Presentation is loading. Please wait.

Presentation is loading. Please wait.

MAGNA3 vs. MAGNA.

Similar presentations


Presentation on theme: "MAGNA3 vs. MAGNA."— Presentation transcript:

1 MAGNA3 vs. MAGNA

2 MAGNA3 vs MAGNA MAGNA3 MAGNA

3 MAGNA3 vs MAGNA Range 32 F (N) 1.25” 40 F (N) 1.5” 50 F (N) 2”
2.5” 80 F 3” 100 F 4” xx-60 xx-80 xx-100 xx-120 xx-150 xx-180 MAGNA3 with Dual Head Option MAGNA3 “Old” MAGNA

4 50 100 150 200 250 300 350 400 450 500 600 550 10 20 30 40 60 Magna3 Old Magna

5 Technical data MAGNA3 “Old” MAGNA Max. Head 60 Ft. 40 Ft. Max. Flow
550 GPM (Dual or Parallel) 170 GPM Max. Power 1550 W 900W Connections 1" to 4" 1" to 2.5" Liquid Temperature 14F to 230F 35F to 230F Ambient Temperature 32F to 104F Nominal Pressure 145 PSI Cast Iron Pump House Stainless Pump House

6 Control Modes MAGNA3 “Old” MAGNA AUTOADAPT ● FLOWADAPT ○ FLOWLIMIT
Proportional Pressure Constant Pressure Constant Speed Constant Temperature Automatic Night Setback

7 Color TFT Screen and Buttons
Readings and Settings MAGNA3 “Old” MAGNA Control panel and display Color TFT Screen and Buttons Button and LEDs Operating status Control Mode Pump performance Warning and alarm Heat energy meter Work log history Dry-running detection Status menu Requires R100 Fitted modules (CIM module connected to the pump) Requires CIU and GeniModule Time and date Pump identification

8 Interface MAGNA3 “Old” MAGNA Display type Color TFT Screen LEDs
Buttons Silicone push-buttons One silicone push-button Descriptions Graphics and text Symbols Grundfos Eye (Green), Running Grundfos Eye (Yellow), Warning Grundfos Eye (Red), Alarm

9 Inputs and Outputs MAGNA3 “Old” MAGNA Analog inputs 1 x Analog input
(0-10V/4-20 mA) Requires GeniModule 1 x Analog Input (0-10V) Relay outputs 2 x relay outputs 1 Relay output Digital inputs 3 x digital inputs 1 Digital Input

10 Wireless communication
Dual Head Pump / Two Pump Operation MAGNA3 “Old” MAGNA Size and no. of dual head pumps 2.5" to 4" 3 models Communication between dual head pumps Wireless communication Multi-pump system Alternating operation Back-up operation Parallel operation

11 Communications and Monitoring
MAGNA3 “Old” MAGNA Hand held pump control Wireless Grundfos GO remote control by means of : iPod, iPad, iPhone, Android phone R100 BUS communication Wireless GENIair incorporated Optional CIM cards Requires GeniModule and CIU

12 Insulation Shells MAGNA3 “Old” MAGNA Heating
Shell for heating applications are delivered as standard for single pumps (part of the package). Cooling For cooling applications, apply silicone sealant to standard insulation shell per instructions

13 Thank you for your time


Download ppt "MAGNA3 vs. MAGNA."