Presentation is loading. Please wait.

Presentation is loading. Please wait.

Chapter 7 AC 800M Hardware Course T314.

Similar presentations


Presentation on theme: "Chapter 7 AC 800M Hardware Course T314."— Presentation transcript:

1 Chapter 7 AC 800M Hardware Course T314

2 Overview Objectives Reference Documentation
AC 800M Hardware Overview Objectives After this chapter you should be able to: Describe the AC 800M hardware components Check the hardware configuration Download and test hardware in online mode Reference Documentation 3BSE IndustrialIT 800xA – Control and I/O AC 800M Controller - Hardware and Operation 3BSE IndustrialIT 800xA – Control and I/O Basic Control Software – Introduction and Configuration 3BSE IndustrialIT 800xA – Control and I/O S800 I/O – General Information and Installation 3BSE IndustrialIT 800xA – Control and I/O S800 I/O – Modules and Termination Units

3 AC 800M Controller Hardware
Overview AC 800M Controller Hardware Optional up to 12 Communication modules CPU S800 I/O RS-232 channels Redundant Ethernet

4 AC 800M Hardware CPU Communication Interfaces I/O Connections
Hardware Redundancy Hardware Configuration Application Download Online Functions

5 Fuses for Modulebus and CEX-bus
CPU CPU PM8xx Compact Flash Card Fuses for Modulebus and CEX-bus CPU Baseplate

6 Choice of speed, memory and availability
CPU Choosing the Right CPU Choice of speed, memory and availability Redundant Redundant PM865 PM864 Redundant PM861 PM860 PM856 32MB 96 MHz SIL2 32MB 96 MHz PM851 16MB 48 MHz 8MB 48 MHz 8MB 24 MHz 8MB 24 MHz

7 Different Processor Units
CPU Different Processor Units Unit Description On-line replacement Redundancy PM851 48 MHz / 8 Mbytes RAM 1 Ethernet port, 1 Serial port and 1 tool port. Application speed is half of PM860. Maximum one CEX bus module. No PM856 2 Ethernet ports, 1 Serial port and 1 tool port. Application speed is half of PM860. PM860 2 Ethernet ports, 1 Serial port and 1 tool port. PM861 48 Mhz / 16 Mbytes RAM 2 Ethernet ports, 1 Serial port and 1 tool port. Singular or redundant. Yes PM861A Same as PM861 but can use redundant communication unit CI854A, CI860 and BC810. PM864 96 Mhz / 32 Mbytes RAM 2 Ethernet ports, 1 Serial port and 1 tool port. Singular or redundant. PM864 is 50% faster than PM861 in executing an application. PM864A Same as PM864 but can use redundant communication unit CI854A, CI860 and BC810. PM865 (PA/HI) 2 Ethernet ports, 1 Serial port and 1 tool port. PM865 can be used in an AC 800M High Integrity system.

8 Start Modes Warm restart Cold restart Reset
CPU Start Modes Warm restart Power Off/On with a battery backed up CPU Applications restart with retain values Cold restart Press Init < 2.5 s Applications restart with cold retain values Reset Press Init > 3 s or until Run LED flashes Applications are deleted !!!

9 CPU Battery Compact Flash card available for non-volatile storage (application and data) Internal External

10 AC 800M Ports CPU Communication Expansion CEX-bus CPU
S800I/O’s on the Electrical ModuleBus RCU link connection Fiber opticale ModuleBus Ethernet ports COM 3-4 ports

11 AC 800M High Integrity Controller
CPU AC 800M High Integrity Controller Added functionality on PM865 includes: Double over voltage protection on internal voltages Additional watchdog timer updated with data from SM810 Increased oscillator supervision Support for S800 I/O High Integrity system Support for SM810 Increased system diagnostic and online self tests

12 AC 800M Hardware CPU Communication Interfaces I/O Connections
Hardware Redundancy Hardware Configuration Application Download Online Functions

13 Communication Interface Units
Overview CI854A CI867 CI865 CI862 CI860 CI858 CI857 CI856 CI855 CI853 PM8xx Modbus TCP Satt I/O TRIO I/O FF HSE DriveBus INSUM S100 I/O MB300 PROFIBUS DP RS232

14 Refer to Manuals for Details
Communication Interface Units Refer to Manuals for Details Unit Description On-line replacement Redundancy CI851 PROFIBUS DP-V0 communication interface unit. Only to use with S200 I/O. No CI853 RS-232C serial CI854 PROFIBUS DP-V1 communication interface unit. Redundant Profibus cabling possible. CI854A Redundant Profibus cabling and redundant interface cards. Yes CI855 MasterBus 300 communication interface unit for the AC 800M. CI856 S100 I/O system communication interface unit. Up to five S100 I/O racks can be connected to one CI856 where each I/O rack can hold up to 20 I/O boards. CI857 INSUM communication interface unit. CI858 Communication interface for ABB Drives using DriveBus CI860 Fieldbus Foundation HSE communication interface unit. Not possible to use in AC800M HI. CI865 Communication interface unit for older Satt I/O systems. CI867 Provides communication with Modbus TCP via Ethernet.

15 Communication Exchange Bus - CEX Bus
Communication Interfaces Communication Exchange Bus - CEX Bus TB850 TK850 with DB25P and TB851 or

16 AC 800M Hardware CPU Communication Interfaces I/O Connections
Hardware Redundancy Hardware Configuration Application Download Online Functions

17 I/O Connections Range of ABB I/O Units

18 I/O Connection Possibilities
I/O Connections I/O Connection Possibilities

19 S800 I/O Connected with ModuleBus
I/O Connections S800 I/O Connected with ModuleBus max. 2.5 meters Base cluster ModuleBus extension Termination TB807 I/O cluster 1 TB820 Optical modem I/O cluster 2 I/O cluster 3 I/O cluster 4 Duplex Simplex max. 15 or 200m max. 15 or 200m

20 S800 I/O Connected with Profibus
I/O Connections S800 I/O Connected with Profibus CI801 Profibus slave with TB810 CI854 Profibus master Base cluster Max. 2.5 meters TB820 Optical modem I/O cluster 1 I/O cluster 2 I/O cluster 3 I/O cluster 4 Duplex Simplex max 15 or 200m max 15 or 200m

21 I/O Connections Limitations of CI801 + = ~ - Due to the PROFIBUS-DPV1 specification it is not possible to always connect 24 I/O modules. The reason is that the S800 I/O system includes more data and user parameters than PROFIBUS-DPV1 can handle. + = ~ - Compact MTU with 2-wire connection More compact, Requires external wiring Mix and match compact and extended termination block to the actual installation Extended MTU with 3-wire connection No external wiring required, i.e. cost saving of external marshalling Compact MTU´s TU810, Screw terminals, RIV 50V TU811, Screw terminals, RIV 250V TU812, 25 pol D-sub, RIV 50V (E.g. Exi) TU814, Crimp snap-in connector, RIV 50V Extended MTU´s TU830, Screw terminals, RIV 50V TU831, Screw terminals, RIV 250V TU835, Screw term, Ext. Fused RIV 50V TU836, Screw term, Ext. Fused RIV 250V (DO820) TU837, Screw term, Ext. Fused RIV 250V (DO820) TU838, Screw term, Ext. Fused RIV 50V

22 Module Termination Units
I/O Connections Module Termination Units + = ~ - Compact Extended + = ~ - Compact MTU with 2-wire connection More compact, Requires external wiring Mix and match compact and extended termination block to the actual installation Extended MTU with 3-wire connection No external wiring required, i.e. cost saving of external marshalling Compact MTU´s TU810, Screw terminals, RIV 50V TU811, Screw terminals, RIV 250V TU812, 25 pol D-sub, RIV 50V (E.g. Exi) TU814, Crimp snap-in connector, RIV 50V Extended MTU´s TU830, Screw terminals, RIV 50V TU831, Screw terminals, RIV 250V TU835, Screw term, Ext. Fused RIV 50V TU836, Screw term, Ext. Fused RIV 250V (DO820) TU837, Screw term, Ext. Fused RIV 250V (DO820) TU838, Screw term, Ext. Fused RIV 50V

23 AC 800M Hardware CPU Communication Interfaces I/O Connections
Hardware Redundancy Hardware Configuration Application Download Online Functions

24 Redundant Processor Unit
Hardware Redundancy Redundant Processor Unit

25 Controller and I/O Redundancy
Hardware Redundancy Controller and I/O Redundancy CEX - bus splitter BC810 Redundant S800 Redundancy Redundant I/O as direct I/O Lin k Cable PROFIBUS CI CI854A Redundant or Singular S800 I/O Optical ModuleBus Cable

26 ModuleBus I/O Redundancy
Hardware Redundancy ModuleBus I/O Redundancy

27 PROFIBUS I/O Redundancy
Hardware Redundancy PROFIBUS I/O Redundancy

28 AC 800M Hardware CPU Communication Interfaces I/O Connections
Hardware Redundancy Hardware Configuration Application Download Online Functions

29 Hardware Configuration
Adding a CPU ModuleBus Scan Cycle Time can be set in the range ms default setting is 0 (as fast as possible) and can load the CPU significantly minimum scan time in practice will be 6 ms

30 Adding Communication Interface
Hardware Configuration Adding Communication Interface

31 Hardware Configuration
Hardware Libraries

32 Adding S800 I/O on ModuleBus
Hardware Configuration Adding S800 I/O on ModuleBus

33 Adding S800 I/O on PROFIBUS
Hardware Configuration Adding S800 I/O on PROFIBUS

34 Hierarchical Dot Notation
Hardware Configuration Hierarchical Dot Notation position number for the CI851 is the physical location on the CEX-bus position for the CI830 is the PROFIBUS node number (set by switches)

35 Hardware Configuration
Settings of I/O Units

36 Hardware Configuration
Adding Compact Flash

37 Changing the IP address
Hardware Configuration Changing the IP address System identity should normally correspond to the setting for Ethernet 1

38 AC 800M Hardware CPU Communication Interfaces I/O Connections
Hardware Redundancy Hardware Configuration Application Download Online Functions

39 Application Download Download

40 Application Download Difference Report

41 Application Download Re-Authentication

42 AC 800M Hardware CPU Communication Interfaces I/O Connections
Hardware Redundancy Hardware Configuration Application Download Online Functions

43 Online Functions Status of I/O-Signals

44 Online Functions Forcing

45 Online Functions SoftController

46


Download ppt "Chapter 7 AC 800M Hardware Course T314."

Similar presentations


Ads by Google