Two Minute Drill Number 32- Journeyman Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith
2
Directions Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 15 seconds. As you progress through the slide show, the time for each question will be reduced. This drill is primarily concerning Journeyman Electrical installations. Copyright 2008 Ted "Smitty" Smith
3
1. Standard trade size 2-inch rigid polyvinyl chloride conduit (PVC), shall be supported at least every _____. a.3 feet b.5 feet c.6 feet d.8 feet Copyright 2008 Ted "Smitty" Smith
4
1. b Tbl. 352.30 Copyright 2008 Ted "Smitty" Smith
5
2. When sizing time-delay Class CC fuses for motor branch-circuit, short- circuit, and ground-fault protection, they are to be sized at the same value as _____. a.inverse-time circuit breakers b.Non-time-delay fuses c.Instantaneous trip circuit breakers d.Adjustable trip circuit breakers Copyright 2008 Ted "Smitty" Smith
6
2. bTbl. 430.52,Note 1 Copyright 2008 Ted "Smitty" Smith
7
3. Where sizes 1/0 AWG single conductor cables are installed in ladder type cable tray, the MAXIMUM allowable rung spacing for the ladder cable tray shall be _____. a.6 inches b.9 inches c.12 inches d.15 inches Copyright 2008 Ted "Smitty" Smith
8
3. b392.3(B)(1)(a) Copyright 2008 Ted "Smitty" Smith
9
4. The NEC® requires the MAXIMUM length permitted for a flexible cord supplying a 208-volt, single-phase, room air-conditioner to be ____. a.4 feet b.6 feet c.8 feet d.10 feet Copyright 2008 Ted "Smitty" Smith
10
4. b440.64 Copyright 2008 Ted "Smitty" Smith
11
5. In general, which of the following receptacle outlets in a commercial kitchen are required by the NEC® to be GFCI protected? a.All 125-volt, single phase, 15- and 20- ampere rated receptacles. b.All 125-volt, 15- or 20-ampere rated receptacles in wet locations only. c.All receptacle outlets. d.All 125-volt countertop receptacle outlets only. Copyright 2008 Ted "Smitty" Smith
12
5. a210.8(B)(2) Copyright 2008 Ted "Smitty" Smith
13
6. All wiring installed in or under an aircraft hanger floor shall comply with the requirements for ______ locations. a.Class I, Division 1 b.Class I, Division 2 c.Class II, Division 1 d.Class II, Division 2 Copyright 2008 Ted "Smitty" Smith
14
6. a513.8(A) Copyright 2008 Ted "Smitty" Smith
15
7. In general, branch-circuit conductors supplying more than one motor shall have an ampacity of a at least _____ percent of the FLC of the largest motor, and 100 percent of the FLC of the other motor(s) in the group. a.25 b.80 c.100 d.125 Copyright 2008 Ted "Smitty" Smith
16
7. d430.24 Copyright 2008 Ted "Smitty" Smith
17
8. What is the MINIMUM size equipment grounding conductor required for a 5 HP, three-phase, 208-volt motor having 20- ampere rated overload protection and short- circuit overcurrent protection rated at 30 amperes? a.10 AWG b.14 AWG c.12 AWG d.8 AWG Copyright 2008 Ted "Smitty" Smith
18
8. aTbl. 250.122 Copyright 2008 Ted "Smitty" Smith
19
9. If a circuit breaker serves as the controller for a motor, and the motor is not in sight of the breaker, the NEC® requires which of the following? a.The motor to be less than 2 HP. b.The breaker be able to be locked in the open position. c.The motor to be Code letter “E”. d.The breaker to be rated 25,000 AIC. Copyright 2008 Ted "Smitty" Smith
20
9. b430.102(B)(2), Ex. Copyright 2008 Ted "Smitty" Smith
21
10. In Class II, Division 1, hazardous locations, an approved method of connection of conduit to boxes is _____. a.Compression fittings b.Threaded bosses c.Welding d.All of these Copyright 2008 Ted "Smitty" Smith
22
10. b502.10(A)(4) Copyright 2008 Ted "Smitty" Smith
23
11. Given: an AC service is supplied with four parallel kcmil aluminum conductors. What is the MINIMUM size copper grounding electrode required, when connected to the concrete-encased building steel used as the grounding electrode system? a.3/0 AWG b.4/0 AWG c.250 kcmil d.2/0 AWG Copyright 2008 Ted "Smitty" Smith
24
11. aTbl. 250.66 500 kcmil X 4 conductors = 2000 kcmil total *NOTE: Aluminum service-entrance conductors over 1750 kcmil require a size 3/0 AWG copper grounding electrode conductor. Copyright 2008 Ted "Smitty" Smith
25
12. Given: an AC transformer arc welder has a 50-ampere rated primary current and a 60 percent duty-cycle. Determine the MINIMUM size copper 60°C rated conductors the NEC® requires to supply this welder. a.6 AWG b.8 AWG c.10 AWG d.4 AWG Copyright 2008 Ted "Smitty" Smith
26
12. bTbl. 630.11(A) Tbl. 310.16.78 (duty cycle) X 50 amperes (primary current) = 39 amperes Tbl. 310.16 requires a size 8 AWG conductor. Copyright 2008 Ted "Smitty" Smith
27
13. When installing wiring for sensitive electronic equipment, the MAXIMUM voltage to ground is required to be ____ volts. a.30 b.60 c.120 d.300 Copyright 2008 Ted "Smitty" Smith
28
13. b647.1 Copyright 2008 Ted "Smitty" Smith
29
14. In a health care facility, a patient bed location in a critical care area is required to have which of the following? a.Four single receptacles or two duplex receptacles b.Six single receptacles or three duplex receptacles c.Two duplex receptacles or four single receptacles d.Two single receptacles or one duplex receptacle Copyright 2008 Ted "Smitty" Smith
30
14. b517.19(B)(1)&(2) Copyright 2008 Ted "Smitty" Smith
31
15. Which of the following circuits is prohibited for the grounded conductor to be dependent on receptacle devices for continuity? a.All circuits b.Multi-outlet circuits c.GFCI protected circuits d.Multi-wire circuits Copyright 2008 Ted "Smitty" Smith
32
15. d300.13(B) Copyright 2008 Ted "Smitty" Smith
33
16. Where conduits enter a floor-standing switchboard or panel-board at the bottom, the conduits including their end fittings, shall not rise more than _____ above the bottom of the enclosure. a.6 inches b.4 inches c.2 inches d.3 inches Copyright 2008 Ted "Smitty" Smith
34
16. d408.5 Copyright 2008 Ted "Smitty" Smith
35
17. When installed on the service of a building or structure, a type 2 SPD (TVSS) shall be connected _____. a.On the line side of the service disconnect overcurrent device b.On the load side of the service disconnect overcurrent device c.On the meter housing d.At the final overcurrent device Copyright 2008 Ted "Smitty" Smith
36
17.b 285.24(A) Copyright 2008 Ted "Smitty" Smith
37
18. A detached garage supplied from a dwelling with a three-wire feeder of size 4/0 AWG aluminum USE cable with a 200-ampere rated circuit breaker for overcurrent protection requires a MINIMUM size copper grounding electrode to a concrete encased electrode of _____ AWG. a.8 b.6 c.4 d.2 Copyright 2008 Ted "Smitty" Smith
38
18. c250.52(A)(3) Copyright 2008 Ted "Smitty" Smith
39
19. When a raceway is run from the interior to the exterior of a building, the raceway shall _____. a.Be rigid metal conduit (RMC) b.Be rigid polyvinyl chloride conduit (PVC) c.Be sealed with an approved material d.Have an explosion-proof seal Copyright 2008 Ted "Smitty" Smith
40
19. c 300.7(A) Copyright 2008 Ted "Smitty" Smith
41
20. A disconnecting means shall be provided on the supply side of all fuses in circuits having a voltage of at LEAST ______ volts to ground. a.120 b.250 c.150 d.277 Copyright 2008 Ted "Smitty" Smith
42
20. c 240.40 Copyright 2008 Ted "Smitty" Smith
43
End of Drill Click the left mouse button to advance back to the first question. Each question will now be repeated without the timer to give you a chance to review it and find the answer. Clicking the left mouse button will advance the slide to the answer and the code reference. Copyright 2008 Ted "Smitty" Smith
44
1. Standard trade size 2-inch rigid polyvinyl chloride conduit (PVC), shall be supported at least every _____. a.3 feet b.5 feet c.6 feet d.8 feet Copyright 2008 Ted "Smitty" Smith
45
1. b Tbl. 352.30 Copyright 2008 Ted "Smitty" Smith
46
2. When sizing time-delay Class CC fuses for motor branch-circuit, short- circuit, and ground-fault protection, they are to be sized at the same value as _____. a.inverse-time circuit breakers b.Non-time-delay fuses c.Instantaneous trip circuit breakers d.Adjustable trip circuit breakers Copyright 2008 Ted "Smitty" Smith
47
2. bTbl. 430.52,Note 1 Copyright 2008 Ted "Smitty" Smith
48
3. Where sizes 1/0 AWG single conductor cables are installed in ladder type cable tray, the MAXIMUM allowable rung spacing for the ladder cable tray shall be _____. a.6 inches b.9 inches c.12 inches d.15 inches Copyright 2008 Ted "Smitty" Smith
49
3. b392.3(B)(1)(a) Copyright 2008 Ted "Smitty" Smith
50
4. The NEC® requires the MAXIMUM length permitted for a flexible cord supplying a 208-volt, single-phase, room air-conditioner to be ____. a.4 feet b.6 feet c.8 feet d.10 feet Copyright 2008 Ted "Smitty" Smith
51
4. b440.64 Copyright 2008 Ted "Smitty" Smith
52
5. In general, which of the following receptacle outlets in a commercial kitchen are required by the NEC® to be GFCI protected? a.All 125-volt, single phase, 15- and 20- ampere rated receptacles. b.All 125-volt, 15- or 20-ampere rated receptacles in wet locations only. c.All receptacle outlets. d.All 125-volt countertop receptacle outlets only. Copyright 2008 Ted "Smitty" Smith
53
5. a210.8(B)(2) Copyright 2008 Ted "Smitty" Smith
54
6. All wiring installed in or under an aircraft hanger floor shall comply with the requirements for ______ locations. a.Class I, Division 1 b.Class I, Division 2 c.Class II, Division 1 d.Class II, Division 2 Copyright 2008 Ted "Smitty" Smith
55
6. a513.8(A) Copyright 2008 Ted "Smitty" Smith
56
7. In general, branch-circuit conductors supplying more than one motor shall have an ampacity of a at least _____ percent of the FLC of the largest motor, and 100 percent of the FLC of the other motor(s) in the group. a.25 b.80 c.100 d.125 Copyright 2008 Ted "Smitty" Smith
57
7. d430.24 Copyright 2008 Ted "Smitty" Smith
58
8. What is the MINIMUM size equipment grounding conductor required for a 5 HP, three-phase, 208-volt motor having 20- ampere rated overload protection and short- circuit overcurrent protection rated at 30 amperes? a.10 AWG b.14 AWG c.12 AWG d.8 AWG Copyright 2008 Ted "Smitty" Smith
59
8. aTbl. 250.122 Copyright 2008 Ted "Smitty" Smith
60
9. If a circuit breaker serves as the controller for a motor, and the motor is not in sight of the breaker, the NEC® requires which of the following? a.The motor to be less than 2 HP. b.The breaker be able to be locked in the open position. c.The motor to be Code letter “E”. d.The breaker to be rated 25,000 AIC. Copyright 2008 Ted "Smitty" Smith
61
9. b430.102(B)(2), Ex. Copyright 2008 Ted "Smitty" Smith
62
10. In Class II, Division 1, hazardous locations, an approved method of connection of conduit to boxes is _____. a.Compression fittings b.Threaded bosses c.Welding d.All of these Copyright 2008 Ted "Smitty" Smith
63
10. b502.10(A)(4) Copyright 2008 Ted "Smitty" Smith
64
11. Given: an AC service is supplied with four parallel kcmil aluminum conductors. What is the MINIMUM size copper grounding electrode required, when connected to the concrete-encased building steel used as the grounding electrode system? a.3/0 AWG b.4/0 AWG c.250 kcmil d.2/0 AWG Copyright 2008 Ted "Smitty" Smith
65
11. aTbl. 250.66 500 kcmil X 4 conductors = 2000 kcmil total *NOTE: Aluminum service-entrance conductors over 1750 kcmil require a size 3/0 AWG copper grounding electrode conductor. Copyright 2008 Ted "Smitty" Smith
66
12. Given: an AC transformer arc welder has a 50-ampere rated primary current and a 60 percent duty-cycle. Determine the MINIMUM size copper 60°C rated conductors the NEC® requires to supply this welder. a.6 AWG b.8 AWG c.10 AWG d.4 AWG Copyright 2008 Ted "Smitty" Smith
67
12. bTbl. 630.11(A) Tbl. 310.16.78 (duty cycle) X 50 amperes (primary current) = 39 amperes Tbl. 310.16 requires a size 8 AWG conductor. Copyright 2008 Ted "Smitty" Smith
68
13. When installing wiring for sensitive electronic equipment, the MAXIMUM voltage to ground is required to be ____ volts. a.30 b.60 c.120 d.300 Copyright 2008 Ted "Smitty" Smith
69
13. b647.1 Copyright 2008 Ted "Smitty" Smith
70
14. In a health care facility, a patient bed location in a critical care area is required to have which of the following? a.Four single receptacles or two duplex receptacles b.Six single receptacles or three duplex receptacles c.Two duplex receptacles or four single receptacles d.Two single receptacles or one duplex receptacle Copyright 2008 Ted "Smitty" Smith
71
14. b517.19(B)(1)&(2) Copyright 2008 Ted "Smitty" Smith
72
15. Which of the following circuits is prohibited for the grounded conductor to be dependent on receptacle devices for continuity? a.All circuits b.Multi-outlet circuits c.GFCI protected circuits d.Multi-wire circuits Copyright 2008 Ted "Smitty" Smith
73
15. d300.13(B) Copyright 2008 Ted "Smitty" Smith
74
16. Where conduits enter a floor-standing switchboard or panelboard at the bottom, the conduits including their end fittings, shall not rise more than _____ above the bottom of the enclosure. a.6 inches b.4 inches c.2 inches d.3 inches Copyright 2008 Ted "Smitty" Smith
75
16. d408.5 Copyright 2008 Ted "Smitty" Smith
76
17. When installed on the service of a building or structure, a type 2 SPD (TVSS) shall be connected _____. a.On the line side of the service disconnect overcurrent device b.On the load side of the service disconnect overcurrent device c.On the meter housing d.At the final overcurrent device Copyright 2008 Ted "Smitty" Smith
77
17.b 285.24(A) Copyright 2008 Ted "Smitty" Smith
78
18. A detached garage supplied from a dwelling with a three-wire feeder of size 4/0 AWG aluminum USE cable with a 200-ampere rated circuit breaker for overcurrent protection requires a MINIMUM size copper grounding electrode to a concrete encased electrode of _____ AWG. a.8 b.6 c.4 d.2 Copyright 2008 Ted "Smitty" Smith
79
18. c250.52(A)(3) Copyright 2008 Ted "Smitty" Smith
80
19. When a raceway is run from the interior to the exterior of a building, the raceway shall _____. a.Be rigid metal conduit (RMC) b.Be rigid polyvinyl chloride conduit (PVC) c.Be sealed with an approved material d.Have an explosion-proof seal Copyright 2008 Ted "Smitty" Smith
81
19. c 300.7(A) Copyright 2008 Ted "Smitty" Smith
82
20. A disconnecting means shall be provided on the supply side of all fuses in circuits having a voltage of at LEAST ______ volts to ground. a.120 b.250 c.150 d.277 Copyright 2008 Ted "Smitty" Smith
83
20. c 240.40 Copyright 2008 Ted "Smitty" Smith