Download presentation
1
Cooling: Best Practices and Economizers
4/21/2017 Cooling: Best Practices and Economizers Randall Poet A C Systems
2
Ideal Situation Server Load = CRAC Capacity
Server Airflow = CRAC Airflow
3
Agenda The Conventional Approach – Base Case
Raise the Return / Supply Air Temp Contain the Cold Aisle Add Intelligent Control The Set-up Summary
4
Start with Best Practices
Hot aisle / Cold aisle Blanking panels in racks Blanking panels between racks Blanking Panels between racks and floor Cable cut-outs covered Relatively clean underfloor area Proper location of CRAC units Vapor barrier around space
5
Base Case – 75F Return Air Control
20 Racks 8 kW each 35F delta T 4 CRACs (N+1) 54 kW each 21F delta T design
6
Base Case – 75F Return Air Control
20 Racks 8 kW each 35F delta T 3 CRACs Running 54 kW each 21F delta T design
7
Base Case Operating Scenario
75F 89F 54F CFM 100% Unit Airflow – 24,000 CFM Rack Airflow – 14,600 CFM Bypass Airflow – 9,400 CFM
8
The Airflow Pattern
9
Typical Air Cooled DX Energy Consumption
Condenser Fan Motors Evap Fan Motor Compressors
10
Typical Energy Consumption
System kW 75F RA Compressors 35.4 Evap Fans 8.7 Condenser Fans 5.4 Total 49.5 Condenser Fan Motors Evap Fan Motor Compressors Compressors run at full capacity Fans run at full speed
11
Agenda The Conventional Approach – Base Case
Raise the Return / Supply Air Temp Contain the Cold Aisle Add Intelligent Control The Set-up Summary
12
New Operating Scenario
85F 99F 64F CFM 100% Unit Airflow – 24,000 CFM Rack Airflow – 14,600 CFM Bypass Airflow – 9,400 CFM
13
Increased Capacity at Full Airflow
4/21/2017 Increased Capacity at Full Airflow
14
Increased Capacity at Full Airflow
4/21/2017 Increased Capacity at Full Airflow
15
Operating Systems Comparison
System kW 75F RA 85F RA Compressors 35.4 24.9 Evap Fans 8.7 Condenser Fans 5.4 Total 49.5 39.0 Base 78.8% Compressors run at reduced capacity or unloaded Fan motors run at full speed
16
Sanity Check – 100 dF OAT, 6400’ ASL
4/21/2017 Sanity Check – 100 dF OAT, 6400’ ASL
17
Sanity Check
18
Agenda The Conventional Approach – Base Case
Raise the Return / Supply Air Temp Contain the Cold Aisle Add Intelligent Control The Set-up Summary
19
Contain the Cold Aisle Unit Airflow – 21,600 CFM
Rack Airflow – 15,800 CFM Bypass Airflow – 5,800 CFM
20
Operating Systems Comparison
System kW 75F RA 85F RA Contained Compressors 35.4 24.9 25.8 Evap Fans 8.7 7.5 Condenser Fans 5.4 Total 49.5 39.0 38.7 Base 78.8% 78.2% At the higher RA temperature, the contained system has very similar operating costs as the non- contained Fan motors run at full speed but at a reduced CFM and HP due to the higher static pressure Compressors run at reduced capacity or unloaded but slightly higher than the non-contained
21
Why use Containment?? System operating costs are similar
Containment partitions and doors cost $$
22
Hot Spots in Racks due to Wrap-Around
23
No Leakage into the Cold AIsle
24
Higher Temperatures without Containment
25
Containment of Cold Aisle
26
Issues to Consider Fire Detection / Suppression Installation
4/21/2017 Issues to Consider Fire Detection / Suppression Wide variation between municipalities If local Fire Inspector involved early, typically goes well Curtains usually eliminate this issue Installation Will be site specificy Irregular row length/height, gaps, etc. Site conditions critical, one size does NOT fit all
27
4/21/2017 Issues To Consider ADA CAC space is for Service Personnel (Section 4.1.1) What about cooling for components in rest of room? Best solution today may be ducted return from hot aisle Perf tiles near other equipment requiring cooling (eg. UPS) 85⁰ Room temperature?
28
HAC vs CAC Main Purpose of Cooling in Data Center?
4/21/2017 HAC vs CAC Main Purpose of Cooling in Data Center? Cool the equipment Data Centers commonly on raised floor CAC allows current investment to be used HAC typically requires in row cooling So, refrigerant or chilled water and condensate intermingled with IT equipment and racks Which aisle does majority of work take place in? CAC hot aisle likely in 85⁰F range Can use perf tiles in other space HAC hot aisle likely in 100⁰F range
29
Agenda The Conventional Approach – Base Case
Raise the Return / Supply Air Temp Contain the Cold Aisle Add Intelligent Control The Set-up Summary
30
Closer to Matching the Load to the Cooling
92F 97F 62F CFM 70% Variable Capacity Compressors Variable Speed Fans Intelligent Control Unit Airflow – 16,800 CFM Rack Airflow – 14,600 CFM Bypass Airflow – 2,200 CFM
31
Operating Systems Comparison
System kW 75F RA 85F RA Contained 92F RA Contained & Controlled Compressors 35.4 24.9 25.8 25.5 Evap Fans 8.7 7.5 3.0 Condenser Fans 5.4 Total 49.5 39.0 38.7 33.9 Base 78.8% 78.2% 68.5% The airflows and capacities/loads are more closely matched Fan motors run at reduced speed, CFM and HP based on the demand in the contained area Compressors run at reduced capacity or unloaded but slightly higher than the non-contained
32
Agenda The Conventional Approach – Base Case
Raise the Return / Supply Air Temp Contain the Cold Aisle Add Intelligent Control (Creating SmartAisle) The Set-up Summary slide
33
Sensor Location Server centric solution, meaning that it focuses on the inlet temperature to the servers Self adapting to environment changes due to server utilization, equipment location changes and outside variables Can adapt to situations with no containment, end containment, and full containment
34
Rack Sensors Rack Sensors without doors can be mounted on the frame of the racks. Temperature differences were within .5°F
35
Cold Aisle Sensors Sensors can also be mounted at the top of cold aisles when rack mounting is unavailable
36
Supply Compensation Lower Supply
Compensation is the magical link between controlling sensors The controller evaluates the Rack Sensors and Fan Speed If the fan is operating at 100% and remains above the cold aisle set point Then the supply temperature set point will slowly lower to drive the correct cold aisle temperature Fan Speed 100% Lower Supply
37
Controller and CRAC Operation
Unit ON CW Valve Open % Fan Speed % 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% Increase in kW Supply Temperature The increase in fan speed will result in a warmer supply air temperature which is detected by the supply air sensor that will increase cooling to maintain supply air setpoint Cold Aisle Containment iCOM will automatically adjust to changes that result in a temperature increase or decrease Fan Speed Increases So that cold aisle temperature is maintained at customer temperature Setpoint IT Load Increases Rack Temperature Sensor detects inlet rack temperature
38
Controller and CRAC Operation
Advanced freeze protection routine Allow all units to reduce fan speed to 60% Fan speed and compressor capacity (or CW valve) managed for best unit efficiency and performance Multiple remote sensors Controller can use averaged and maximum/minimum values to individually control multiple CRAC systems CRAC systems work as a team All remote sensors used Increase capacity of other applicable adjacent units if one is at maximum and unable to handle the load Automatically adjust for units not in service
39
Agenda The Conventional Approach – Base Case
Raise the Return / Supply Air Temp Contain the Cold Aisle Add Intelligent Control The Set-up Summary
40
Issues to Consider Fire Detection / Suppression Installation
Wide variation between municipalities If local Fire Inspector involved early, typically goes well Curtain eliminates this issue Installation Will be a local responsibility You need to develop relationship with local Cable Contractor or similar company for installation Irregular row length/height Site Survey critical Most expensive component
41
Issues To Consider ADA Consultant raised issue at BAIS project Successfully defended CAC space is for Service Personnel (Section 4.1.1) What about cooling for components in rest of room? Best solution today is ducted return from hot aisle perf tile by IT component 85⁰ Room temperature
42
Issues To Consider Purpose of Cooling in Data Center?
Control equipment inlet temps Data Centers often on raised floor CAC allows current investment to be used Which aisle does majority of work take place in? CAC hot aisle likely in 85⁰F range Could use perf tile in other space HAC hot aisle likely in 100⁰F range
43
Summary Best practices are a must if improved efficiency is a goal
Running warmer temperatures in the space will improve the cooling system operating efficiency Containment improves the availability of the servers by eliminating hot spots Intelligently controlling fan speed and compressor capacity “balances” the system to operate at it’s most efficient level
44
Summary Efficiency is the story, not containment
4/21/2017 Summary Efficiency is the story, not containment Containment can be done in several ways, none necessarily fit all situations Each critical space is unique and merits individual planning Dynamic Control is (currently )the final element
45
…Shifting on to Economizers and Equipment Considerations…
46
90.1 Economizer Map
47
Definitions of Cooling Efficiency
EER (Energy Efficiency Ratio) Total Cooling Capacity (BTUH)/Total power input (watts) Full-load value on 95F design day Commercial return air conditions of 80F/50% SCOP (Sensible Coefficient of Performance) Sensible Cooling Capacity (kW)/Total power input (kW) Data Center return air conditions of 75F/45% These are two common terms to describe the energy efficiency of cooling units: EER (energy efficiency ratio) is expressed at Total cooling BTUhs divided by the total power input (in watts). It is also based on one specific operating point, that the cooling unit is likely never to operate because of cooling redundancy that is usually designed into the data center. It is also based on 80F air temperature back to the cooling unit. SCOP (sensible coefficient of performance) is a net cooling capacity, with fan motor heat removed, and is expressed as kW cooling divided by kW power input. Again, it is based on a full-load condition on a 95F day. Data center conditions of 75F are used. ASHRAE 90.1, reference in most state energy codes, now includes minimum requirements for data center coolin.
48
ASCOP – Efficiency Metric
Annualized Sensible Coefficient of Performance (location specific) Bin efficiency x bin hours/total annual hours Factors hours at each efficiency operating point Factors part-load efficiency Factors economizer hours
49
Single System – Outside Air Economizer
50
Large or Multiple Systems – Outside Air Economizer
51
Single System with Glycol Economizer
52
Precooler on Chilled Water System
53
Chilled Water with Cooling Tower Economizer
54
What if we could do a refrigerant based economizer cycle?
55
Energy Consuming Components Air-Cooled System
Compressor energy reduction is low-hanging fruit
56
Digital Scroll Technology
Continuous variable capacity compressor technology without inverter drive from 10% to 100% of capacity In commercial use since 2004 Available in single compressor and tandem compressor configurations High reliability versus Inverter drive systems No electrical harmonics introduced
57
EC fans in unit
58
EC fans in raised floor
59
EconoPhase Pumped Refrigerant Economizer
Outdoor Ambient 95°F 70% Load 24.1 Summer operation EconoPhase Condenser Check Valve Refrigerant Pumps OFF Solenoid Valve Check Valve Evaporator Check Valve Circuit 2 Electronic expansion valve Circuit 1 Compressors ON
60
EconoPhase – Partial Economization
Outdoor Ambient 65°F 70% Load 15.1 Fall / Evening operation EconoPhase Condenser Check Valve ON Refrigerant Pump Solenoid Valve OFF Check Valve As ambient temperatures get cooler in the evenings or with the change of seasons, the Econophase will act as a “pre-cooler” to reduce compressor operation. In this case one circuit runs on compressor operation and the second circuit runs on the refrigerant pump. This is where the staged A coil comes into play. It pre-cools the refrigerant to reduce the compressor workload. Note in this case my system energy draw has decreased by 37% to 15 kW. ON Evaporator Check Valve Circuit 2 Electronic expansion valve OFF Circuit 1 Compressor
61
EconoPhase - Full Economization
Outdoor Ambient 25°F 70% Load 3.7 Winter operation EconoPhase Condenser Check Valve ON ON Solenoid Valve Refrigerant Pump Check Valve In full economization mode – when temperatures are below 35 degrees – both compressors are off and both refrigerant pumps circulate the refrigerant through their respective circuits. Energy consumption is now only 3.7 kW for the entire system! And I get full capacity from the system. This is an 85% reduction in the total system energy draw – and that’s because the refrigerant pump draws about 1/20 the energy of a compressor! OFF Evaporator Check Valve Circuit 2 Electronic expansion valve Circuit 1 OFF Compressor
62
Refrigerant Economizer
Technology Electronic Expansion Valve EC Plug Fans Tandem compressors w/ Digital Scroll New Evaporator Coil design Staged “A” Coil Greater surface area Microchannel Condenser Indoor Unit Communicates to Condenser Refrigerant Economizer The DSE is loaded with new technology and Liebert firsts. Its features include electronic expansion valves, ec plug fans, and features new to the precision cooling market: tandem compressors in each circuit with digital scroll compressors, a larger, staged “A” coil optimized to the compressor, and a microchannel condenser that even communicates with the indoor unit for optimized performance.
63
Advantages of Refrigerant Economizer
No additional heat exchangers No dust or contamination concerns No need for added ductwork or structural changes to building for economizer No dampers to maintain Quick changeover between compressor mode and economizer mode No water usage No water freeze or coil freeze concerns
64
Liebert DSE Full-Load Efficiency SCOP (kW/kW) @ 85F return air
Liebert DSE 50% load +115% +92% Liebert DSE 100% load Efficiency Plateau Traditional Refrigeration +45% ASHRAE 75F
65
With Refrigerant Economizer Maximum capacity, max airflow
4/21/2017 With Refrigerant Economizer Maximum capacity, max airflow Ambient, ºF
66
No water use for cooling MERV 13 filters No outside air contamination
Designing for LEED Energy efficiency No water use for cooling MERV 13 filters No outside air contamination R-410A refrigerant/lower charge Utility Rebates
67
Condenser Improvements
68
Air Cooled Condenser Improvements
Microchannel vs. Fin and Tube Variable Speed Fans Control Based on Refrigerant Pressure
69
Microchannel Coil Aluminum Fins & Tubes
Developed & used in Automotive A/C for 25+yrs
70
Microchannel Coil Advantage
1” Thin coil replaces 2” to 6” fin/tube coil Lower airside ∆P Reduced maximum fan wattage for heat transfer Reduced refirgerant quantity 6” 1”
71
EC Axial Fan Technology
EC (Electronically Commutated) Motor Every fan/motor is designed for variable speed. Superior part load efficiency 3-Phase AC power feed, but efficiency of a DC motor 20% reduction of fan speed = 49% savings in energy
72
Sound Quiet fan blade design
73
Sound Level Factors & Options
Sound varies with fan speed Fan speed is proportional to % compressor load and outdoor ambient temperature Will you ever hear a lightly loaded system condenser? Even more quiet options Upsizing condenser will keep fan speed in nearly “inaudible” range!
74
Why do they cool things with air, anyway??
75
Why indeed? How about pumped refrigerant?
Refrigerant piping anifold supplies pumped refrigerant Cam levers activates engagement and disengagement of server Refrigerant connection points at top of the rack on left side. All plumbing runs along left side.
76
Cooling Architecture Each server is cooled by an individual cold plate
Cold plates and insertion mechanism is designed for use of standard 1U servers Circulating refrigerant is the cooling medium Rack Server Heat exchanger & circulation unit Cold Plate To/From Chiller Cold Plate Highly flexible Backed with pressure plate Forms to the server lid
77
In-Rack Cooling with Pumped Refrigerant
The rack is 45U tall by 800mm wide by 1200mm deep. 36 1U server slots with cold plate Three non-cooled server slots for “cool” devices like switches, etc. Can be configured for a cooling capacity of 20kW or 40kW.
78
4/21/2017 Thank You. Questions?
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.