlorine free Low toxicity Not flammable Good and efficient refrigerating capacity Moderate operating pressures Applied Systems Sales

10 D. Specifications -> Stepless Compressor
Reliable New compressor: New features: Stepless G-type compressor - Newly designed gate rotors - High efficient electric motor - COP increase of 5 to 10% - Newly designed slide vanes Applied Systems Sales

11 D. Specifications -> Stepless Compressor
High Efficiency Engineered plastic gate rotors Ensuring closer tolerences Compact Design Durable & Reliable Fewer moving parts Balanced forces = Low bearing loads Plastic on metal = Low wear No need for oil pump 1st Service Interval after hours Low Vibration & Noise Plastic on metal = lower noise Runs at 2900rpm = compressions/min Smoothed discharge flow = low vibrations Applied Systems Sales

12 D. Specifications -> Stepless Compressor
Launch of STEPLESS capacity control (Sales launch: August 2005) Better partial load control WHAT YOU WANT IS WHAT YOU GET More precise control of the temperature OUTLET CONTROL (± 0.5oC) Smaller minimum water volume required  Upto 40% less than stepped chillers  Less need for buffer tanks G-type stepless Higher Efficiency Saves the environments resources … and nevertheless your own resources Designed, tested and manufactured in Daikin’s own laboratories. Applied Systems Sales

13 D. Specifications -> Stepless Compressor
Higher Efficiency STEPLESS capacity regulation The compressor has built-in capacity control by 30 – 100% by stepless slide valve mechanism, and adjustable volumetric ratio 100% 30% 12% Chiller Load Demand Starting position Single Circuit 100% 15% 12% Chiller Load Demand Starting position Double Circuit Designed, tested and manufactured in Daikin’s own laboratories. Applied Systems Sales

14 D. Specifications -> Evaporator
Brazed plate heat exchangers for evaporator Filter & Flow switch High W/m² value for increased efficiency Optimal refrigerant distribution Decreased refrigerant charge Super- heated Vapor & Liquid Water Refrigerant Applied Systems Sales

15 D. Specifications -> Evaporator Hydronics
To secure the safety of YOUR installation + EASY INSTALLATION Filter Flow Switch Semi Mounted Perforation diameter = 1mm Evaporator Filter (free supplied) Victaulic Joints (free supplied) Flow switch (factory semi-mounted) Applied Systems Sales

16 D. Specifications -> Evaporator Hydronics
Victaulic joints: - Absorb vibration - Reduce operating sound - Reduce thermal deflection - Simplify chiller installation 8° angle guarantees stress free Leak tight water piping connection Applied Systems Sales

17 D. Specifications -> Condensor
Shell and Tube condenser __Refrigerant in Shell Special double sided enhanced tube: 40% size reduction Reduction in refrigerant charge Ideal for stable refrigerant R-134a High W/m² value for increased efficiency Optimal refrigerant distribution Condenser Applied Systems Sales

18 D. Specifications -> pCO2 Controller
The nerve centre of the Chiller System Benefits for the user ... - provides detailed information - accurate control of all functional parameters - easy menu screen scrolling. Applied Systems Sales

19 D. Specifications -> pCO2 Controller
Features Automatic restart after power failure Control of operating and safety parameters Schedule timer (4 timer groups) Advanced freeze-up control Floating set point according to ambient temperature Extended alarm history (20 alarms) 5 languages Time and date information Daily pump on Temperature probe fine tuning Lead-lag of compressors Applied Systems Sales

20 D. Specifications -> Temperature Control
Inlet / Outlet Control Floating Setpoint Alters setpoint in function of ambient or ∆T Increase setpoint = increase evaporating temp Sampling of temperatures every 12seconds Fast (7%) Load-up, Slow Load-up (3%) or No Action depending on deviation Fast (7%) Load-down, Slow Load-down (3%) or No Action depending on deviation Applied Systems Sales

21 D. Specifications -> Freeze-up Control
LWE (°C) Freeze-up Prevention Unload compressor if LWE drops 1oC below MOW 4 3 2) Freeze-up Protection Stop compressor if LWE drops 1,5oC below MOW 2,5 Freeze-Up Safety Setting 1 2 t(min) STOP *For Glycol: ZH -6,5°C / ZL -11,5°C Applied Systems Sales

22 D. Specifications -> Expansion Device
EEV Greater control over a wider operating range Superheat kept to a minimum – optimizing evaporator Can cope with lower head pressures than TEV’s Pro’s Energy savings at part load condition Energy savings at reduced optimum head pressures TEV on the 110, 180, 360 and 440 kW systems Operation based on external Pressure compensation Applied Systems Sales

23 D. Specifications -> DICN
WHAT? Combine up to 4 DAIKIN chillers as if they were 1 unit … FEATURES : - Entering or Leaving water control - Running hours balancing between units - Flexible and efficient pump control - Features of the individual unit remain ADVANTAGES: Comfort cooling : Process / Industrial cooling : - Extend the DAIKIN chiller range - Create a chiller system of up to 2 MegaWatt ... - Even more precise & efficient capacity control - Standby : provide backup in case of alarm - Cooling available under any conditions Bigger System Capacity Increase System Reliability Applied Systems Sales

24 D. Specifications -> DICN
DICN - System Example 1 Slave 3 “Constant water volume system” Leaving water control with sensor. Slave 2 Pump runs if at least 1 unit = ON. Slave 1 Fixed Speed Pump Master LOAD EKCLWS Applied Systems Sales

25 D. Specifications -> DICN
Fixed Speed Pumps Slave 3 DICN - System Example 2 “Variable flow water system” SL3 Slave 2 Entering water control. SL2 Pump SL1-3 runs if unit = ON Pump Master runs always. Slave 1 SL1 Inverter pump Master M1 Applied Systems Sales

26 D. Specifications -> Safety Devices
Double high pressure switch Low pressure switch Freeze-up prevention & protection Discharge thermal protector Pressure relief valve on compressor Compressor motor over current protector Compressor motor thermal protector Reverse phase protector Recycling and guard timer Digital display controller with electronic temperature control Emergency Stop HP LP Applied Systems Sales

27 E. Construction -> Robust Chassis
High Quality Platework! Galvanized steel plate Zinc-Phosphate coating Epoxy powder painted COLOR  Ivory white = Munsell code 5Y7.5/1 Applied Systems Sales

28 E. Construction -> EWWD120~280
1 014mm 898mm 2 672mm Applied Systems Sales

29 E. Construction -> EWWD360~540
Single or double circuit have the same footprint DAIKIN : proposes COMPACT LINE units. EASY split up in separate modules, without influence on refrigerant circuit ! EWWD MBYN EWLD MBYN split up in 2 modules. unscrew 6 bolts disconnect 9 wires Applied Systems Sales

30 E. Construction -> Compact Design
Enter through the roof. Transport through the basement. Applied Systems Sales

31 E. Construction -> Serviceability
600 500 600 900 Applied Systems Sales

32 F. Options & Kits -> Factory Fitted
Low Noise Operation OPLN Dual Pressure Relief Valve OP03 Suction Stop Valve OP12 Mains Isolator Switch OP52 Ammeter Voltmeter OP57 Applied Systems Sales

33 F. Options & Kits -> Low Noise (OPLN)
operation The casing is completely closed with sheet metal insulated from the inside with sound absorbing insulation. Sound power level reduction of - 6 dB(A) Applied Systems Sales

34 Non Return Valve on HP-Side
F. Options & Kits -> For Service OP03 Dual Pressure Relief OP12 Suction Stop Valve Non Return Valve on HP-Side is Standard Stop Valve on LP-Side is an option 1 Pressure Side HP-Side Suction Side LP-Side 2 Re-calibration possible without refrigerant evacuation Daikin Single Screw Compressor Applied Systems Sales

35 1 2 V A 1&2 F. Options & Kits -> For Service
OP57 Ammeter / Voltmeter Unit 2 1 Terminal FOR 1&2 A V Compressor 1 Compressor 2 L1, L2, L3 OP52 Mains Isolator Switch Applied Systems Sales

36 F. Options & Kits -> Field Installed
Remote Controller EKRUPC BMS Modbus EKBMSMBA Bacnet EKBMSBNA DICN LWE Sensor EKCLWS Applied Systems Sales

37 F. Options & Kits -> Remote & BMS
Remote Controller & BMS UNIT Remote Controller PCO² - Controller PCO-controller EKRUPC BMS (Building Management System) EKAC200A Gateway RS232/485/422 EKBMSMBA EKBMSBNA Applied Systems Sales

38 F. Options & Kits -> BMS
Interface needed Question Answer Read out :  Temperatures  Pressures  Status  Alarms... Write :  Setpoints  Remote on/off  Operation mode ... Modbus: Max. 16 addresses BACnet: Max. 8 addresses Data exchange and communication between the chiller and the BMS is realized by CLICK the principle of “QUESTION” and “ANSWER”. The BMS sends out a question signal concerning a certain parameter, and the chiller replies with the proper answer. CLICK Among the exchanged information, we can find 2 kinds of parameters. READ ONLY parameters, such as temperatures, pressures, status, alarms. Then we also have the WRITABLE or CHANGEABLE parameters. These are for instance altering of the setpoints, changing of the operation mode for small chillers, start/stop circuits, … All together, with a 2 circuit large chiller, you can access up to more than 130 parameters. Access up to 130 parameters Applied Systems Sales

39 Unique Concept & Design, excellent installation possibilities!
Large Water-Cooled Chillers EWWD MBYNN EWLD MBYNN Unique Concept & Design, excellent installation possibilities! Applied Systems Sales