Download presentation
Presentation is loading. Please wait.
Published byKelley Perry Modified over 9 years ago
1
SWEDE - April 26 th, 2011 - Bastrop Tommy Nylec Austin Energy Fusing and Fault Indicator Applications
2
2 22 2 OverviewOverview Introduction to Austin Energy Purpose of Coordination Concern Unique Situations Engineering and Operational Solutions Future Work and Conclusions
3
3 33 3 Austin Energy Statistics >400,000 Customers >2,800 MW Generation ># mi Transmission 56 Distribution Substations > 10,000 miles of Distribution >1,600 Employees Serve 437 square miles including Austin city limits and neighboring areas Started in 1887
4
4 44 4 Austin Energy Reliability SAIFI =.63 SAIDI = 43.97 CAIDI = 69.86 Challenge ourselves with high goals for reliability indices Consistently in the top performance in the country
5
5 55 5 Coordination Scheme Revisited Need to be simple to interpret for field personnel Must allow for ease of use in design environment Application must hold in > 80% cases Point of coordination determined by maximum available fault current 20% Separation between Total Clear and Minimum Melt curves of devices
6
6 66 6 Austin Energy Fault Current Levels Item of Concern Infinite Bus Calculations for Larger Transformers= 14.5 kA Short Feeders High density of substations System is primarily 12.5 kV Transmission Impedance on larger transformers creates approximately 10 kA Majority of fuses are at > 2kA Typical Unit Installation results in Fault Current < 8.5 kA at Bus
7
7 77 7 Warehouse Inventory Limited space in warehouse and trucks Minimize variety of fuses Standardize applications Reduction of inventory
8
8 88 8 Substation Coordination Most relays set at 360 A Ground Pickup Eases coordination with downstream devices Provides adequate system protection Considerations Some substations do not have this setting Conflicts with some fusing scenarios
9
9 99 9 Unique Scenarios Slugging Required due to presence of extra fuse Fault Level Cheat Sheets Rules of Thumb don’t apply Skip fuse size between devices
10
10 SolutionSolution Keep same fuse ampacity ratings Limit number of fuses with same ampacity but different speeds Allow duplicates in most common sizes Austin Energy Rule of Thumb Must skip 2 fuse sizes between devices
11
11 Feeder Coordination Studies Studies performed on 5 year rotational basis Creates opportunity to revisit coordination scheme Allows adjustment of existing fuses to new scheme Limited inventory restricts solutions to encountered problems
12
12 Fault Indicator Application Fault must pass through equipment Placed accordingly Follow Cooper Application guide
13
13 Austin Energy Standard Traditional Placement: Located at transformer Austin Energy Additional Requirements: Additional F.I.’s located at risers and switchgears
14
14 Installation Methods Concentric Neutral Identified misapplication Changes made to standard to correct In accordance with industry standards
15
15 Fault Indicator Conclusions Provide additional visual cues of fault locations Decrease service restoration time Reduce equipment exposure during restoration practices Economic Impact
16
16 Questions?Questions?
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.