1 EWAP-MBYNN Air-cooled Applied Systems Sales

2 EWAP-MBYNN Air-cooled Contents A. Equipment Overview B. Capacity Range
C Operation Range D. Specifications E. Construction F. Options & Kits Applied Systems Sales

3 Single Circuit (1 Compressor) Double Circuit (2 Compressors)
A. Equipment Overview EWAP MBYNN EWAP MBYNN EWAP MBYNN Single Circuit (1 Compressor) Double Circuit (2 Compressors) Large Chillers: R-407C Daikin stepless single screw compressor All components optimized for use with R-407C Air heat exchanger: Cross fin coils / Hi-X tubes and PE waffle louvre fins Water heat exchanger: Brazed plate evaporator Double refrigeration circuit (from 400kW) Applied Systems Sales

4 EWAP-MBYNN B. Capacity Range Model 110 140 160 200 280 340 400 460 540
kW HP Single circuit (1 compressor) Double circuit (2 compressors) Applied Systems Sales

5 LWE to -10°C Low Ambient to -15°C
C. Operation Range Ambient (°C ) 50 LWE to °C 43 40 39 36 30 20 Continuous Operation Area Pull-Down Area 10 On special request Protect against freezing by: Evaporator heater tape (std) Glycol Low Ambient to -15°C The air-cooled chillers operate from ambient temperatures as low as -15°C to +43°C. Units are fitted standard with head pressure control to deal with low ambient. Above 43Deg C high pressure setback prevents the unit tripping on high pressure so ensuring cooling. On the water side, chilled water from 16oC down to -10°C can be produced. The dual setpoint facility can be used to ones advantage by producing chilled water during the day, while making ice for storage during the evening off peak billing period. An evaporator heater tape protects the unit against freezing, however in severe ambients or negative leaving water applications a % of glycol needs to be added. -10 -15 -20 Glycol Water LWE (°C) -30 -5 4 16 26 -20 -10 10 20 30 Applied Systems Sales

6 Single Screw Compressor
D. Specifications Brazed Plate Heat Exchanger Daikin Stepless Single Screw Compressor pCO2 Control Platform Applied Systems Sales

7 D. Specifications -> Refrigerant
EWAP~MBY Zeotropic Blend R32-R125-R134a Chlorine free Not toxic Not flammable Good and efficient refrigerating capacity Applied Systems Sales

8 D. Specifications -> Stepless Compressor
Reliable New compressor: New features: Stepless G-type compressor - Newly designed gate rotors - High efficient electric motor - COP increase of 5 to 10% - Newly designed slide vanes Applied Systems Sales

9 D. Specifications -> Stepless Compressor
High Efficiency Engineered plastic gate rotors Ensuring closer tolerences Compact Design Durable & Reliable Fewer moving parts Balanced forces = Low bearing loads Plastic on metal = Low wear No need for oil pump 1st Service Interval after hours Low Vibration & Noise Plastic on metal = lower noise Runs at 2900rpm = compressions/min Smoothed discharge flow = low vibrations Applied Systems Sales

10 D. Specifications -> Stepless Compressor
Launch of STEPLESS capacity control (Sales launch: August 2005) Better partial load control WHAT YOU WANT IS WHAT YOU GET More precise control of the temperature OUTLET CONTROL (± 0.5oC) Smaller minimum water volume required  Upto 40% less than stepped chillers  Less need for buffer tanks G-type stepless Higher Efficiency Saves the environments resources … and nevertheless your own resources Designed, tested and manufactured in Daikin’s own laboratories. Applied Systems Sales

11 D. Specifications -> Stepless Compressor
Higher Efficiency STEPLESS capacity regulation The compressor has built-in capacity control by 30 – 100% by stepless slide valve mechanism, and adjustable volumetric ratio 100% 30% 12% Chiller Load Demand Starting position Single Circuit 100% 15% 12% Chiller Load Demand Starting position Double Circuit Designed, tested and manufactured in Daikin’s own laboratories. Applied Systems Sales

12 D. Specifications -> Evaporator
Brazed plate heat exchangers for evaporator Filter & Flow switch High W/m² value for increased efficiency Optimal refrigerant distribution Decreased refrigerant charge Super- heated Vapor & Liquid Water Refrigerant Applied Systems Sales

13 D. Specifications -> Evaporator Hydronics
To secure the safety of YOUR installation + EASY INSTALLATION Filter Semi Full Flow Switch * NOTE: Only for EWAP MBYNN Standard Mounting * Perforation diameter = 1mm Filter to Daikin Spec (free supplied) Victaulic Joints (free supplied) Flow switch (factory pre-mounted) Applied Systems Sales

14 D. Specifications -> Evaporator Hydronics
Victaulic joints: - Absorb vibration - Reduce operating sound - Reduce thermal deflection - Simplify chiller installation 8° angle guarantees stress free Leak tight water piping connection Applied Systems Sales

15 D. Specifications -> Evaporator Heater
Standard with Evaporator Heater Tape Applied Systems Sales

16 D. Specifications -> pCO2 Controller
The nerve centre of the Chiller System Benefits for the user ... - provides detailed information - accurate control of all functional parameters - easy menu screen scrolling. Applied Systems Sales

17 D. Specifications -> pCO2 Controller
Features Automatic restart after power failure Control of operating and safety parameters Schedule timer (4 timer groups) Advanced freeze-up control Floating set point according to ambient temperature Extended alarm history (20 alarms) 5 languages Time and date information Daily pump on Temperature probe fine tuning Lead-lag of compressors Applied Systems Sales

18 D. Specifications -> Temperature Control
Inlet / Outlet Control Floating Setpoint Alters setpoint in function of ambient or ∆T Increase setpoint = increase evaporating temp Sampling of temperatures every 12seconds Fast (7%) Load-up, Slow Load-up (3%) or No Action depending on deviation Fast (7%) Load-down, Slow Load-down (3%) or No Action depending on deviation Applied Systems Sales

19 D. Specifications -> Freeze-up Control
LWE (°C) Freeze-up Prevention Unload compressor if LWE drops 1oC below MOW 4 3 2) Freeze-up Protection Stop compressor if LWE drops 1,5oC below MOW 2,5 Freeze-Up Safety Setting 1 2 t(min) STOP *For Glycol: ZH -6,5°C / ZL -11,5°C Applied Systems Sales

20 D. Specifications -> DICN
WHAT? Combine up to 4 DAIKIN chillers as if they were 1 unit … FEATURES : - Entering or Leaving water control - Running hours balancing between units - Flexible and efficient pump control - Features of the individual unit remain ADVANTAGES: Comfort cooling : Process / Industrial cooling : - Extend the DAIKIN chiller range - Create a chiller system of up to 2 MegaWatt ... - Even more precise & efficient capacity control - Standby : provide backup in case of alarm - Cooling available under any conditions Bigger System Capacity Increase System Reliability Applied Systems Sales

21 D. Specifications -> DICN
DICN - System Example 1 Slave 3 “Constant water volume system” Leaving water control with sensor. Slave 2 Pump runs if at least 1 unit = ON. Slave 1 Fixed Speed Pump Master LOAD EKCLWS Applied Systems Sales

22 D. Specifications -> DICN
Fixed Speed Pumps Slave 3 DICN - System Example 2 “Variable flow water system” SL3 Slave 2 Entering water control. SL2 Pump SL1-3 runs if unit = ON Slave 1 Pump Master runs always. SL1 Inverter pump Master M1 Applied Systems Sales

23 D. Specifications -> Safety Devices
Double high pressure switch Low pressure switch Freeze-up prevention & protection Discharge thermal protector Pressure relief valve on compressor Compressor motor over current protector Compressor motor thermal protector Reverse phase protector Recycling and guard timer Digital display controller with electronic temperature control Emergency Stop HP LP Applied Systems Sales

24 E. Construction -> Condenser
Cross fin coils (Aluminum) Lubricant layer Hydrophilic layer Colouring & Corrosion proof Corrosion proof layer Standard anti-corrosion treated As standard, all air-cooled condensers are given anti-corrosion treatment. Depending on the capacities and models, the Daikin chillers are undergoing acrylic, black-epoxy or chromate treatment. This treatment significantly increases resistance to acid rain and saline corrosion. Typically in an acetic salt spray test at 1000hrs a bare aluminium coil has a 7,5% mass loss whereas the acrylic coated coil has about 4% mass loss. After a 1000hrs corrosion of the bare Al coil is accelerated. On request, Daikin can also provide extra corrosion protection options for special applications in harsh environmental conditions. Acetic Salt Spray Test in accordance with ISO9227 Applied Systems Sales

25 High Quality Platework!
E. Construction -> Robust Chassis All-Weather Urban and Industrial Environment PE Condenser Coils ( “Blue color” ) High Quality Platework! Galvanized steel plate Zinc-Phosphate coating Epoxy powder painted) COLOR  Ivory white (Munsell code 5Y7.5/1) Applied Systems Sales

26 E. Construction -> EWAP110-160MBY
Single Circuit 2 V-Shape PE Condensers 2250 Daikin Controller + cover Plate Heat Evaporator (Back Side) Daikin Single Screw Compressor + Housing 2238 2346 Applied Systems Sales

27 E. Construction -> EWAP200-340MBY
Single Circuit 4 V-Shape Chromate Treated Condensers 2250 Plate Heat Evaporator (Back Side) Daikin Single Screw Compressor + Housing 4280 2238 Applied Systems Sales

28 High Reliability !!! E. Construction -> EWAP400-540MBY
Double Circuit 6 V-Shape Chromate Treated Condensers 2250 Daikin Single Screw Compressor + Housing 2 x Plate Heat Evaporator (Inside) 5901 Daikin Single Screw Compressor + Housing 2238 High Reliability !!! Applied Systems Sales

29 E. Construction -> Switchbox
Automatic Door Lock Spacious / Easy accessible Switch Box Space Space Field Wiring  Spacious  Ergonomic Height  High Quality Components * EWAP MBYNN Applied Systems Sales

30 E. Construction -> Serviceability
Easy Maintenance 3000 Required Space for Service and Air Intake 1000 1000 1000 500* 1000* Same Specs for complete Range *Only Range Applied Systems Sales

31 F. Options & Kits -> Factory Fitted
Low Noise Operation OPLN Inverter Fans OPIF High ESP Fans OPHF Dual Pressure Relief Valve OP03 Suction Stop Valve OP12 Mains Isolator Switch OP52 Ammeter Voltmeter OP57 Condenser Protection OPCG Heat Recovery (See EWTP unit) OPHR Applied Systems Sales

32 F. Options & Kits -> Low Noise (OPLN)
Insulated compressor compartment + Reduce fan speed 900 to 600rpm High performance absorption & insulation material Anti vibration material. = Sound power level reduction of - 6 dB(A) Applied Systems Sales

33 Offered with or without OPLN
F. Options & Kits -> Inverter Fans (OPIF) - Smooth operation, better colour of sound - Linear sound reduction in function of ambient Sound reduction in function of ambient temperature 15 20 25 30 35 40 -1 -2 -3 -4 Sound power level (dBA) Ambient temp. (°C) Further Reduction of - 3dBa Offered with or without OPLN Applied Systems Sales

34 Example: EWAP540 @ 5oC ambient Result = 15kWhr Energy Saving!
F. Options & Kits -> Inverter Fans (OPIF) Stable HP control, better part load efficiency Energy savings at ambient 10oC to -15oC Example: 5oC ambient On/Off Fan HP control Cycling of fans On and Off Requires dead band Avg Tcondensing = 39oC ON/OFF Inverter Fan HP control Stepless modulation of fan speed No dead band Target Tcondensing = 30oC Inverter Result = 15kWhr Energy Saving! Applied Systems Sales

35 F. Options & Kits -> High ESP Fans (OPHF)
Applied Systems Sales

36 Non Return Valve on HP-Side
F. Options & Kits -> For Service OP03 Dual Pressure Relief OP12 Suction Stop Valve Non Return Valve on HP-Side is Standard Stop Valve on LP-Side is an option 1 Pressure Side HP-Side Suction Side LP-Side 2 Re-calibration possible without refrigerant evacuation Daikin Single Screw Compressor Applied Systems Sales

37 V A F. Options & Kits -> For Service OP57 Ammeter / Voltmeter
Compressor 1 Compressor 2 OP52 Mains Isolator Switch L1, L2, L3 Applied Systems Sales

38 F. Options & Kits -> Protection Grilles (OPCG)
Factory Mounted Condenser Protection Grilles Applied Systems Sales

39 F. Options & Kits -> Heat Recovery (OPHR)
Cooling Load 400C 450C 120C 70C Heating Return Supply COP>5 Criteria Hot water demand must be great enough to justify cost High enough useful waste heat temperature * See EWTP~MBYNN presentation Applied Systems Sales

40 F. Options & Kits -> Field Installed
Remote Controller EKRUPC BMS Modbus EKBMSMBA Bacnet EKBMSBNA DICN LWE Sensor EKCLWS Applied Systems Sales

41 F. Options & Kits -> Remote & BMS
Remote Controller & BMS UNIT Remote Controller PCO² - Controller PCO-controller EKRUPC BMS (Building Management System) EKAC200A Gateway RS232/485/422 EKBMSMBA EKBMSBNA Applied Systems Sales

42 F. Options & Kits -> BMS
Interface needed Question Answer Read out :  Temperatures  Pressures  Status  Alarms... Write :  Setpoints  Remote on/off  Operation mode ... Modbus: Max. 16 addresses BACnet: Max. 8 addresses Data exchange and communication between the chiller and the BMS is realized by CLICK the principle of “QUESTION” and “ANSWER”. The BMS sends out a question signal concerning a certain parameter, and the chiller replies with the proper answer. CLICK Among the exchanged information, we can find 2 kinds of parameters. READ ONLY parameters, such as temperatures, pressures, status, alarms. Then we also have the WRITABLE or CHANGEABLE parameters. These are for instance altering of the setpoints, changing of the operation mode for small chillers, start/stop circuits, … All together, with a 2 circuit large chiller, you can access up to more than 130 parameters. Access up to 130 parameters Applied Systems Sales

43 Large Air-Cooled Chillers EWAP110~540MBY
1. R-407C: the good choice ! 2. High specifications 3. High Quality Components 4. Useful Options Applied Systems Sales