1 K. Siva Kumar CEDT, IISc, Bangalore
Multilevel Voltage Space Vector Generation for Induction Motor Drives using Conventional Two-level Inverters and H-bridge cells K. Siva Kumar CEDT, IISc, Bangalore CEDT, Indian Institute of Science Bangalore

2 Overview of the presentation
Introduction Proposed three-level inverter scheme Experimental results Proposed Five-level inverter schemes Conclusion CEDT, Indian Institute of Science Bangalore

3 CEDT, Indian Institute of Science Bangalore
Introduction CEDT, Indian Institute of Science Bangalore

4 CEDT, Indian Institute of Science Bangalore
The induction motor is called as a work horse of the industry The induction motor requires a variable voltage magnitude and frequency to control the rotor speed Conventional two-level inverter CEDT, Indian Institute of Science Bangalore

5 CEDT, Indian Institute of Science Bangalore
Normalized harmonics spectrum of pole voltage Inverter pole voltage (sine-triangle PWM) The harmonic components in the inverter pole voltage are present at higher (switching) frequencies The popular PWM control scheme is space vector pulse width modulation (SVPWM) technique Space vector (Vr) is nothing but a resultant representation of all three phase voltage phasors and it is defined as CEDT, Indian Institute of Science Bangalore

6 CEDT, Indian Institute of Science Bangalore
space vector diagram of conventional two-level inverter The symbols ‘+’ and ‘-’ respectively indicate that the top switch and the bottom switch in a given phase leg are turned on The conventional two-level inverter has to switch at higher frequencies to get a better harmonic profile at the inverter output voltage But in high power applications, high switching frequency is generally not preferred because of the high switching losses and large dv/dt. CEDT, Indian Institute of Science Bangalore

7 CEDT, Indian Institute of Science Bangalore
This dv/dt effect causes EMI problem in the motor and increases stress on the motor winding To overcome these disadvantages, many multilevel inverter configurations and associated analysis of PWM techniques have been suggested The most significant advantages of the multi-level inverters compared to two-level inverters It is possible to use power semiconductor devices of lower voltage ratings to realize high voltage levels at inverter output It is possible to obtain refined output voltage waveforms and reduced total harmonic distortion (THD) It is possible to reduce the EMI problems by reducing the switching dv/dt CEDT, Indian Institute of Science Bangalore

8 CEDT, Indian Institute of Science Bangalore
Multilevel Voltage Source Inverter One phase leg of general n-level inverter The most popular topologies to realize the multilevel inverters are Neutral Point Clamped (NPC) topology Cascaded H-bridge (CHB) topology Flying capacitor (FC) topology CEDT, Indian Institute of Science Bangalore

9 CEDT, Indian Institute of Science Bangalore
Multi-level Inverter topologies feeding from one side of the induction motor NPC inverter FC inverter H-Bridge inverter CEDT, Indian Institute of Science Bangalore

10 Multi-level inverters with open-end winding induction motor
The concept of multilevel inverters with open-end winding is introduced by H. Stemmler and P. Guggenbach in the year 1993 The three-level inverter topology can be realized by feeding an open-end winding induction motor with two two-level inverter from both sides of the winding Three-level inverter topology for open-end winding induction motor CEDT, Indian Institute of Science Bangalore

11 CEDT, Indian Institute of Science Bangalore
The triplen harmonic voltage introduced by the PWM inverters will cause triplen harmonic currents in the motor phase windings, because of the lake of isolated neutral This topology requires either harmonic filter or isolated dc-link voltages to prevent triplen harmonic currents flowing through the motor phase windings The dc-link voltage requirement for each inverter Vdc/2, which is half the dc-link voltage of conventional three-level inverter fed IM drive But the radii of the combined voltage vector hexagon will be Vdc This multilevel inverter topology is free from capacitor voltage balancing issues CEDT, Indian Institute of Science Bangalore

12 CEDT, Indian Institute of Science Bangalore
Motivation Many interesting multi level inverter topologies are proposed by various research groups across the world from industry and academic institutions Apart from the conventional 3-level NPC and H-bridge topology, others are not yet highly preferred for general high and medium power drives applications In this respect, two different five-level inverter topologies and one three-level inverter topology for high power induction motor drive applications are proposed CEDT, Indian Institute of Science Bangalore

13 CEDT, Indian Institute of Science Bangalore
Part - 1 A Dual Two-Level Inverter scheme for a Four-Pole Induction Motor Drive with a single voltage source CEDT, Indian Institute of Science Bangalore

14 Induction machine stator winding arrangement
Stator winding of an induction machine is an arrangement of conductors in the machine slots to produce nearly sinusoidal air gap MMF Four pole induction motor stator winding (full pitch) diagram The conductors in the slots 1 to 3 and 19 to 21 should have the same voltage profile to produce identical magnetic poles Similarly the conductor in the slots 10 to 12 and 28 to 30 should have the same voltage profile CEDT, Indian Institute of Science Bangalore

15 CEDT, Indian Institute of Science Bangalore
In a four pole induction motor, two sets of identical voltage profile coils will be present in the total phase winding, at a phase displacement of 360o (electrical) The identical voltage profile winding coils (or pole pair winding coils) in the stator winding will equally share the applied voltage vector Voltage vector distribution in the four pole induction machine winding CEDT, Indian Institute of Science Bangalore

16 CEDT, Indian Institute of Science Bangalore
Modified four pole induction motor stator winding diagram These identical voltage profile winding coils can be disconnected from a conventional four pole induction machine without any design change Coil connection after the identical pole pair winding disconnection CEDT, Indian Institute of Science Bangalore

17 CEDT, Indian Institute of Science Bangalore
These two identical voltage profile coil groups can be connected in parallel instead of series, thereby the voltage vector Vr/2 is sufficient to drive the four pole induction motor with the same air gap flux profile With this arrangement the dc-link voltage magnitude requirement will come down to half compared to the conventional arrangement From the above discussion one can observe that, it is sufficient to feed the disconnected pole pair winding coils with the same fundamental voltage to get a performance similar to the conventional induction motor CEDT, Indian Institute of Science Bangalore

18 CEDT, Indian Institute of Science Bangalore
Three-level voltage space vector generation for an open-end winding induction motor drive with single voltage source using decoupled space-vector PWM strategy Proposed three-level inverter with one active source for four-pole induction motor drive Cont.. CEDT, Indian Institute of Science Bangalore

19 CEDT, Indian Institute of Science Bangalore
The two identical voltage profile, pole pair winding coils, in each phase of a four pole induction motor, is connected in two star groups These two star connected winding coil groups are fed from two inverters But these two inverters should produce the same fundamental voltage on the motor pole pair winding to generate uniform air gap flux So a decoupled space-vector PWM scheme is used to drive the inverters inverter-I and inverter-II are operated with a reference voltage space vector of Vr/2 and –Vr/2 CEDT, Indian Institute of Science Bangalore

20 CEDT, Indian Institute of Science Bangalore
Space vector diagram of the two inverters Space vector diagram of three-level inverter CEDT, Indian Institute of Science Bangalore

21 CEDT, Indian Institute of Science Bangalore
Timing distribution of the switching states for two inverters in one sampling interval Using the decoupled PWM technique the voltage reference is equally divided in to two new reference vectors for two two-level inverters to generate the same fundamental voltage In a switching time period Ts the voltage vectors OA and OA’ can be generated with a sequence of switching states for inverter-I and 8’-5’-4’-7’ for inverter-II The resultant switching sequence is 88’-15’-25’-24’-77’ CEDT, Indian Institute of Science Bangalore

22 CEDT, Indian Institute of Science Bangalore
Similarly Maximum modulation index Resultant Phase voltage The proposed topology is capable of producing a maximum phase voltage of 0.577Vdc in linear modulation with a single dc link voltage of Vdc/2 So in the proposed scheme, the dc-bus utilization is increased by 15% compared to the earlier schemes presented with a single voltage source CEDT, Indian Institute of Science Bangalore

23 CEDT, Indian Institute of Science Bangalore
Experimental results The proposed topology are experimentally verified on a 5 H.P four pole induction motor (pole pair winding disconnected) drive The drive is operated in open loop V/f control for different voltage reference covering the entire speed range A decoupled space vector PWM scheme is used to generate the switching pulses The inverter switching frequency is kept at 1 kHz for the entire speed range The controller is implemented on TMS320F2812 DSP platform CEDT, Indian Institute of Science Bangalore

24 CEDT, Indian Institute of Science Bangalore
Block diagram of V/f control scheme used for the proposed three-level inverter topology The modulation index (M) given by the Vr/Vdc, so at the end of linear modulation M equal is to 0.866 CEDT, Indian Institute of Science Bangalore

25 Experimental results for modulation index 0.4 (i.e. 20Hz operation)
pole voltages [Y-axis: 100V/div] phase voltage [Y-axis: 200V/div] Phase currents [Y-axis: 2A/div, X-axis: 10ms/div] CKT DIG Normalized harmonic spectrum of the two inverters pole voltages CEDT, Indian Institute of Science Bangalore

26 The first center band harmonics are completely eliminated
Phase voltage [Y-axis: 200V/div] common mode voltage [Y-axis: 100V/div] Effective phase voltage [Y-axis: 200V/div, X-axis: 10ms/div] phase currents effective phase current Normalized harmonic spectrum of the effective phase voltage The first center band harmonics are completely eliminated CEDT, Indian Institute of Science Bangalore

27 Experimental results for modulation index 0.8 (i.e. 40Hz operation)
pole voltages [Y-axis: 100V/div] phase voltage [Y-axis: 200V/div] Phase currents [Y-axis: 2A/div, X-axis: 10ms/div] The first centre band harmonics appear at 25 (1000Hz/40Hz) times the fundamental frequency The isolated neutral presented in the proposed topology will not allow the triplen currents to flow through the motor phase windings Normalized harmonic spectrum of the two inverters pole voltages CEDT, Indian Institute of Science Bangalore

28 The first center band harmonics are completely eliminated
Phase voltage [Y-axis: 200V/div] common mode voltage [Y-axis: 100V/div] Effective phase voltage [Y-axis: 200V/div, X-axis: 10ms/div] phase currents Normalized harmonic spectrum of the effective phase voltage effective phase current The first center band harmonics are completely eliminated the ripple content in the two currents are approximately equal in magnitude with opposite direction CEDT, Indian Institute of Science Bangalore

29 Experimental results for over modulation
pole voltages [Y-axis: 100V/div] phase voltage [Y-axis: 200V/div] Phase currents [Y-axis: 2A/div, X-axis: 10ms/div] The first center band harmonics appear at approximately 21 (1000Hz/47Hz) times the fundamental frequency Because of this square wave operation fifth and seventh harmonic will be presented in the inverter pole voltages Normalized harmonic spectrum of the two inverters pole voltages CEDT, Indian Institute of Science Bangalore

30 common mode voltage [Y-axis: 100V/div]
Phase voltage [Y-axis: 200V/div] common mode voltage [Y-axis: 100V/div] Effective phase voltage [Y-axis: 200V/div, X-axis: 10ms/div] From the above results it is clear that, for full modulation range the first center band harmonics are suppressed in the effective motor phase voltage Normalized harmonic spectrum of the effective phase voltage CEDT, Indian Institute of Science Bangalore

31 CEDT, Indian Institute of Science Bangalore
Salient features The identical voltage profile winding coils are disconnected and connected in two star groups These star connected phase windings are fed from independently controlled inverters The two inverters are fed from a single dc-link voltage source (The isolated neutrals provided by two star winding groups will not allow the triplen currents to flow through the motor phase windings) The first center band harmonics are at two times the carrier frequency The implementation of the proposed scheme does not necessitate any special design requirements for the induction motor It can be extended to induction motor with number of poles more than four CEDT, Indian Institute of Science Bangalore

32 CEDT, Indian Institute of Science Bangalore
Part - 2 A Five Level Inverter Scheme for a Four Pole Induction Motor Drive by Feeding the Identical Voltage Profile Windings from Both Sides CEDT, Indian Institute of Science Bangalore

33 CEDT, Indian Institute of Science Bangalore
Proposed Five-level Inverter Power circuit The advantages of the open-end winding structure along with identical voltage profile winding coils for a four pole induction motor are effectively utilized to realize multilevel structures using conventional two-level inverters CEDT, Indian Institute of Science Bangalore

34 CEDT, Indian Institute of Science Bangalore
In the proposed topology, three isolated voltage source with a magnitude of Vdc/4 (where Vdc is the dc-bus voltage required for a conventional NPC three-level inverter) is used to deny the path for zero sequence currents The switches S11 to S46, in the above figure, are part of the two level inverters which are fed from the voltage source magnitude of Vdc/4 So the maximum voltage blocking capacity of the switches (labelled as Sxy, where x= 1 to 4 and y= 1 to 6) is Vdc/4 With the proposed topology, it is possible to switch four two-level inverters independently and thereby each inverter will have eight switching states Therefore a total of 4096 (8x8x8x8) switching combinations are possible, which are spread over 61 locations CEDT, Indian Institute of Science Bangalore

35 CEDT, Indian Institute of Science Bangalore
Voltage space vector locations for a Five-level inverter Note that each voltage level can be realized in a number of ways CEDT, Indian Institute of Science Bangalore

36 All switching combinations for the five voltage levels for a-phase
Voltage magnitude (level) S11 S21 S31 S41 +Vdc/2 (2) ON OFF +Vdc/4 (1) 0 (0) -Vdc/4 (-1) -Vdc/2 (-2) Presently, the bi-directional switches S1 to S6 , in the power circuit, are assumed to be shorted CEDT, Indian Institute of Science Bangalore

37 CEDT, Indian Institute of Science Bangalore
Schematic of possible voltage levels across the A-phase winding Voltage level at Vdc/2 Voltage level at Vdc/4 Voltage level at 0 Voltage level at -Vdc/4 Voltage level at -Vdc/2 As mentioned above turning on the bidirectional switches (S1 to S6) permanently will cause a short circuit at the middle of motor phase windings CEDT, Indian Institute of Science Bangalore

38 CEDT, Indian Institute of Science Bangalore
It will create an unequal voltage sharing between the same winding groups and this is explained using with switching state combinations 110 and 20-1 (a)Phase winding connection to the voltage sources for switching state 110 (b) Phase winding connection to the voltage sources for switching state 20-1 CEDT, Indian Institute of Science Bangalore

39 CEDT, Indian Institute of Science Bangalore
From the Phase winding connection to the voltage sources for switching state 110, shown above, it can be observed that One group of windings (i.e. A1-A2, B1-B2 and C1-C2) is fed from a voltage vector (110) and the other group of windings (i.e. A3-A4, B3-B4 and C3-C4) is fed from a zero voltage vector (000) part of the A-phase and B-phase winding group (A1A2 & B1-B2) has a voltage of Vdc/4 across it and the other phase group has zero voltage across it Similarly for switching state 20-1 it can be observed that, one group of windings (i.e. A1-A2, B1-B2 and C1-C2) is fed from a voltage vector (100) and the other group of windings (i.e. A3-A4, B3-B4 and C3-C4) is fed from a voltage vector (10-1) However, for a four pole induction machine, two parts of the winding groups should have identical voltage profile for a uniform flux distribution Therefore the present sequence with turning on the bidirectional switches will result in a distorted flux profile CEDT, Indian Institute of Science Bangalore

40 CEDT, Indian Institute of Science Bangalore
(a) Phase winding connection to the voltage sources with equal voltage distribution across the phase winding groups for switching state 110 using the bidirectional switches. (b) Phase winding connection to the voltage sources with equal voltage distribution across the phase winding groups for switching state 20-1 using the bidirectional switches CEDT, Indian Institute of Science Bangalore

41 Possible switching combinations
Voltage magnitude (level) S11 S21 S31 S41 S1 S2 +Vdc/2 (2) ON OFF +Vdc/4 (1) 0 (0) -Vdc/4 (-1) -Vdc/2 (-2) Based on the above considerations it is not possible to realize all the switching combinations presented in the above table CEDT, Indian Institute of Science Bangalore

42 CEDT, Indian Institute of Science Bangalore
All the voltage vector locations inside the first and second innermost hexagon can be realized with the voltage levels ‘-1’, ‘0’ and ‘1’ By using the switching state redundancy, it is possible to clamp inverter-2 and inverter-3 up to modulation index of 0.433 Where the maximum radius of the reference voltage vector within the second innermost hexagon is achieved at a modulation index of 0.433 Both the bi-directional switches, in corresponding phases, are completely turned off for the voltage levels ‘-1’, ‘0’ and ‘1’ The bi-directional switches are also need not to switch up to the modulation index like inverter-2 and inverter-3 So in case of any switch failure in inverter-2 or inverter-3, the proposed five-level inverter can still be operated as a three-level inverter for lower modulation indices CEDT, Indian Institute of Science Bangalore

43 CEDT, Indian Institute of Science Bangalore
voltage rating of the bidirectional switches Phase winding connection to the voltage sources for switching state 22-2, with bi-directional switches the voltage equation for the loop (using Kirchhoff’s voltage Law) (B1 B2 X C2 C1 B1) The maximum voltage across the switch is half the voltage difference between Vdc/4 and the difference between the back emf’s of two phases Maximum voltage appears across the bidirectional switches is Vdc/8 CEDT, Indian Institute of Science Bangalore

44 CEDT, Indian Institute of Science Bangalore
Switching strategy Space vector pulse width modulation (SVPWM) technique is used to generate gating pulses for the proposed inverter The voltage space vector reference (Vr*) can be generated from the motor speed requirement using V/f control , where va, vb and vc are three phase voltages The individual phase voltage references (va*,vb* and vc*) can be derived from voltage space vector To have maximum utilization of dc-bus voltage, in linear modulation, an offset voltage is added to the three reference voltages Voffset = -[max(va*,vb* and vc*) + min(va*,vb* and vc*)]/2 van*= va*+Voffset CEDT, Indian Institute of Science Bangalore

45 CEDT, Indian Institute of Science Bangalore
The A-phase reference voltage Van* modulation index (M= Vr/Vdc) equal to 0.8 In actual experimental verification using a DSP it is difficult to generate four level shifted triangles CEDT, Indian Institute of Science Bangalore

46 CEDT, Indian Institute of Science Bangalore
The modified A-phase reference voltage and triangle carriers The voltage level required by the load is released by comparing the reference wave form with carrier wave The switching state can be select from the above mentioned table CEDT, Indian Institute of Science Bangalore

47 CEDT, Indian Institute of Science Bangalore
Experimental results The proposed five-level inverter topology is experimentally verified on a 5hp four pole induction motor The motor is run at no load condition to show the effect of changing PWM patterns on the motor current Open loop V/f control is used to test the drive for the full modulation range Throughout the speed range, the switching frequency is kept at 1 kHz The controller is implemented in TMS320F2812 DSP platform The gating signals generated from GAL22V10B CEDT, Indian Institute of Science Bangalore

48 CEDT, Indian Institute of Science Bangalore
Block diagram of V/f control scheme used for the proposed five-level inverter topology CEDT, Indian Institute of Science Bangalore

49 Experimental results for modulation index 0.2 (i.e. 10Hz operation)
Total phase voltage voltage across the one phase winding coils phase current [X-axis: 20ms/div, Y-axis: 100V/div, 1A/div] From the phase voltage it can be noted that, the proposed inverter is operating in two-level mode CEDT, Indian Institute of Science Bangalore

50 CEDT, Indian Institute of Science Bangalore
Voltage between the point A2,A3 Inverter-1 pole voltage Inverter-4 pole voltage phase current [X-axis: 20ms/div, Y-axis: 100V/div, 1A/div] Voltage across the bidirectional switch The inverter 1 and 4 are switching half of the period in a fundamental cycle The negative and positive voltage peaks (across the bidirectional switch) are less than half of the inverter pole voltage peak So the maximum voltage appear across the bidirectional switch is Vdc/8 CEDT, Indian Institute of Science Bangalore

51 Experimental results for modulation index 0.4 (i.e. 20Hz operation)
Total phase voltage voltage across the one phase winding coils phase current [X-axis: 20ms/div, Y-axis: 100V/div, 1A/div] From the phase voltage it can be noted that, the proposed inverter is operating in three-level mode CEDT, Indian Institute of Science Bangalore

52 CEDT, Indian Institute of Science Bangalore
Voltage between the point A2,A3 Inverter-1 pole voltage Inverter-4 pole voltage phase current [X-axis: 20ms/div, Y-axis: 100V/div, 1A/div] Voltage across the bidirectional switch Here also the inverter 1 and 4 are switching half of the period in a fundamental cycle The middle inverters (i.e. Inverter 3 and 4) are not switching for full fundamental cycle The negative and positive voltage peaks (across the bidirectional switch) are less than half of the inverter pole voltage peak CEDT, Indian Institute of Science Bangalore

53 Experimental results for modulation index 0.6 (i.e. 30Hz operation)
Total phase voltage voltage across the one phase winding coils phase current [X-axis: 20ms/div, Y-axis: 100V/div, 1A/div] From the phase voltage it can be noted that, the proposed inverter is operating in four-level mode CEDT, Indian Institute of Science Bangalore

54 CEDT, Indian Institute of Science Bangalore
Voltage between the point A2,A3 Inverter-1 pole voltage Inverter-4 pole voltage phase current [X-axis: 20ms/div, Y-axis: 100V/div, 1A/div] Voltage across the bidirectional switch Inverters (inv-2 and inv-3) are switching when the other two inverters (inv-1 and inv-4) are clamped This indicates that, at a time only two inverters are switching, in a fundamental cycle of operation CEDT, Indian Institute of Science Bangalore

55 Experimental results for modulation index 0.8 (i.e. 40Hz operation)
Total phase voltage voltage across the one phase winding coils phase current [X-axis: 20ms/div, Y-axis: 100V/div, 1A/div] From the phase voltage it can be noted that, the proposed inverter is operating in five-level mode CEDT, Indian Institute of Science Bangalore

56 CEDT, Indian Institute of Science Bangalore
Voltage between the point A2,A3 Inverter-1 pole voltage Inverter-4 pole voltage phase current [X-axis: 20ms/div, Y-axis: 100V/div, 1A/div] Voltage across the bidirectional switch Here also inverters (inv-2 and inv-3) are switching when the other two inverters (inv-1 and inv-4) are clamped This indicates that, at a time only two inverters are switching, in a fundamental cycle of operation CEDT, Indian Institute of Science Bangalore

57 Experimental results for over modulation
Total phase voltage voltage across the one phase winding coils phase current Inverter-1 pole voltage Inverter-4 pole voltage Voltage between the point A2,A3 phase current Throughout the modulation range, at a time only two inverters are switched This will result in less switching losses, and it will increase the overall efficiency of the drive system CEDT, Indian Institute of Science Bangalore

58 CEDT, Indian Institute of Science Bangalore
Transient performance of the proposed drive Phase voltage Phase current The transient performance of the proposed drive is tested by accelerating induction motor from 10Hz operation (i.e. 300rpm) to 47Hz (i.e. 1410rpm) The smooth transition of the voltage profile from two-level to five-level can be seen from the waveforms CEDT, Indian Institute of Science Bangalore

59 Comparison between the proposed topology and conventional topologies
NPC Topology Flying capacitor topology H-bridge topology Proposed topology Switches (with a voltage rating of Vdc/4) 24 Clamping diodes Voltage rating of 3*Vdc/4 6 Vdc/2 Vdc/4 Isolated voltage sources (voltage magnitude) 1* (Vdc) 6 (Vdc/4) 3 (Vdc/4) Number of capacitor banks (with a voltage rating of Vdc/4) 4 18 Bi-directional switches (voltage rating ) 6 (Vdc/8) CEDT, Indian Institute of Science Bangalore

60 CEDT, Indian Institute of Science Bangalore
Salient features Two identical voltage profile winding coils in each phase of a four pole induction motor are disconnected The dc bus voltage magnitude requirement is one-fourth compared to a conventional five-level NPC inverter All the inverters are switching for a maximum period of half, in a fundamental cycle In lower modulation indices (M<0.43) the middle two inverters can be clamped for the entire period of fundamental cycle Only conventional two-level inverters are used so this will eliminate all capacitor voltage unbalance issues normally encountered in NPC inverters This concept can be easily extended to induction motor with number of poles more than four and thereby the number of levels on the phase winding can be further increased CEDT, Indian Institute of Science Bangalore

61 CEDT, Indian Institute of Science Bangalore
Part - 3 A Hybrid Five level Inverter Topology for an Open-end winding Induction Motor Drive Using Two-Level Inverters in series with a Capacitor fed H-Bridge Cell CEDT, Indian Institute of Science Bangalore

62 CEDT, Indian Institute of Science Bangalore
Proposed Five-level Inverter Power circuit In this circuit, only one voltage source is used with a magnitude of Vdc/2 where Vdc is the dc-link voltage requirement for the conventional NPC inverter CEDT, Indian Institute of Science Bangalore

63 CEDT, Indian Institute of Science Bangalore
This topology is similar to an open-end winding multilevel inverter structure In the open-end winding multilevel inverter structure, it is possible to generate a three voltage levels on phase winding by connecting two two-level inverters from both sides of the motor phase windings This concept is further extended by introducing an additional flying capacitor with H-bridge cell in series with motor phase windings For the present study, the flying capacitors (Ca, Cb and Cc) are charged to a voltage Vdc/4 If the two level inverters are now clamped to zero voltage, then the H-bridge cell can produce voltage levels of Vdc/4, 0 and –Vdc/4 on the motor phase winding On the other hand, by clamping the H-Bridge cells to zero voltage, the two two-level inverters, with a voltage source magnitude of Vdc/2, can independently generate voltage levels of Vdc/2, 0 and –Vdc/2 on the phase winding When both of them are operated together, it is possible to have five voltage levels on the motor phase windings CEDT, Indian Institute of Science Bangalore

64 CEDT, Indian Institute of Science Bangalore
All possible Switching combinations for the five voltage levels for phase-a Phase voltage Vdc/2 Vdc/4 -Vdc/4 -Vdc/2 Sa1 ON OFF Sa2 * Sa3 Sa4 Capacitor Ca status Ideal ia>0: charging ia<0: discharging ia>0: discharging ia<0: charging ideal Due to the complementary nature of the two-level inverter switches, switch Sa1 ‘ON’ automatically implies that switch S’a1 ‘OFF’ The current from A to A’ is assumed to be the positive direction of current and is shown as ia>0 CEDT, Indian Institute of Science Bangalore

65 CEDT, Indian Institute of Science Bangalore
There are 14 possible switching combinations for one phase to realize the five voltage levels Therefore a total of 2744 (14x14x14) switching combinations are possible for the present work The flying capacitors can be charged or discharged independent of the phase current direction for the voltage levels Vdc/4 and –Vdc/4 (it can be observed from the previous table) The other voltage levels (i.e. Vdc/2, 0 and -Vdc/2) on the phase winding is achieved by bypassing the flying capacitors, so it will not affect the capacitor voltages CEDT, Indian Institute of Science Bangalore

66 CEDT, Indian Institute of Science Bangalore
Common Mode Voltage It is known that inverters controlled by conventional two-dimensional SVPWM will produce a common mode (triplen) voltage along with the fundamental voltage on the motor phase windings The triplen harmonic content in the phase voltage would cause a high triplen harmonic current to flow through the motor phases and power semi-conductor devices To suppress the triplen harmonic current, either harmonic filter or isolated power supplies should be used In this proposed topology two isolated voltage sources are used to deny the path for triplen current CEDT, Indian Institute of Science Bangalore

67 CEDT, Indian Institute of Science Bangalore
Modified Five-level inverter topology The proposed topology can be operate as a dual inverter fed open-end winding Induction motor drive (i.e. three-level operation) for full modulation range, by properly clamping the H-bridge cells CEDT, Indian Institute of Science Bangalore

68 CEDT, Indian Institute of Science Bangalore
Flying Capacitor Design The performance of the proposed topology is dependent on flying capacitor ripple voltage The capacitors can be designed properly to restrict the ripple voltage within acceptable limits The capacitance required by the flying capacitor can be calculated by using the formula Where C is flying capacitor (Ca, Cb or Cc) Ip is peak phase current Ts is switching time period ∆V is the peak-to-peak voltage ripple allowed in the flying capacitor. CEDT, Indian Institute of Science Bangalore

69 CEDT, Indian Institute of Science Bangalore
Experimental results The proposed five-level inverter topology is experimentally verified on a 5hp open-end winding induction motor The motor is run at no load condition to show the effect of changing PWM patterns on the motor current Open loop V/f control is used to test the drive for the full modulation range Throughout the speed range, the switching frequency is kept at 1 kHz The flying capacitor value is chosen as 1100μF The controller is implemented in TMS320F2812 DSP platform The gating signals generated from SPARTAN XC3S200 FPGA CEDT, Indian Institute of Science Bangalore

70 CEDT, Indian Institute of Science Bangalore
The V/f controller block schematic for proposed five-level inverter scheme The symbols vca, vcb and vcc represents the voltage across the flying capacitors (Ca, Cb and Cc) CEDT, Indian Institute of Science Bangalore

71 CEDT, Indian Institute of Science Bangalore
Experimental results for modulation index 0.2 Flying capacitor ripple voltage [2V/div] phase voltage [Y-axis: 50V/div] phase current [Y-axis: 1A/div] [X-axis: 20ms/div] The proposed topology is operating in three-level mode The flying capacitor peak to peak voltage ripple is less than 1V CEDT, Indian Institute of Science Bangalore

72 CEDT, Indian Institute of Science Bangalore
inverter-1 pole voltage [Y-axis: 50v/div] inverter-1 pole voltage H-bridge cell output voltage phase current [Y-axis: 1A/div] [X-axis: 20ms/div] High voltage fed inverters (i.e. inverter-1 and inverter-2) are switching half of the period in fundamental cycle CEDT, Indian Institute of Science Bangalore

73 CEDT, Indian Institute of Science Bangalore
Experimental results for modulation index 0.4 Flying capacitor ripple voltage [2V/div] phase voltage [Y-axis: 50V/div] phase current [Y-axis: 1A/div] [X-axis: 10ms/div] The proposed topology is operating in three-level mode The flying capacitor peak to peak voltage ripple is less than 1V CEDT, Indian Institute of Science Bangalore

74 CEDT, Indian Institute of Science Bangalore
inverter-1 pole voltage [Y-axis: 50v/div] inverter-1 pole voltage H-bridge cell output voltage phase current [Y-axis: 1A/div] [X-axis: 10ms/div] High voltage fed inverters (i.e. inverter-1 and inverter-2) are switching half of the period in fundamental cycle So this will reduce the switching losses of the drive CEDT, Indian Institute of Science Bangalore

75 CEDT, Indian Institute of Science Bangalore
Experimental results for modulation index 0.6 Flying capacitor ripple voltage [2V/div] phase voltage [Y-axis: 50V/div] phase current [Y-axis: 1A/div] [X-axis: 10ms/div] inverter-1 pole voltage [Y-axis: 50v/div] inverter-1 pole voltage H-bridge cell output voltage phase current [Y-axis: 1A/div] [X-axis: 10ms/div] The proposed topology is operating in three-level mode CEDT, Indian Institute of Science Bangalore

76 CEDT, Indian Institute of Science Bangalore
Experimental results for modulation index 0.8 Flying capacitor ripple voltage [2V/div] phase voltage [Y-axis: 50V/div] phase current [Y-axis: 1A/div] [X-axis: 5ms/div] inverter-1 pole voltage [Y-axis: 50v/div] inverter-1 pole voltage H-bridge cell output voltage phase current [Y-axis: 1A/div] [X-axis: 5ms/div] The flying capacitor voltage is well balanced (since, ripple voltage magnitude is less) when the inverter is operating at five-level mode CEDT, Indian Institute of Science Bangalore

77 CEDT, Indian Institute of Science Bangalore
Normalized harmonic spectrum of the motor phase voltage The first centre band harmonics is present at 25 (1000Hz/40Hz) times the fundamental frequency the peak harmonic voltage magnitude is around 8% and it is placed at 50 times of the fundamental frequency, thereby the effect of this harmonic voltage on motor phase current is insignificant CEDT, Indian Institute of Science Bangalore

78 CEDT, Indian Institute of Science Bangalore
Experimental results for over modulation Flying capacitor ripple voltage [2V/div] phase voltage [Y-axis: 50V/div] phase current [Y-axis: 1A/div] [X-axis: 5ms/div] inverter-1 pole voltage [Y-axis: 50v/div] inverter-1 pole voltage H-bridge cell output voltage phase current [Y-axis: 1A/div] [X-axis: 5ms/div] The H-bridge capacitor voltage is well balanced (since, ripple voltage magnitude is less) when the inverter is operating at over modulation CEDT, Indian Institute of Science Bangalore

79 CEDT, Indian Institute of Science Bangalore
Transient performance of the proposed drive Transient performance of the proposed scheme during speed reversal operation of the drive The capacitor voltage is balanced for the full modulation range Even though the accelerating and decelerating the motor draws current much more than the steady state operation, yet the capacitor voltage is balanced for the full modulation range CEDT, Indian Institute of Science Bangalore

80 Comparison between the proposed topology and conventional topologies
NPC Topology Flying capacitor topology H-bridge topology Proposed topology Switches voltage rating of Vdc/4 24 12 Vdc/2 Clamping diodes Voltage rating of 3*Vdc/4 6 Vdc/4 Isolated voltage sources (voltage magnitude) 1* (Vdc) 6 (Vdc/4) 2 (Vdc/2) Number of capacitor banks (with a voltage rating of Vdc/4) 4 18 3 CEDT, Indian Institute of Science Bangalore

81 CEDT, Indian Institute of Science Bangalore
Salient features The concept of open-end winding structure is extended by adding a flying capacitor in series with motor phase winding This results in a five level inverter topology It does not require any clamping diodes as in a conventional five-level NPC inverter It requires only one capacitor bank for each phase, whereas five-level flying capacitor require 6 additional capacitor banks for each phase this proposed topology reduces the power circuit complexity compared to NPC or flying capacitor topologies In case of any switch failure in the H-bridge cell, the proposed inverter topology can be operated as a three-level inverter for full modulation range using open-end winding concept CEDT, Indian Institute of Science Bangalore

82 CEDT, Indian Institute of Science Bangalore
Overall experimental setup CEDT, Indian Institute of Science Bangalore

83 CEDT, Indian Institute of Science Bangalore
List of publications K. Sivakumar, A. Das, R. Ramchand, C. Patel, K. Gopakumar, “A Five Level Inverter Scheme for a Four Pole Induction Motor Drive by Feeding the Identical Voltage Profile Windings from Both Sides”, IEEE Trans. on Industrial Electronics(accepted for publication) K. Sivakumar, A. Das, R. Ramchand, C. Patel, K. Gopakumar, “A Hybrid Multilevel Inverter Topology for an Open-end winding Induction Motor Drive Using Two-Level Inverters in series with a Capacitor fed H-Bridge Cell”, IEEE Trans. on Industrial Electronics(accepted for publication) K.Sivakumar, Rijil Ramchand, Anadarup das, Chintan Patel, K.Gopakumar, “Two different Schemes for Three-level Voltage Space Vector Generation for Induction Motor drives with Reduced DC-Link Voltage”, EPE( European power electronics journal),(accepted for publication and scheduled on march 2010) K. Sivakumar, Anandarup Das, Rijil Ramchand, Chintan Patel, K.Gopakumar, “A Simple Five-Level Inverter Topology for Induction Motor Drive Using Conventional Two-Level Inverters and Flying Capacitor Technique”, IEEE IECON 2009, 3-5 November 2009 at Porto, Portugal. K. Sivakumar, Anandarup Das, Rijil Ramchand, Chintan Patel, K.Gopakumar, “A Three Level Voltage Space Vector Generation for Open End Winding IM Using Single Voltage Source Driven Dual Two-Level Inverter”, IEEE TENCON 2009, November 2009 at Singapore. CEDT, Indian Institute of Science Bangalore

84 CEDT, Indian Institute of Science Bangalore
Thank you CEDT, Indian Institute of Science Bangalore