Download presentation
Presentation is loading. Please wait.
Published byKelley Long Modified over 9 years ago
1
E VERY L IFE H AS A P URPOSE… Chillgard ® RT Refrigerant Monitors
2
AGENDA Why Monitor Refrigerants? Photoacoustic Infrared Detection Chillgard RT Features and Benefits BACnet Capabilities Summary
3
Personnel Safety inside Mechanical Rooms ASHRAE 15 Guideline Local Building Codes International Mechanical Code Economics $$$$ System Efficiency Replacement Cost of Refrigerant Potential Government (EPA) Fines Why Monitor?
4
ASHRAE Guidelines ASHRAE 15 Why Monitor?
5
MSA offers a variety of devices to meet this requirement Strobes Horns Remote Display Signs per specification ASHRAE 15 requires Entry-Way Signaling at each entrance of a Mechanical Room Why Monitor? ASHRAE Guidelines
6
ASHRAE 147: The Green Standard - Acknowledges Ozone Depletion and EPA Clean Air Act Why Monitor? ASHRAE Guidelines
7
Where They Are Used SCHOOLS UNIVERSITIES DATA CENTERS COMMERCIAL BUILDINGS HOTELS CASINOS HOSPITALS CONVENTION CENTERS INDUSTRIAL PLANTS
8
Who are the Customers? ● Chiller manufacturers ● Building Control Companies ● Contractors - HVAC & Mechanical ● End Users - Direct sales ● Hospitals, Universities, Government
9
Both absorptive and photoacoustic techniques utilize infrared energy of a selective wavelength. Majority of gases absorb infrared energy of various wavelengths. Infrared Detection Methodology The wavelength selected for use in detection is determined by the gas in use and its specific characteristics.
10
Photoacoustic Infrared Gas Detection Technology To better understand the advantages of Photoacoustic Infrared Technology, we will briefly compare it to the older, more commonly used Absorptive Infrared Technology. Photoacoustic Infrared Technology Absorptive Infrared Technology How Does It Differ?
11
Infrared Technology Yellow Yellow is an infrared wavelength used to detect this specific gas. Red is representative of a typical gas absorption characteristic.
12
Absorptive Technique All absorptive infrared detection methods differ from manufacturer-to-manufacturer. However, the basic principal remains the same. Sample and reference measurements must be taken. The sample cell is exposed to the gas to be detected. The reference cell is either isolated from the gas to be detected or infrared energy outside the absorptive wavelength characteristics of the gas to be detected is used. The two measurements are compared. If they are equal, the instrument will indicate zero (0).
13
In this example, infrared sources deliver infrared energy through separate sample and reference cells to separate sample and reference detectors. Absorptive Technique
14
When the gas to be detected is present, it absorbs some portion of the sample infrared energy The reference infrared energy is unaffected by the gas to be detected The change in ratio of the sample and reference detectors is the actual concentration of gas present
15
Photoacoustic Infrared Technology Has been in use since the 1960’S MSA – 10 Years of experience in PIR gas monitors Has replaced many traditional infrared analyzers as well as other sensing technologies
16
Photoacoustic Infrared Gas Detection The ability to sense a leak as low as in the PPB level for some applications. Photoacoustic Infrared sensing technology differs from all other available detection techniques on the market. It has 2 distinct advantages: The ability to operate long periods of time without adjustment or zero drift, a common problem with all other technologies in use today.
17
Basic PIR Cell Assembly
18
Photoacoustic IR Optical Bench IR source - wire filament emitting multiple wavelengths of light Chopper (not shown) - used to setup modulation Optical filters – provide sensitivity and selectivity for a given gas selected for specific application Optical block - volume can be changed for specific ranges Detector- high sensitivity microphone Solenoid valves - sample inlet and outlet provide seal during photoacoustic gas detection Heater and thermostat (not shown) - temperature control critical for low PPM or PPB detection
19
CHILLGARD RT REFRIGERANT MONITOR
20
1, 4, or 8 Channel Configuration All Refrigerants & Ammonia Standalone Sample Draw System Chillgard RT Monitor Premier Monitor on the Market NEMA 4 Design Multiple Refrigerants, up to 6
21
Refrigerants Detected R11, 12, 22, 123, 134A 400 Series Refrigerants including R410A and R407C 500 Series Refrigerants New Refrigerants such R1234YF Ammonia There isn’t a commercially available refrigerant that we can’t detect!
22
Sample Points Up to 8 points Samples each point for 30 seconds when no gas present Samples an extra 60 seconds if gas level exceeds threshold value 150 ft w/ 1/8 inch id tubing 500 feet w/ 3/16 inch id tubing
23
UL2075 Performance to 1ppm Photoacoustic Infrared Sensor Meets ASHRAE 15 & 147 Requirements Chillgard RT Monitor Direct Measurement Technique
24
Chillgard ® RT Monitor Text Message Display Data Logging via RS-232 4-20 mA or 0-10V Output Local Event and Diagnostics 3 Levels of Alarm Relays plus Fault
25
Accessories Remote relay package Provides individual banks of relays for each point Remote Display Provides refrigerant level info before entering room Filters, Calibration kits, tubing etc.
26
BACnet BACnet is acronym for Building Automation Controls network. ASHRAE was a huge proponent in development of the protocol. Published as Standard ASHRAE/ANSI Std 135. The key benefit to BACnet is that it allows communication across multiple product lines. Major Building Controls Companies have migrated to BACnet as their choice of communication Protocol.
27
BACnet capabilities Millenium gateway from Industrial Control Communications provides BACnet MS/TP output Can be connected to a Chillgard L series as well as an RT Gateways will be loaded with a driver to convert from the MSA protocol to BACnet PN 10117875 for the Chillgard L Series PN 10117876 for the Chillgard RT
28
BACnet Gateway No configuration is necessary Data is automatically mapped into database upon protocol selection Fixed network characteristics 19200 baud rate 8 data bits 1 start bit 1 stop bit No parity
29
Wiring Instructions Connect MSA monitors to the Gateway selected RS-485 port using a twisted-pair cable, connected as shown in the next slides The gateway can be powered from the 12V supply on the Chillgard RT Monitor by connecting J14 terminals 1 (+12V) and 3 (GND) to POWER and GND Gateway terminals, respectively.
30
Wiring to a Chilgard L series Connect “+” (RS-485 to optional relay module terminal block for Chillgard LC and LE Monitors) to terminal “A” of the gateway, “-” (RS-485 to optional relay module terminal block for L series Monitors) connects to terminal “B” of the gateway, the ground terminal “G” (RS-485 to optional relay module terminal block for LC and LE) terminal to terminal GND of the gateway Install jumper wires connecting terminal “A” to terminal “Y, and terminal “B” to terminal “Z” on the gateway
31
Wiring to a Chilgard RT Connect “+ / A” (J15 terminal 2 or 4 for terminal of Chilgard RT to Gateway terminal “A”, “- / B” (J15 terminal 1 or 3 for Chillgard RT Monitor) terminal “B” and ground terminal GND (J14 terminal 3 for Chillgard RT Monitor) terminal to terminal GND. Also install jumper wires connecting terminal A to terminal Y, and terminal B to terminal Z on Gateway.
32
How to order and notes Contact MSA’s Custom Products group to purchase a Chillgard system with BACnet output MSA will pre-load the configuration file to convert to BACnet based on either an L series or an RT Gateway will provide BACnet objects that will need to be mapped to your network Review the default configurations from the gateway with regards to the Chillgard mapping
33
CHILLGARD RT Summary PREMIER MONITOR ON THE MARKET PROVEN, RELIABLE PHOTOACOUSTIC INFRARED TECHNOLOGY CAN DETECT ANY REFRIGERANT DESIRED UL 2075 APPROVAL – DETECTION TO 1 PPM
34
Questions? THANK YOU !
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.