System Features Interactive Digital Addressable Fire Detection and Alarm System. Designed for Small and Medium Sized Installations.

Similar presentations


Presentation on theme: "System Features Interactive Digital Addressable Fire Detection and Alarm System. Designed for Small and Medium Sized Installations."— Presentation transcript:

1

2 6300

3 6300 System Features Interactive Digital Addressable Fire Detection and Alarm System. Designed for Small and Medium Sized Installations such as Nursing Homes Hotels and Offices Fully Conformant to EN54 Requirements Recessed Option Range of Finishes. Networkable (Up to 32 Panels) 1 , 2 and 4 Loop options. 191 Devices Per Loop

4 6300 System Features Controls and Displays.
Silence/Sound Alarms/Reset/Accept 80 Character LCD Display Twin Fire LEDs 32 Zonal Fire LEDs Full Fault Monitoring LEDs Optional Low Noise Printer

5 6300 System Features

6 6300 Front display LCD display General fire LEDS Fire ZONE display
Status LEDs Control buttons Thermal printer

7 6300 Status LEDs Fault - illuminates with a general fault.
System fault - illuminated when the processor has failed. Alarm fault - problem with the internal alarm circuits. Fire link fault - problem with the fire station link Power-supply status - illuminated in a healthy condition (GREEN) Test - illuminates when the system is in engineers test mode. Pre-alarm - illuminates when a devices is approaching a fire condition Alarms disabled -sounders are isolated Fire link active -signal to the fire brigade active (if link fitted) Disablement - illuminates when a devices has been isolated. Fire link disabled - fire station link isolated

8 System Features LCD in a quiescent condition Lower line User Message Upper line Current time & date System Normal /1/09 15:35:31 ASM - HUNGARY Liquid Crystal Display - The 80, large character liquid crystal display will under normal quiescent conditions display the current time and date with the option to also display a 40-character user’s message such as the site name or installation company. In an alarm or fault condition the LCD will display the device Loop, address and Zone number and up to 40 characters of user definable location text, programmable on site using Protec 6300/WinTEXT windows based software. LCD in a fire condition Upper line Zone, Loop and address number Lower line User definable Location text Fire 01 of 01 Zone 32 Loop 1 address 191 Building 2, Ground Flr, East Wing Rm 12

9 6300 System Features Thermal Printer 40 Character
On Demand Real Time Data for Fire and Fault Condition Prints Device Number and Location Text Prints Event Reports Prints Device Configuration Prints Programming Matrix Prints List of Devices becoming contaminated. Thermal Printer Fire in Zone /7/00 22:50: Loop 1 Address 191 Building 2, Ground Flr, East Wing Rm 12 Typical fire print-out

10 6300 Fire LEDs General fire LEDs 32 Fire ZONE LEDs

11 6300 Control buttons Accept - the fault buzzer to be muted (not all events) Previous -allows previous events or menu options to be selected. Next -allows the next event or menu options to be selected. Menu - allows access to the menu options. Sound alarms - activates all sounders on the system Silence - Allows all sounders to be silenced following either a fire or sound alarms event. Reset - allows the system to be fully reset following a fire event.

12 Maximum of 4 repeater / mimics from a Master 6300
6300 Standalone Maximum of 4 repeater / mimics from a Master 6300 6300 Master 6300 Repeater Mimic 6300 Repeater 6300 Repeater

13 Max Network distance NOT to exceed 8Km (5 miles)
2 Core network Max 32 x 6300 per Network 1 Km Max between Nodes Max Network distance NOT to exceed 8Km (5 miles)

14 6300 Network break Network break 3 & 4

15 X300 Software X300 WIN TEXT - Free software to allow client to write their own device text files (PC Only). X300 Engineer - software charged, to allow engineer to write their own program and download to control panel DONGLE PROTECTED.

16 Device Text Editor Device Text can be edited to suit the site layout
A print out of the device text is available

17 Matrix X300 Matrix - The system cause and effects can be configured using the X300 WINPROG matrix editor. Outputs can be configured as alarm or control O/Ps Selectable Sound settings C&E program Overview shows the cause and effect for the whole system. Matrix delay setting set via ‘Timeouts’ editor Misc settings - refer to next slide Group text to detail C&E areas X300 setting refer to slide

18 Miscellaneous 24 non Latching Fire Devices and 24 latching non fire devices Pulse times for output groups Miscellaneous Keyswitch Inputs The walk test function allows access in User Menu

19 X300 Button Fire Link Delay allows delays on all individual devices or groups of devices The Fire Link output can be programmed for all of the options listed Different languages are supported Network Input Filtering allows a panel to display all events from chosen network panels Check the panel overlay Sensitivity Settings can be changed for individual devices or groups of devices The internal charger is the S9000 EN54 but external chargers can be utilised.

20 Device Editor Unique Serial Number
Sensitivity settings are changeable. LOOP No Address No. Zone – Geographical Representation – up to 32 zones. Alt. display shows more options for the device. Input Group - 96 Output Group - 96 Reset Class resets the device to the default setting.

21 6400

22 6400 System Features Distributed Network System.
Designed for Medium to Large sized buildings such as hotels, Offices, Universities and Hospital Sites. EN54 Compliant DCN (Display Control Node) LPN (Loop Processing Node) Distributed Loop and Sounder Wiring

23 6400 System Features 6400 DCN Accessed Via hinged Lockable Door
Main Fire Lamps Quarter VGA Graphics LCD Display Backlit Zonal display UP TO 100 Zones Fault Lamps

24 6400 System Features 6400 DCN Sound Alarms, Silence, Accept and Reset Buttons Access to Menu Keys On demand Low Noise 40 Character Printer Qwerty Key Board

25 Location text displayed during fault & Fire

26 Alarm text displayed only for Fire

27 6400 System Features 6400 LPN Processes Loop Data
Network Communication Implementation of Cause and Effects Sounder Circuitry Auxillary Changeover Contacts 127 devices per loop either 2 Loop (2LPN) or 4 loop (4LPN) Two Full Duplex RS232 Ports for Graphics and Programming 6400 LPN

28 6400 System Features & = 6400 DCN/LPN
Combining DCN and LPN in single Point Enclosure. Combination gives fully functional system functions and controls in a stand alone panel. DCN/LPN often used as Master Panel for a fully networked system

29 all use the same Processor PCB
RDN / LCD / Mimic The 6400 RCN, LCD and MIMIC all use the same Processor PCB

30 Repeat Display Node Menu / Select / Mute / Silence and Repeat Buttons
Optional Printer Node on the Network Can be Combined with LPN

31 6400 LCD Repeater Listen Only Device Menu / Silent / Mute Buttons
No System Controls Not a Node on the Network but sits on Network. Loop Powered version available.

32 Mimic Repeater Customised Illuminated Mimic Display
LEDS activated by appropriate zone Node on Network Customised Control Options

33 6400 Secure Network Interconnects all Node Options
All nodes are accessible from any 6400/DCN location. Wired as a loop. Dual Channel Fault Tolerant RS 485 No Single fault disables the system. Can act as Stand Alone Up to 99 Nodes on Network Wired as Copper or Fibre Optic

34 6400 Secure Network 99 NODES per NETWORK 2 CORE RS485 NETWORK 1 KM Max
Single and Dual Break safety 99 NODES per NETWORK 1 KM Max

35 Graphics RS232 1 x GRAPHICS PER DCN MAX 20 Mtrs Windows Based
Large Sites – Full Display and Control. Touch Screen option. Zoom Levels Event Logging System available RS232 1 x GRAPHICS PER DCN MAX 20 Mtrs

36 6400

37 6000 PLUS Sensors Temperature Optical Op/ht/co Op/Ht
Low Profile Design Advanced Fire Sensing Technology Electronic Sounders High Intensity LED Warning Beacons Speech Enhanced Talking Sounder Semi Flush Option and Fast Fix Base. All Incorporated in to the Sensor Head Temperature Optical Op/ht/co Op/Ht

38 6000 PLUS Sensors Base Options Fast Fix Recessed Base. Standard Base

39 6000 PLUS Sensors Recessed Fast Fix Bases Step 1
Wire base to diagram shown. Fit and commission sensor, or leave sensor commissioning until after false ceiling is fitted. Step 4 Rotate screw covers to reveal screws. Step 2 Pull sensor/base combination, or base only through ceiling tile hole. (121mm dia) Step 5 Tighten screws until resistance is felt, and clamps have engaged ceiling tile. Do not overtighten Step 3 Push trim onto base. Rotate clockwise to lock trim in position. Push base back through false ceiling so trim is flat to ceiling. Step 6 Rotate screw covers back to original position.

40 Interactive Algo-Tec evaluates the data of each fire sensor and is able to learn from the information received. This may simply be to recognise that a sensor is becoming contaminated or in a dirty environment and to automatically increase the alarm threshold to compensate for the background levels (Threshold compensation). More complex Algo-Tec functions include the ability to discriminate between certain fire and non-fire conditions, filtering out certain environment stimuli, such as steam from a hotel bathroom, and increasing the sensitivity of a sensor (6000 plus OPHT) when an increase in temperature is detected. The net effect of the interaction between the sensors and the Algo-Tec decision making is enhanced performance, through immunity to false alarm and more responsive fire detection.

41 6000 Plus Sensors Optical Sensor • Heat Sensor & Optical Sensor
• Dual Technology High Performance • Multi Criteria High Performance Optical Smoke, Heat and CO Sensor • Independent Channel Control • Day/Night Operation • Protec Algo-TecTM 6000PLUS Protocol • Devices Display Address Number • Easy To Address • FASTTM Addressing • Reduced False Alarms • Electronic Sounder • High Intensity LED Beacon • Voice Enhanced ‘Talking’ Sounder with selectable msgs Optical Sensor

42 6000 Plus Sensors Temp Sensor • Heat Sensor & Optical Sensor
• Dual Technology High Performance • Multi Criteria High Performance Optical Smoke, Heat and CO Sensor • Independent Channel Control • Day/Night Operation • Protec Algo-TecTM 6000PLUS Protocol • Devices Display Address Number • Easy To Address • FASTTM Addressing • Reduced False Alarms • Electronic Sounder • High Intensity LED Beacon • Voice Enhanced ‘Talking’ Sounder with selectable msgs Temp Sensor

43 6000 Plus Sensors Op/Ht/Co Sensor • Heat Sensor & Optical Sensor
• Dual Technology High Performance • Multi Criteria High Performance Optical Smoke, Heat and CO Sensor • Independent Channel Control • Day/Night Operation • Protec Algo-TecTM 6000PLUS Protocol • Devices Display Address Number • Easy To Address • FASTTM Addressing • Reduced False Alarms • Electronic Sounder • High Intensity LED Beacon • Voice Enhanced ‘Talking’ Sounder with selectable msgs Op/Ht/Co Sensor

44 6000 Plus Sensors Op/Ht Sensor • Heat Sensor & Optical Sensor
• Dual Technology High Performance • Multi Criteria High Performance Optical Smoke, Heat and CO Sensor • Independent Channel Control • Day/Night Operation • Protec Algo-TecTM 6000PLUS Protocol • Devices Display Address Number • Easy To Address • FASTTM Addressing • Reduced False Alarms • Electronic Sounder • High Intensity LED Beacon • Voice Enhanced ‘Talking’ Sounder with selectable msgs Op/Ht Sensor

45 6000 / Beam

46 Loop Powered Sounder (2 wire)
6000 / SSR 2 Loop Powered Sounder (2 wire) No of addresses - 1 address No of Cables - 2 cables Alarm Current - 5 mA Quiescent Current mA DB Output dB 1m) Colour - RED or White

47 6000 / ZAI Connections 6000 Loop 6000 Loop Max 1 amp Load
Mains Supply Max 1 amp Load Max 20 x 3000 detectors 8k2 or 100uF EOL 10k EOL Alarm Circuit Detection Circuit

48 Volt free changeover contacts
6000 / Micco Connections 6000 Loop 6000 Loop NO switch 47K EOL Volt free changeover contacts 240 VAC (5amp)

49 Loop Test Unit Compatible with all current Protec
6000 series and 6000 plus Series devices Enables rapid confirmation of correct loop wiring Allows verification of correct number and type of loop devices User may activate a single output at a time Retrieves analogue values from devices Drives 6000PLUS talking sounders Robust construction Easy to read display Can be powered from mains (via supplied charger), or internal batteries

50 Bar-Codes documentation

51 Bar-code sticker removable
Device Bar-Codes 2 x Removable Bar-codes Rear of 6000 Sensor Device Serial Number Bar-code sticker removable 1 x Fixed Bar-code

52 Bar-Codes documentation

53 Download of Serial Nos Serial Numbers entered into 6400 software editor program Device Serial number Bar-Code sticker Bar-Code Reader

54 (Remote Visual Address Verification)
RVAV (Remote Visual Address Verification)

55 Advantages UK Manufacture – All Sensors and Panels made in same factory Fast Addressing – Saves time on site no Switches Identification - Devices can be traced via serial numbers etc. Combined Sensors – Optical/Heat and Optical/Heat/CO Integrated Sounders/LED Beacons/Talking Sounders/Isolators Systems - Small Medium and Large Systems catered for.