Novec 1230™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid
2
Design Concepts Total Flooding Fire Protection System
Must have an enclosure Agent mixes with atmosphere to protect entire volume No local application Agent mixing performed by nozzles
3
Design Concepts Enclosure Integrity Air leaks effectively sealed
Door fan test is used to determine whether or not integrity exists Procedure in Appendix C of NFPA 2001 Must be performed on all new installations
4
Design Concepts Duration of Protection
“...(Extinguishing concentration) shall be maintained for the specified period of time to allow effective emergency action by trained personnel.” -NFPA 2001, Section 5.6 Hold time is typically 10 minutes, but not standard Refer to local AHJ
5
Design Concepts Discharge Time Must be 10 seconds or less
Rapid extinguishment reduces production of by-products (HF) Per NFPA Software will issue a warning for less than 6 seconds
6
HAZARD SURVEY AND ANALYSIS
7
Perform Hazard Survey Define Hazard: Enclosure boundaries Fuels
Enclosure integrity exists? Fuels Hazard type (Class A, B, C or D) MSDS for chemicals present
8
Required Data Dimensions Ambient Temperature Range
Min. and Max. Occupancy Requirements Normally occupied?
9
Determine Novec 1230 Suitability
Novec 1230 is suitable for: Class A: Fires in ordinary combustibles Class B: Flammable Liquid Fires Class C: Fires involving energized electrical equipment
10
Determine Novec 1230 Suitability
Novec 1230 is NOT suitable for use with: Deep seated fire hazards Metal fires per NFPA 2001, par Certain chemicals capable of rapid oxidation in the absence of air: gunpowder, Reactive metals: sodium, magnesium, etc. Metal hydrides Chemicals capable of undergoing autothermal decomposition
11
Determine Novec 1230 Suitability
Operating temperature range for Novec 1230 equipment is 32°F to 130°F
12
AGENT QUANTITY
13
Extinguishing Concentration
NFPA Class A extinguishing concentration determined as part of witness testing UL 2166 Class B extinguishing concentrations determined by cup burner test Appendix B
14
Minimum Design Concentration
NFPA Class A design concentration EC x 1.2 Class B design concentration MCB x 1.3 Class C design concentration must be at least that for Class A Manual-Only systems design concentration EC x 1.3
15
Minimum Design Concentration
Determined by Hazard Analysis: Class A Hazard: 4.2% (Minimum) Class C Hazard: At least that of Class A: 4.2% Manual-Only systems: 4.6%
16
Minimum Design Concentration
Determined by Hazard Analysis: Class B Hazard: Reference list in manual or call Kidde
17
Minimum Design Concentration
Class B Reference list
18
Minimum Design Concentration
If multiple fuels and/or classifications are present, highest applicable concentration is used
19
Minimum Design Quantity (MDQ)
Equation -or- Table
20
Calculate Volume Dimensions taken during hazard analysis
OK to subtract permanent volume reductions Columns Platforms Do NOT subtract for equipment and moveable objects!
21
Design Temperature To calculate agent quantity, use minimum expected ambient temperature Agent concentration is proportional to air temperature Same quantity of agent will result in a low concentration at low temperatures and a high concentration at high temperatures
22
MDQ Calculation Example
Enclosure is 10 ft. W x 10 ft. L x 10 ft. H Min Ambient Temperature = 70°F Class A Surface Fire Hazard
23
MDQ Calculation Example
Volume = ft.3 s = ( x 70°F) = W = (1000 ft.3 / ) x (4.2% / 100% - 4.2%) = 37.9 lb. - or - Flooding Factor (4.2%, 70°F) = lb./ft.3 W = ft.3 x lb./ft. 3 = 37.9 lb.
24
EXAMPLE PROBLEMS
25
Correct For Pressure Differentials
Must correct if ±11% or more from normal barometric pressure at sea level Approximately ± 3000 feet from sea level Reference Table in NFPA (also in manual) Atmospheric correction Highly pressurized; keep dust out Highly depressurized; keep particles in
26
EXAMPLE PROBLEMS
27
Minimum Design Concentration vs. Adjusted Design Concentration
Minimum Design Concentration is the minimum required per NFPA 2001 Adjusted Design Concentration is the concentration used to calculate the quantity of agent in the cylinder ADC >= MDC
28
AGENT STORAGE CONTAINER LOCATION
29
Agent Storage Container Location
As close as possible to or within the protected enclosure Per NFPA 2001 KIDDE
30
Agent Storage Container Location
Floor loading Container weight plus agent weight KIDDE
31
Agent Storage Container Location
Space requirements Single/Multiple cylinders Space for riser and attached controls KIDDE
32
Agent Storage Container Location
Accessibility Cylinder(s) accessible for maintenance KIDDE
33
Agent Storage Container Location
Storage temperature Balanced or Single Hazard Systems = 32°F to130°F Unbalanced, Multi-Hazard Systems = 60°F to 80°F KIDDE
34
Agent Storage Container Location
Storage temperature If necessary, build an enclosure and control temperature Does not reflect hazard temperature(s) KIDDE
35
Agent Storage Container Location
Classified areas Explosion-proof equipment needed/available? KIDDE
36
Novec 1230™ SERIES SYSTEMS
37
NOVEC 1230 Nozzles Two nozzle types Nozzle sizes
3/8” through 2” 1/4” offered - Non UL and FM All nozzles must be pendant (hanging down)
38
NOVEC 1230 Nozzles 180° Nozzle Placed 6” ± 2” from a wall
Orifices aimed away from the wall 6 - 19” ± 2” from ceiling to orifices As close to center of the wall as possible At least 1/3 No corner placement
39
NOVEC 1230 Nozzles 360° Nozzle Discharges agent in a 360° pattern
Placed as close to center of hazard as possible 6” to 19” from ceiling to orifices
40
Novec 1230 Discharge Discharged as both liquid and vapor
When near obstructions, liquid will “splash” Will effect the mixing of agent in the space due to reduced momentum in discharge.
41
NOVEC 1230 Nozzle Locations
Proximity of nozzles to significant obstructions 6 ft. of clearance between nozzle and wall (or significant obstruction) Additional agent can be discharged to compensate for “losses” on obstructions
42
NOVEC 1230 Nozzle Locations
Proximity of multiple nozzles At least 10 ft. of clearance between nozzles
43
NOVEC 1230 Nozzle Locations
Back-to-Back 180° Nozzles 1 ft. to 2 ft. apart Must face away from each other Nozzles discharge equal quantities
44
NOVEC 1230 Nozzle Locations
For smaller enclosures Recommend using 180 nozzles in order to meet 6 ft. clearance Recommend placing 180 nozzles along longest wall to allow maximum clearance in all directions
45
NOVEC 1230 Nozzle Coverage Tested 35.6 ft. x 35.6 ft. Rectangle
(10.9 m x 10.9m) Actual coverage area defined as rectangle with diagonal, d 180°-d = 39.8 ft.(12.1m) °–d = 25.2 ft.(7.7 m)
46
NOVEC 1230 Nozzle Height Maximum height for single nozzle is 16 ft.
Minimum height 1 ft. for UL Listed systems
47
Nozzle Tiering Use two rows of nozzles to protect enclosures greater than 16 ft. high (note max elevation difference limit) Max 16’ Max 16’
48
Quantity of Nozzles Not always dictated by coverage area
Coverage volume 35.6 ft. x 35.6 ft. x 12 ft. requires 574 lb. of Novec 1230 Will not discharge out of a single nozzle within 10 seconds! Rule of Thumb: Approximately 200 lb. per nozzle
49
Novec 1230™ Engineered System Limits
50
NOVEC 1230 Engineered Systems
Hydraulic flow calculations used as basis of design Allows for unbalanced systems Allows designer to use smaller pipe Use computer software to run flow calculations
51
NOVEC 1230 Piping Network: Tees
Tee Parameters: Tee Orientation Flow Splits Bull Tees Side Tees “10 Pipe Diameters”
52
NOVEC 1230 Piping Network: Tees
Orientation 1 inlet May be horizontal or vertical (bull head tee only) 2 outlets Both must be horizontal
53
NOVEC 1230 Piping Network: Tees
Bull tee flow split Minimum imbalance: 50/50 Maximum imbalance: 75/25 IN OUT
54
NOVEC 1230 Piping Network: Tees
Side tee flow split Minimum imbalance: 65/35 Maximum imbalance: 90/10 SIDE OUTLET ( ) IN RUN OUTLET ( )
55
NOVEC 1230 Piping Network: Tees
“10 Pipe Diameters” Rule: Length of pipe between a tee and a change in direction must be equal to 10 times the nominal diameter of the pipe A change in direction is defined as either an elbow or another tee Must be adhered to before and after the tee Only necessary if the tee feeds agent to separate hazards
56
NOVEC 1230 Piping Network: Layout
Keep network as simple, balanced and short as possible Consider structural members for hanging/bracing Avoid obstructions KIDDE
57
NOVEC 1230 Piping Network: Layout
Maximum allowable elevation difference in system piping (outlet and furthest horizontal pipe run/nozzle, or nozzles) is 20 ft. Max 20’
58
NOVEC 1230 Piping Network: Layout
Percent of Agent in Pipe Percentage of the available agent that is required to fill the pipe network Maximum 100% Affected by agent quantity, pipe lengths and pipe diameters
59
NOVEC 1230 Piping Network: Layout
Percent of Agent Before 1st Tee is 2% Percentage of the available agent that is required to fill the pipe network between the cylinder outlet and the first tee
60
NOVEC 1230 Piping Network: Layout
Arrival Time Imbalance Difference in time between when the agent reaches the first nozzle and when it reaches the last nozzle Max 1.0 seconds (Subject to change) Runout Time Imbalance Similar to Arrival Time Imbalance, but refers to when agent runs out at each nozzle Max 3.2 seconds (Subject to change)
61
NOVEC 1230 Piping Network: Pipe Sizes
Pipe sizes are estimated by the software based on quantity of agent designated to each nozzle Flow rate = lb. of Novec 1230 in branch / 10 seconds Pipe estimating table in DIOM manual (Table 3-6) Some manual changes may be required
62
NOVEC 1230 Piping Network: Pipe Sizes
Pipe sizes 1/2” through 6” are listed/approved Largest Nozzle Size is 2” Smaller than 1/2” is available in software, but not listed/approved Smallest Nozzle Size is 3/8” 1/4” nozzle is available (Unapproved systems only)
63
NOVEC 1230 Piping Network: Nozzles
Minimum Nozzle Pressure 91 psig (per UL 2166 Requalification)
64
NOVEC 1230 Piping Network: Hydraulic Calculation
Enter: Enclosure info Agent quantity Agent Source Pipe network Run Main Calculations Verify system acceptance
65
Hints, Tips and Other Considerations
66
Multiple Systems / Single Hazard
If enclosure is large, consider using: Multiple, modular NOVEC 1230 systems, which will discharge simultaneously, located throughout the hazard However - With 100% Agent in Pipe limit - Novec flows well in complex pipe networks.
67
Single System / Multiple Hazards
If protecting more than four enclosures that are not connected, consider: Separate NOVEC 1230 systems
68
Agent Migration If protecting a single space with multiple nozzles, each nozzle should discharge the quantity of agent required by the nozzle’s design coverage area Maximum of 5% of the required agent may be discharged by a nozzle protecting an adjacent area
69
Designing for Multiple Hazards
For more than one hazard, design with an adjusted concentration of 4.2% or higher Extra agent will make flow splits a lot easier NOTE: Still use 4.2% as minimum
70
Tee Design Factor NFPA 2001 5-5.3.1 Starting from each hazard, count:
Every tee within the hazard that splits to a separate hazard Each tee between entry point to hazard and the agent source (not including tees in a manifold) Reference Table in NFPA 2001 for additional agent required
71
Tee Design Factor Example
72
Tee Design Factor Example
Maximum tee count is 6 From NFPA 2001, Table , a tee count of 6 requires a 0.02 (2%) safety factor