Download presentation
Presentation is loading. Please wait.
Published bySophia Bryant Modified over 9 years ago
1
Development of the Envelope Criteria Merle McBride, Ph.D., P.E Senior Research Associate Owens Corning ASHRAE Representative At Large Orlando, FL February 7, 2005
2
Agenda - Objective - Problem Statement - Background - Approach - Analysis - Results - Conclusions - Recommendations - Q & A
3
Objective Develop prescriptive criteria that will result in a 30% energy savings relative to ANSI/ASHRAE/IESNA Standard 90.1-1999.
4
Problem Statement Include in Analysis: - Envelope - HVAC - O.A. Damper Controls - SWH - Interior Lighting Exclude from Analysis: - Exterior Lighting - Plug Loads (Office Equip. & Appliances)
5
Background 90.1 Development LCC Economics Classes of Construction Base Energy Usage –Climate Zones –Constructions –Size
6
Classes of Construction Roofs –Ins. Above Deck –Metal Building –Attic and Other Walls, Above Grade –Mass –Metal Building –Steel Framed –Wood Framed & Other Floors –Mass –Steel Joist –Wood Framed & Other Walls, Below Grade Slab –On-Grade –Unheated –Heated Opaque Doors –Swinging –Non-Swinging Fenestration (U, SHGC) –10%, 20%, 30%, 40%, 50% Skylights (3% max.) –Curb, Glass –Curb, Plastic –No Curb
8
8 Climate Zones, 15 Cities
9
15 Cities
10
90.1-2004 and SP102 8 Climate Zones, Counties Map
11
Approach Floor Area5,000 ft 2 20,000 ft 2 No. StoriesOneTwo RoofWood FramedIns. Above Deck WallsWood FramedMass FoundationUnheated SlabUnheated Slab WWR20% & 40%30% & 40%
12
Analysis Couple economics and energy savings Design of Experiment (DOE) Simplified Energy Regression Models –Heating, Cooling, SWH, Fans, AUX Iterative Solution Technique –30% Energy Savings by Climate Zone Merge 5,000 ft 2 and 20,000 ft 2
13
LCC Economics INCREMENTAL ENERGY SAVINGS > INCREMENTAL FIRST COSTS (1) HEATING + COOLING > INCREMENTAL FIRST COSTS (2) (U 1 –U 2 )*Hcoef*HDD65*P h *SR + (U 1 –U 2 )*Ccoef1*CDD50*P c *SR > FC 2 –FC 1 (3) Hcoef*HDD65*P h *SR + Ccoef1*CDD50*P c *SR > (FC 2 –FC 1 ) (4) (U 1 –U 2 ) (FC 2 –FC 1 ) = ΔFC/ΔU(5) (U 1 –U 2 ) [Hcoef*HDD65*P h + Ccoef1*CDD50*P c ]*SR > ΔFC/ΔU (6)
14
dFC/dU
15
Design of Experiment 5,000 ft2
16
DOE-2 Simulations
17
Heating Regression Equation HEATING = UoAo*24*HDD65/(AFUE*CF) + 1.08*ACH*VOLUME*24*HDD65/(AFUE*CF) - WALLg*WWR*(N.Area-%)*SHGCn*PFn*SOLARn*%HEAT/CF - WALLg*WWR*(E.Area-%)*SHGCe*PFe*SOLARe*%HEAT/CF - WALLg*WWR*(S.Area-%)*SHGCs*PFs*SOLARs*%HEAT/CF - WALLg*WWR*(W.Area-%)*SHGCw*PFw*SOLARw*%HEAT/CF - (Lighting + Plugs + Fans)*%HEAT - People*Sensible*55hr.wk*52wk/yr*%HEAT/CF %HEAT = HDD65/(HDD65+CDD50) where:
18
Heating 5,000 ft2
19
Cooling Regression Equation COOLING = UoAo*24*CDD50/(EFF*CF) + 1.08*ACH*VOLUME*24*CDD50/(EFF*CF) + WALLg*WWR*(N.Area-%)*SHGCn*PFn*SOLARn*(1 - %HEAT)/CF + WALLg*WWR*(E.Area-%)*SHGCe*PFe*SOLARe*(1 - %HEAT)/CF + WALLg*WWR*(S.Area-%)*SHGCs*PFs*SOLARs*(1 – %HEAT)/CF + WALLg*WWR*(W.Area-%)*SHGCw*PFw*SOLARw*(1 – %HEAT)/CF + (Lighting + Plugs + Fans)*(1 – %HEAT) + People*Sensible*55hr.wk*52wk/yr*(1 – %HEAT)/CF
20
Cooling 5,000 ft2
21
Fans FANS = INTERCEPT + (HDD65 + CDD50) + WWR + Ufen + PF + Ufen*WWR + Ufen*PF + (HDD65 + CDD50)*Ufen*PF*WWR
22
Fans 5,000 ft2
23
O.A. Damper Energy Savings 5,000 ft2 and 20,000 ft2
24
AUX 5,000 ft2
25
SWH 5,000 ft2
27
Regression Model Statistics
30
Scalar Ratio for 30% Savings Bin City 5,000ft 2 20,000ft 2 Criteria 1Miami 10 810 2Houston 12 812 3Memphis 12-20-22 12-18-22 14 4Albuquerque 10 14-1814 5Boise 10-14 814 6Helena 12-16 812 7Duluth14 1014 8Fairbanks 12-20-26 1020
31
Results - Tables of Prescriptive Criteria for 8 Climate Zones - Same Format as 90.1 - Roof – Surface reflectance/emittance (0.65 initial/0.86) - WWR – 20% to 40% max. - SHGC – North has separate criteria - Window Orientation – (Zones 1-5) - (A n *SHGC n + A s *SHGC s ) > (A e *SHGC e + A w *SHGC w ) - Exterior Sun Control – Projection Factors (Zones 1-5) - How-To-Use (EN1- to EN-42) - Appendix A (R-values and U-factors)
32
Conclusions - Collaborative Effort - Multiple Organizations - Many Individuals - Challenging - Rewarding
33
Recommendations Encourage Participation in Future Projects Accept the Challenge
34
Acknowledgements SP102 Members Bing Liu - PNNL Leonard Suharli - OC Doug Walden - OC